Sensor (clamp-on ultrasonic flowmeter) · Modbus register map

Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) Modbus register map

Updated 17 November 2026

Short answer

The Prosonic Flow W 400 is Endress+Hauser's clamp-on ultrasonic time-of-flight flowmeter. Its Modbus RS485 interface gives every operating parameter a fixed register. This map covers what an integrator needs: flow, velocity, sound velocity, temperature, signal diagnostics, three totalizers and their controls, units, diagnostics and the Modbus settings.

This page lists 60 Modbus registers for the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.

Manufacturer
Endress+Hauser
Model
Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)
Equipment type
Sensor (clamp-on ultrasonic flowmeter)
Registers
60 (35 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
247
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Valid from device firmware 01.00.zz
Also known as
Prosonic Flow W 400
Source document
Description of Device Parameters Proline Prosonic Flow W 400 Modbus RS485 · GP01207D/06/EN/01.24-00 · rev. 2024-05-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)

Integration in brief

Read volume flow (wire 2006) and totalizer 1 (wire 2609) as CDAB floats with function 03 or 04; check actual diagnostics (wire 2731) and signal strength for clamp-on health. Reset totalizers through the totalizer control registers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2006Volume flowFLOAT32 CDABVolume flowRead
HR 2014Flow velocityFLOAT32 CDABFlow velocityRead
HR 2609Totalizer 1 valueFLOAT32 CDABTotalizer 1 valueRead
HR 2102Volume flow unitUINT16Volume flow unit codeRead/write
HR 4958Signal strengthFLOAT32 CDABSignal strengthRead
HR 2731Actual diagnosticsUINT16Active diagnosticRead
HR 2607Totalizer 1 controlUINT16Totalizer 1 controlRead/write

Enable Modbus control & writes

Modbus settings are under Expert > Communication > Modbus configuration. Fieldbus writing access (register 6807) must be Read + write for Modbus writes.

Byte order & addressing

Network setup

Watch out for

Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

60 of 60 shown
Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2006doc 2007 to 2008Volume flowMeasured volume flow in the volume flow unit.FLOAT32CDABRead
HR2008doc 2009 to 2010Mass flowMass flow from volume flow and density.FLOAT32CDABRead
HR2010doc 2011 to 2012DensityDensity used for the mass flow calculation.FLOAT32CDABRead
HR2012doc 2013 to 2014Sound velocityMeasured sound velocity of the fluid.FLOAT32CDABRead
HR2014doc 2015 to 2016Flow velocityAverage flow velocity in the pipe.FLOAT32CDABRead
HR2016doc 2017 to 2018TemperatureFluid temperature used by the device.FLOAT32CDABRead
HR2100doc 2101Mass flow unitUINT16Read/write0 = g/s; 1 = g/min; 2 = g/h; 3 = g/d; 4 = kg/s; 5 = kg/min; 6 = kg/h; 7 = kg/d; 8 = t/s; 9 = t/min; 10 = t/h; 11 = t/d; 12 = oz/s; 13 = oz/min; 14 = oz/h; 15 = oz/d; 16 = lb/s; 17 = lb/min; 18 = lb/h; 19 = lb/d; 20 = STon/s; 21 = STon/min; 22 = STon/h; 23 = STon/d
HR2101doc 2102Mass unitUINT16Read/write50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon
HR2102doc 2103Volume flow unitUINT16Read/write0 = cm³/s; 1 = cm³/min; 2 = cm³/h; 3 = cm³/d; 4 = dm³/s; 5 = dm³/min; 6 = dm³/h; 7 = dm³/d; 8 = m³/s; 9 = m³/min; 10 = m³/h; 11 = m³/d; 12 = ml/s; 13 = ml/min; 14 = ml/h; 15 = ml/d; 16 = l/s; 17 = l/min; 18 = l/h; 19 = l/d; 20 = hl/s; 21 = hl/min; 22 = hl/h; 23 = hl/d; 24 = Ml/s; 25 = Ml/min; 26 = Ml/h; 27 = Ml/d; 32 = af/s; 33 = af/min; 34 = af/h; 35 = af/d; 36 = ft³/s; 37 = ft³/min; 38 = ft³/h; 39 = ft³/d; 40 = fl oz/s (us); 41 = fl oz/min (us); 42 = fl oz/h (us); 43 = fl oz/d (us); 44 = gal/s (us); 45 = gal/min (us); 46 = gal/h (us); 47 = gal/d (us); 48 = Mgal/s (us); 49 = Mgal/min (us); 50 = Mgal/h (us); 51 = Mgal/d (us); 52 = bbl/s (us;liq.); 53 = bbl/min (us;liq.); 54 = bbl/h (us;liq.); 55 = bbl/d (us;liq.); 56 = bbl/s (us;beer); 57 = bbl/min (us;beer); 58 = bbl/h (us;beer); 59 = bbl/d (us;beer); 60 = bbl/s (us;oil); 61 = bbl/min (us;oil); 62 = bbl/h (us;oil); 63 = bbl/d (us;oil); 64 = bbl/s (us;tank); 65 = bbl/min (us;tank); 66 = bbl/h (us;tank); 67 = bbl/d (us;tank); 68 = gal/s (imp); 69 = gal/min (imp); 70 = gal/h (imp); 71 = gal/d (imp); 72 = Mgal/s (imp); 73 = Mgal/min (imp); 74 = Mgal/h (imp); 75 = Mgal/d (imp); 76 = bbl/s (imp;beer); 77 = bbl/min (imp;beer); 78 = bbl/h (imp;beer); 79 = bbl/d (imp;beer); 80 = bbl/s (imp;oil); 81 = bbl/min (imp;oil); 82 = bbl/h (imp;oil); 83 = bbl/d (imp;oil); 88 = kgal/s (us); 89 = kgal/min (us); 90 = kgal/h (us); 91 = kgal/d (us)
HR2103doc 2104Volume unitUINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us)
HR2106doc 2107Density unitUINT16Read/write0 = g/cm³; 2 = kg/dm³; 3 = kg/l; 4 = kg/m³; 5 = SD4°C; 6 = SD15°C; 7 = SD20°C; 8 = SG4°C; 9 = SG15°C; 10 = SG20°C; 11 = lb/ft³; 12 = lb/gal (us); 13 = lb/bbl (us;liq.); 14 = lb/bbl (us;beer); 15 = lb/bbl (us;oil); 16 = lb/bbl (us;tank); 17 = lb/gal (imp); 18 = lb/bbl (imp;beer); 19 = lb/bbl (imp;oil); 21 = g/m³
HR2108doc 2109Temperature unitUINT16Read/write0 = °C; 1 = K; 2 = °F; 3 = °R
HR2546doc 2547Device IDFour-digit hex device type code.UINT16Read
HR2589doc 2590 to 2591Preset value 1Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2591doc 2592 to 2593Preset value 2Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2593doc 2594 to 2595Preset value 3Start value used by the preset totalizer commands.FLOAT32CDABRead/write
HR2599doc 2600Velocity unitUINT16Read/write20 = ft/s; 21 = m/s
HR2600doc 2601Totalizer 1 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Mass flow; 2 = Volume flow
HR2604doc 2605Totalizer 1 operation modeUINT16Read/write0 = Net; 1 = Forward; 2 = Reverse
HR2605doc 2606Totalizer 1 failure behaviorTotalizer behaviour while a device alarm is active.UINT16Read/write0 = Hold; 1 = Continue; 2 = Last valid value + continue
HR2607doc 2608Totalizer 1 controlWrite to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR2608doc 2609Reset all totalizersWrite 1 to reset all totalizers and keep counting.UINT16Read/write0 = Cancel; 1 = Reset + totalize
HR2609doc 2610 to 2611Totalizer 1 valueCurrent totalizer count in the totalizer unit.FLOAT32CDABRead
HR2611doc 2612 to 2613Totalizer 1 overflowNumber of overflows, -32000 to 32000.FLOAT32CDABRead
HR2731doc 2732Actual diagnosticsCurrently active diagnostic event as an integer code.UINT16Read
HR2733doc 2734Previous diagnosticsLast diagnostic event before the current one.UINT16Read
HR2735doc 2736Diagnostics 1Entry 1 of the diagnostic list.UINT16Read
HR2737doc 2738Diagnostics 2Entry 2 of the diagnostic list.UINT16Read
HR2739doc 2740Diagnostics 3Entry 3 of the diagnostic list.UINT16Read
HR2741doc 2742Diagnostics 4Entry 4 of the diagnostic list.UINT16Read
HR2743doc 2744Diagnostics 5Entry 5 of the diagnostic list.UINT16Read
HR2800doc 2801Totalizer 2 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Mass flow; 2 = Volume flow
HR2804doc 2805Totalizer 2 operation modeUINT16Read/write0 = Net; 1 = Forward; 2 = Reverse
HR2805doc 2806Totalizer 2 failure behaviorTotalizer behaviour while a device alarm is active.UINT16Read/write0 = Hold; 1 = Continue; 2 = Last valid value + continue
HR2807doc 2808Totalizer 2 controlWrite to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR2809doc 2810 to 2811Totalizer 2 valueCurrent totalizer count in the totalizer unit.FLOAT32CDABRead
HR2811doc 2812 to 2813Totalizer 2 overflowNumber of overflows, -32000 to 32000.FLOAT32CDABRead
HR3000doc 3001Totalizer 3 assign process variableWhich flow the totalizer adds up.UINT16Read/write0 = Off; 1 = Mass flow; 2 = Volume flow
HR3004doc 3005Totalizer 3 operation modeUINT16Read/write0 = Net; 1 = Forward; 2 = Reverse
HR3005doc 3006Totalizer 3 failure behaviorTotalizer behaviour while a device alarm is active.UINT16Read/write0 = Hold; 1 = Continue; 2 = Last valid value + continue
HR3007doc 3008Totalizer 3 controlWrite to reset, preset, hold or run the totalizer.UINT16Read/write0 = Totalize; 1 = Reset + totalize; 2 = Preset + hold; 3 = Reset + hold; 4 = Preset + totalize; 5 = Hold
HR3009doc 3010 to 3011Totalizer 3 valueCurrent totalizer count in the totalizer unit.FLOAT32CDABRead
HR3011doc 3012 to 3013Totalizer 3 overflowNumber of overflows, -32000 to 32000.FLOAT32CDABRead
HR4480doc 4481Device revisionFour-digit hex device revision.UINT16Read
HR4550doc 4551 to 4552Acceptance rateShare of accepted measurements, 0-100 %.FLOAT32CDAB%Read
HR4603doc 4604Totalizer 1 unitEngineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 111 = Mft³; 251 = None
HR4604doc 4605Totalizer 2 unitEngineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 111 = Mft³; 251 = None
HR4605doc 4606Totalizer 3 unitEngineering unit of the totalizer.UINT16Read/write0 = cm³; 1 = dm³; 2 = m³; 3 = ml; 4 = l; 5 = hl; 6 = Ml Mega; 8 = af; 9 = ft³; 10 = fl oz (us); 11 = gal (us); 12 = Mgal (us); 13 = bbl (us;liq.); 14 = bbl (us;beer); 15 = bbl (us;oil); 16 = bbl (us;tank); 17 = gal (imp); 18 = Mgal (imp); 19 = bbl (imp;beer); 20 = bbl (imp;oil); 22 = kgal (us); 23 = Mft³; 50 = g; 51 = kg; 52 = t; 53 = oz; 54 = lb; 55 = STon; 111 = Mft³; 251 = None
HR4909doc 4910Bus addressModbus slave address, 1-247.UINT16Read/write
HR4911doc 4912BaudrateUINT16baudRead/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200; 8 = 230400
HR4912doc 4913Data transfer modeUINT16Read/write0 = RTU; 1 = ASCII
HR4913doc 4914Parity0 = Even, 1 = Odd; codes 2/3 (no parity) conflict in the manual.UINT16Read/write
HR4914doc 4915Byte orderByte sequence for floats and strings (factory 1-0-3-2).UINT16Read/write0 = 0-1-2-3; 1 = 3-2-1-0; 2 = 2-3-0-1; 3 = 1-0-3-2
HR4915doc 4916 to 4917Telegram delayReply delay after a request, 0-100 ms.FLOAT32CDABmsRead/write
HR4919doc 4920Failure modeValue sent for measured values while a diagnostic is active.UINT16Read/write1 = Last valid value; 255 = NaN value
HR4958doc 4959 to 4960Signal strengthUltrasonic signal strength (diagnostic).FLOAT32CDABRead
HR4982doc 4983 to 4984Signal to noise ratioFLOAT32CDABRead
HR6806doc 6807Fieldbus writing accessAllow or block writes over Modbus.UINT16Read/write0 = Read + write; 1 = Read only
HR6816doc 6817Device resetRestart the device or return it to delivery settings.UINT16Read/write0 = Cancel; 1 = Restart device; 2 = To delivery settings; 25 = Restore S-DAT backup
HR22771doc 22772 to 22773TurbulenceTurbulence indicator of the flow profile.FLOAT32CDABRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)

What Modbus registers does the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) have?

This map lists 60 registers: 60 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers in the Modbus Application Protocol form and equates them with Modicon 3XXXX/4XXXX numbers (its own example: 2007 = 32007); the scan-list parameter calls register addresses 1-based. Subtract 1 on the wire: volume flow at register 2007 is requested at 2006.

What byte order does the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)?

Start with HR 2006 Volume flow (Volume flow); HR 2014 Flow velocity (Flow velocity); HR 2609 Totalizer 1 value (Totalizer 1 value); HR 2102 Volume flow unit (Volume flow unit code); HR 4958 Signal strength (Signal strength); HR 2731 Actual diagnostics (Active diagnostic); HR 2607 Totalizer 1 control (Totalizer 1 control).

How do I enable Modbus control of the Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)?

Modbus settings are under Expert > Communication > Modbus configuration. Fieldbus writing access (register 6807) must be Read + write for Modbus writes.

Where is the official Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485) Modbus documentation?

The source is Description of Device Parameters Proline Prosonic Flow W 400 Modbus RS485 (GP01207D/06/EN/01.24-00), revision 2024-05-15, published free by Endress+Hauser at https://bdih-download.endress.com/file/005056A5E3831EEF84BF247676F6F971/GP01207DEN_0124-00.pdf.

More Endress+Hauser Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Description of Device Parameters Proline Prosonic Flow W 400 Modbus RS485 · GP01207D/06/EN/01.24-00 · rev. 2024-05-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.