Energy meter · Modbus register map
inepro Metering 4PU / 4PS three-phase energy meter Modbus register map
Updated 17 November 2026
The 4PU and 4PS are inepro's MID three-phase DIN-rail energy meters with RS485 Modbus RTU, M-bus and Bluetooth options. Values are IEEE 754 floats sent high word first, read with function 03 from hex blocks 4000h (setup), 5000h (live values) and 6000h (energy, four tariffs and quadrant reactive energy). This map covers per-phase voltages, currents, powers, power factor, frequency, energy counters and the writable communication, tariff, pulse and display settings.
This page lists 117 Modbus registers for the inepro Metering 4PU / 4PS three-phase energy meter — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.
- Manufacturer
- inepro Metering
- Model
- 4PU / 4PS three-phase energy meter
- Equipment type
- Energy meter
- Registers
- 117 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 4PU, 4PS, inepro 4PU, inepro 4PS
Integration notes: inepro Metering 4PU / 4PS three-phase energy meter
Wire RS485 A/B to terminals 7 and 8, poll unit 1 at 9600 baud 8E1 with function 03 and decode values as high-word-first floats. Live values sit at 5002h-5037h, energy at 6000h-6090h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20482 | L1 Voltage | FLOAT32 ABCD | L1 voltage | Read |
| HR 20492 | L1 Current | FLOAT32 ABCD | L1 current | Read |
| HR 20498 | Total active power | FLOAT32 ABCD | Total active power (kW) | Read |
| HR 20522 | Power factor | FLOAT32 ABCD | Power factor | Read |
| HR 20488 | Grid frequency | FLOAT32 ABCD | Grid frequency | Read |
| HR 24588 | Forward active energy | FLOAT32 ABCD | Forward (import) active energy | Read |
| HR 24600 | Reverse active energy | FLOAT32 ABCD | Reverse (export) active energy | Read |
Enable Modbus control & writes
No enable step is described for Modbus. Set ID, baud and parity on the display menus or over Modbus at 4003h/4004h/4011h.
Byte order & addressing
- Addresses are hex: 5012h is decimal 20498 on the wire.
- Floats are ABCD (high word first).
- Baud rate is written as a code (6 = 9600), not the number.
- Check that 4026h reads 1 (standard); the integer format is undocumented.
Network setup
- Defaults: Modbus ID 1, 9600 baud, 8 data bits, even parity, 1 stop bit.
- Baud can be changed to 300-115200; parity to none or odd; data and stop bits are fixed.
- Fit a 120 ohm / 0.25 W resistor across terminals 7 and 8 at the meter when testing through an RS485 converter.
Watch out for
- Total active energy (6000h) follows the combination code; read forward (600Ch) and reverse (6018h) for import and export.
inepro Metering 4PU / 4PS three-phase energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 16387doc 4003 | Modbus ID | Slave address 1-247 (default 1). | INT16 | Read/write | ||||
| HR | 16388doc 4004 | Baud rate | Baud rate code. | INT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | |||
| HR | 16389doc 4005 | Protocol version | FLOAT32 | ABCD | Read | ||||
| HR | 16391doc 4007 | Software version | FLOAT32 | ABCD | Read | ||||
| HR | 16393doc 4009 | Hardware version | FLOAT32 | ABCD | Read | ||||
| HR | 16395doc 400B | Meter amps | Current rating of the meter. | INT16 | A | Read | |||
| HR | 16397doc 400D | S0 output rate | Pulse output rate; write both registers with function 16. | FLOAT32 | ABCD | imp/kWh | Read/write | ||
| HR | 16399doc 400F | Combination code | How total energy combines forward and reverse. | INT16 | Read/write | 1 = Forward only; 2 = Reverse only; 3 = Forward + reverse; 4 = Import - export; 5 = Import - export (10) | |||
| HR | 16401doc 4011 | Parity setting | INT16 | Read/write | 1 = Even; 2 = None; 3 = Odd | ||||
| HR | 16406doc 4016 | Power down counter | Number of power losses; write 0 to reset. | INT16 | Read/write | ||||
| HR | 16407doc 4017 | Present quadrant | Present operating quadrant. | INT16 | Read | ||||
| HR | 16408doc 4018 | L1 quadrant | INT16 | Read | |||||
| HR | 16409doc 4019 | L2 quadrant | INT16 | Read | |||||
| HR | 16410doc 401A | L3 quadrant | INT16 | Read | |||||
| HR | 16417doc 4021 | Pulse width | S0 pulse width, 2-99 ms. | INT16 | ms | Read/write | |||
| HR | 16422doc 4026 | Data type setting | Value encoding; this map assumes 1 (standard, floats). | INT16 | Read/write | 1 = Standard; 2 = Integer | |||
| HR | 16434doc 4032 | Screen direction | INT16 | Read/write | 0 = Standard; 1 = Turned 180 degrees | ||||
| HR | 16435doc 4033 | OBIS code on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 20482doc 5002 | L1 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20484doc 5004 | L2 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20486doc 5006 | L3 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20488doc 5008 | Grid frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 20492doc 500C | L1 Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20494doc 500E | L2 Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20496doc 5010 | L3 Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20498doc 5012 | Total active power | FLOAT32 | ABCD | kW | Read | |||
| HR | 20500doc 5014 | L1 Active power | FLOAT32 | ABCD | kW | Read | |||
| HR | 20502doc 5016 | L2 Active power | FLOAT32 | ABCD | kW | Read | |||
| HR | 20504doc 5018 | L3 Active power | FLOAT32 | ABCD | kW | Read | |||
| HR | 20506doc 501A | Total reactive power | FLOAT32 | ABCD | kvar | Read | |||
| HR | 20508doc 501C | L1 Reactive power | FLOAT32 | ABCD | kvar | Read | |||
| HR | 20510doc 501E | L2 Reactive power | FLOAT32 | ABCD | kvar | Read | |||
| HR | 20512doc 5020 | L3 Reactive power | FLOAT32 | ABCD | kvar | Read | |||
| HR | 20514doc 5022 | Total apparent power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 20516doc 5024 | L1 Apparent power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 20518doc 5026 | L2 Apparent Power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 20520doc 5028 | L3 Apparent Power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 20522doc 502A | Power factor | FLOAT32 | ABCD | Read | ||||
| HR | 20524doc 502C | L1 Power factor | FLOAT32 | ABCD | Read | ||||
| HR | 20526doc 502E | L2 Power factor | FLOAT32 | ABCD | Read | ||||
| HR | 20528doc 5030 | L3 Power factor | FLOAT32 | ABCD | Read | ||||
| HR | 20530doc 5032 | L1-L2 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20532doc 5034 | L1-L3 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20534doc 5036 | L2-L3 Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 24576doc 6000 | Total active energy | Forward and reverse combined per the combination code (400Fh). | FLOAT32 | ABCD | kWh | Read | ||
| HR | 24578doc 6002 | T1 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24580doc 6004 | T2 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24582doc 6006 | L1 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24584doc 6008 | L2 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24586doc 600A | L3 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24588doc 600C | Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24590doc 600E | T1 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24592doc 6010 | T2 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24594doc 6012 | L1 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24596doc 6014 | L2 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24598doc 6016 | L3 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24600doc 6018 | Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24602doc 601A | T1 Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24604doc 601C | T2 Reverse Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24606doc 601E | L1 Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24608doc 6020 | L2 Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24610doc 6022 | L3 Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24612doc 6024 | Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24614doc 6026 | T1 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24616doc 6028 | T2 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24618doc 602A | L1 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24620doc 602C | L2 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24622doc 602E | L3 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24624doc 6030 | Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24626doc 6032 | T1 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24628doc 6034 | T2 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24630doc 6036 | L1 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24632doc 6038 | L2 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24634doc 603A | L3 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24636doc 603C | Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24638doc 603E | T1 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24640doc 6040 | T2 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24642doc 6042 | L1 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24644doc 6044 | L2 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24646doc 6046 | L3 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24648doc 6048 | Tariff | Active tariff. | INT16 | Read/write | 1 = T1; 2 = T2; 3 = T3; 4 = T4 | |||
| HR | 24649doc 6049 | Resettable day counter | Write 0.0 with function 16 to reset. | FLOAT32 | ABCD | kWh | Read/write | ||
| HR | 24651doc 604B | T3 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24653doc 604D | T4 Total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24655doc 604F | T3 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24657doc 6051 | T4 Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24659doc 6053 | T3 Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24661doc 6055 | T4 Reverse Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24663doc 6057 | T3 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24665doc 6059 | T4 Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24667doc 605B | T3 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24669doc 605D | T4 Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24671doc 605F | T3 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24673doc 6061 | T4 Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24675doc 6063 | Imp. Inductive reactive energy in Q1 (total) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24677doc 6065 | Imp. Inductive reactive energy in Q1 (T1) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24679doc 6067 | Imp. Inductive reactive energy in Q1 (T2) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24681doc 6069 | Imp. Inductive reactive energy in Q1 (T3) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24683doc 606B | Imp. Inductive reactive energy in Q1 (T4) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24685doc 606D | Imp. capacitive reactive energy in Q2 (total) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24687doc 606F | Imp. capacitive reactive energy in Q2 (T1) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24689doc 6071 | Imp. capacitive reactive energy in Q2 (T2) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24691doc 6073 | Imp. capacitive reactive energy in Q2 (T3) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24693doc 6075 | Imp. capacitive reactive energy in Q2 (T4) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24695doc 6077 | Exp. Inductive reactive energy in Q3 (total) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24697doc 6079 | Exp. Inductive reactive energy in Q3 (T1) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24699doc 607B | Exp. Inductive reactive energy in Q3 (T2) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24701doc 607D | Exp. Inductive reactive energy in Q3 (T3) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24703doc 607F | Exp. Inductive reactive energy in Q3 (T4) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24705doc 6081 | Exp. capacitive reactive energy in Q4 (total) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24707doc 6083 | Exp. capacitive reactive energy in Q4 (T1) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24709doc 6085 | Exp. capacitive reactive energy in Q4 (T2) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24711doc 6087 | Exp. capacitive reactive energy in Q4 (T3) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24713doc 6089 | Exp. capacitive reactive energy in Q4 (T4) | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24715doc 608B | Resettable day counter L1 | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24717doc 608D | Resettable day counter L2 | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24719doc 608F | Resettable day counter L3 | FLOAT32 | ABCD | kWh | Read |
Notes on this map
- The PDF is inepro's own user manual (hosted on inepro's website CDN).
- 'Float ABCD' = IEEE 754 32-bit float, high word first; 'Signed' rows are 16-bit integers.
- Data type setting (4026h) offers 1 = standard or 2 = integer. The manual does not describe the integer encoding, and does not say which setting is the factory default; this map assumes 1 (standard), under which the map prints every value as Float ABCD.
- The quadrant reactive energy rows (6063h-6089h) print the unit kWh; they are reactive energies and are listed here in kvarh.
- Left out: serial number, meter code, checksums, active status word and CT ratio 400Ch (HEX), LCD cycle time and voltage/current rows 5000h/500Ah (marked 'PRO series only'), current direction (ASCII), error code 4015h (no code list), CT ratio 401Fh (two-word primary/secondary format, e.g. 9995/5) and pulse type 4022h (typed HEX in the read map, Signed in the write table).
- The day-counter write row prints length 1, but its example frame writes 2 registers with function 16; it is listed as a 2-register float.
- Power is in kW/kvar/kVA and energy in kWh/kvarh, as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the inepro Metering 4PU / 4PS three-phase energy meter
What Modbus registers does the inepro Metering 4PU / 4PS three-phase energy meter have?
This map lists 117 registers: 117 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the inepro Metering 4PU / 4PS three-phase energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints hex addresses that go into the request unchanged; the manual's write examples are 01 06 4003 000A (set Modbus ID) and 01 06 6048 0002 (set tariff). So 5012h (total active power) is wire address 20498.
What byte order does the inepro Metering 4PU / 4PS three-phase energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the inepro Metering 4PU / 4PS three-phase energy meter?
Start with HR 20482 L1 Voltage (L1 voltage); HR 20492 L1 Current (L1 current); HR 20498 Total active power (Total active power (kW)); HR 20522 Power factor (Power factor); HR 20488 Grid frequency (Grid frequency); HR 24588 Forward active energy (Forward (import) active energy); HR 24600 Reverse active energy (Reverse (export) active energy).
How do I enable Modbus control of the inepro Metering 4PU / 4PS three-phase energy meter?
No enable step is described for Modbus. Set ID, baud and parity on the display menus or over Modbus at 4003h/4004h/4011h.
Where is the official inepro Metering 4PU / 4PS three-phase energy meter Modbus documentation?
The source is 4PU and 4PS Series MID Three phase energy meter - User manual (Version 1.03), revision 2025, published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/6877702cbeaaaf598808a327_4PU%204PS%20Full%20user%20manual%20V1.03.pdf.
More inepro Metering Modbus register maps
- Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Energy meter
inepro Metering PRO380-Mod three-phase energy meter
PRO380-Mod and PRO380-Mod CT (RS485 Modbus RTU), current register map from PRO380 user manual version 2.18-8.
Also known as: PRO380 Mod, PRO380-Mod CT, PRO380-MOD, inepro PRO380, PRO380 MID
Other power & energy meters register maps
- Power meter (power quality analyser)
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
UMG 604 (non-PRO) from firmware release 2.x, per address list 1.033.033.g.
Also known as: UMG604, UMG 604-E, UMG 604-EP, Janitza UMG 604 (non-PRO) - Energy meter
KEBA KeContact E10 smart energy meter (Modbus)
KEBA KeContact E10 energy meter (companion meter for KeContact wallboxes and PV home systems), register list v1.00 (03.2024).
Also known as: E10, KEBA E10, KeContact E10 - Energy meter
Legrand Energy meter 4 120 68 (RS-485 Modbus)
Legrand energy meter cat. no. 4 120 68 with RS-485 Modbus RTU, per Modbus table F02230EN-01.
Also known as: 412068, 4 120 68, Legrand 412068 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110
All power & energy meters Modbus register maps →