Energy meter · Modbus register map
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus register map
Updated 17 November 2026
The PRO2-Mod is inepro's single-phase MID DIN-rail energy meter with an RS485 Modbus RTU port (this is the older PRO line, not the 2026 PRO1/PRO2 template). Every measurement is an IEEE 754 float, high word first, read with function 03 from hex blocks 4000h (setup), 5000h (live values) and 6000h (energy). The map covers voltage, current, power, power factor, frequency, total/tariff energy and the writable ID, baud, parity, S0, tariff and combination-code settings.
This page lists 40 Modbus registers for the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.
- Manufacturer
- inepro Metering
- Model
- PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
- Equipment type
- Energy meter
- Registers
- 40 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy
Integration notes: inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
Wire RS485 to terminals 10 and 11, poll unit 1 at 9600 baud 8E1 with function 03 and decode each value as a high-word-first float. Live values sit at 5000h-502Bh, energy at 6000h-604Ah.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20480 | Voltage | FLOAT32 ABCD | Voltage | Read |
| HR 20490 | Current | FLOAT32 ABCD | Current | Read |
| HR 20498 | Total active power | FLOAT32 ABCD | Total active power (kW) | Read |
| HR 20522 | Power factor | FLOAT32 ABCD | Power factor | Read |
| HR 20488 | Grid frequency | FLOAT32 ABCD | Grid frequency | Read |
| HR 24588 | Forward active energy | FLOAT32 ABCD | Forward (import) active energy | Read |
| HR 24600 | Reverse active energy | FLOAT32 ABCD | Reverse (export) active energy | Read |
Enable Modbus control & writes
Modbus is on the -Mod version only. Set the ID in Program mode 2 and baud/parity in Program mode 3 (4-digit password, default 0000), or over Modbus at 4003h/4004h/4011h.
Byte order & addressing
- Addresses are hex: 5012h is decimal 20498 on the wire.
- Floats are ABCD (high word first).
- Power is in kW/kvar/kVA, not W.
- Default parity is even (8E1), not 8N1.
Network setup
- RS485 on terminals 10 and 11; defaults Modbus ID 1, 9600 baud, 8 data bits, even parity, 1 stop bit.
- Baud can be lowered to 4800, 2400 or 1200; parity can be none or odd; data and stop bits are fixed.
- Fit a 120 ohm / 0.25 W resistor across the RS485 terminals at the meter when testing through an RS485 converter.
Watch out for
- Program mode 3 settings (S0, combination code, baud, parity, power-down counter) need the display password (default 0000).
- Total active energy (6000h) follows the combination code; read forward (600Ch) and reverse (6018h) for import and export.
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 16387doc 4003 | Modbus ID | Slave address 1-247 (default 1); write with function 06. | INT16 | Read/write | ||||
| HR | 16388doc 4004 | Baud rate | Baud rate as a plain number, e.g. 9600 = 0x2580. | INT16 | Read/write | ||||
| HR | 16389doc 4005 | Protocol version | FLOAT32 | ABCD | Read | ||||
| HR | 16391doc 4007 | Software version | FLOAT32 | ABCD | Read | ||||
| HR | 16393doc 4009 | Hardware version | FLOAT32 | ABCD | Read | ||||
| HR | 16395doc 400B | Meter amps | Current rating of the meter. | INT16 | A | Read | |||
| HR | 16397doc 400D | S0 output rate | Pulse output rate; write both registers with function 16. | FLOAT32 | ABCD | imp/kWh | Read/write | ||
| HR | 16399doc 400F | Combination code | How total energy combines forward and reverse. | INT16 | Read/write | 1 = Forward only; 4 = Reverse only; 5 = Forward + reverse; 6 = Reverse - forward; 9 = Forward - reverse; 10 = Forward - reverse | |||
| HR | 16401doc 4011 | Parity setting | INT16 | Read/write | 1 = Even; 2 = None; 3 = Odd | ||||
| HR | 16406doc 4016 | Power down counter | Number of times the meter lost power; write 0 to reset. | INT16 | Read/write | ||||
| HR | 16407doc 4017 | Present quadrant | Present operating quadrant. | INT16 | Read | ||||
| HR | 20480doc 5000 | Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20482doc 5002 | L1 voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 20488doc 5008 | Grid frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 20490doc 500A | Current | FLOAT32 | ABCD | A | Read | |||
| HR | 20492doc 500C | L1 current | FLOAT32 | ABCD | A | Read | |||
| HR | 20498doc 5012 | Total active power | FLOAT32 | ABCD | kW | Read | |||
| HR | 20506doc 501A | Total reactive power | FLOAT32 | ABCD | kvar | Read | |||
| HR | 20514doc 5022 | Total apparent power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 20522doc 502A | Power factor | FLOAT32 | ABCD | Read | ||||
| HR | 24576doc 6000 | Total active energy | Forward and reverse combined per the combination code (400Fh). | FLOAT32 | ABCD | kWh | Read | ||
| HR | 24578doc 6002 | T1 total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24580doc 6004 | T2 total active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24588doc 600C | Forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24590doc 600E | T1 forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24592doc 6010 | T2 forward active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24600doc 6018 | Reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24602doc 601A | T1 reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24604doc 601C | T2 reverse active energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 24612doc 6024 | Total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24614doc 6026 | T1 total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24616doc 6028 | T2 total reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24624doc 6030 | Forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24626doc 6032 | T1 forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24628doc 6034 | T2 forward reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24636doc 603C | Reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24638doc 603E | T1 reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24640doc 6040 | T2 reverse reactive energy | FLOAT32 | ABCD | kvarh | Read | |||
| HR | 24648doc 6048 | Tariff | Active tariff; 11/12 switch tariff without saving it. | INT16 | Read/write | 1 = T1; 2 = T2; 11 = T1 (not saved); 12 = T2 (not saved) | |||
| HR | 24649doc 6049 | Resettable day counter | Forward energy since last reset; write 0.0 with function 16 to reset. | FLOAT32 | ABCD | kWh | Read/write |
Notes on this map
- The PDF is inepro's own user manual (hosted on inepro's website CDN).
- The register map is shared with the PRO380; rows marked '*PRO380 only' (L2/L3 values, per-phase energy, CT ratio/mode, L2/L3 current direction and quadrants) are left out of this single-phase file.
- 'Float ABCD' = IEEE 754 32-bit float, high word first. 'Signed' rows are 16-bit integers.
- Units are as printed: power in kW, kvar and kVA (not W), energy in kWh and kvarh.
- Left out: serial number, meter code, checksum and active status word (typed HEX with no decoding), LCD cycle time (HEX; the write example 0025 for 25 s suggests BCD), current direction (ASCII) and error code 4015h (no code list given).
- Baud rate (4004h) is written as the plain number, e.g. 2580h = 9600. The Modbus section allows 1200, 2400, 4800 and 9600.
- Combination code 11 is marked PRO380 only and is left out of the value list.
- The day-counter write row prints function 06 and length 1, but its example frame writes 2 registers with function 16; it is listed here as a 2-register float.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
What Modbus registers does the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) have?
This map lists 40 registers: 40 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints hex addresses that go into the request unchanged; the manual's example frames are 01 06 4003 000A (set Modbus ID) and 01 06 6048 0002 (set tariff). So 5012h (total active power) is wire address 20498. Do not enter the hex numbers as decimal.
What byte order does the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)?
Start with HR 20480 Voltage (Voltage); HR 20490 Current (Current); HR 20498 Total active power (Total active power (kW)); HR 20522 Power factor (Power factor); HR 20488 Grid frequency (Grid frequency); HR 24588 Forward active energy (Forward (import) active energy); HR 24600 Reverse active energy (Reverse (export) active energy).
How do I enable Modbus control of the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)?
Modbus is on the -Mod version only. Set the ID in Program mode 2 and baud/parity in Program mode 3 (4-digit password, default 0000), or over Modbus at 4003h/4004h/4011h.
Where is the official inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus documentation?
The source is PRO2 Series MID Single phase energy meter - User manual (Version 2.18-6), published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/667ec2f1562208b2b57c5742_PRO2%20User%20manual.pdf.
More inepro Metering Modbus register maps
- Energy meter
inepro Metering 4PU / 4PS three-phase energy meter
4PU (meter code 1111) and 4PS (1112) MID three-phase DIN-rail meters with Modbus, user manual version 1.03 (2025).
Also known as: 4PU, 4PS, inepro 4PU, inepro 4PS - Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Energy meter
inepro Metering PRO380-Mod three-phase energy meter
PRO380-Mod and PRO380-Mod CT (RS485 Modbus RTU), current register map from PRO380 user manual version 2.18-8.
Also known as: PRO380 Mod, PRO380-Mod CT, PRO380-MOD, inepro PRO380, PRO380 MID
Other power & energy meters register maps
- Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Sensor (Coriolis mass flowmeter)
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).
Also known as: MFC300, KROHNE MFC 300 - Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30 - Power meter (multi-circuit power monitor)
Omron KM-N3-FLK on-panel power monitor
Omron KM-N3-FLK power monitor (catalog N214-E1-04).
Also known as: KM-N3-FLK, KM-N3
All power & energy meters Modbus register maps →
Source: PRO2 Series MID Single phase energy meter - User manual · Version 2.18-6. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.