Energy meter · Modbus register map

inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus register map

Updated 17 November 2026

Short answer

The PRO2-Mod is inepro's single-phase MID DIN-rail energy meter with an RS485 Modbus RTU port (this is the older PRO line, not the 2026 PRO1/PRO2 template). Every measurement is an IEEE 754 float, high word first, read with function 03 from hex blocks 4000h (setup), 5000h (live values) and 6000h (energy). The map covers voltage, current, power, power factor, frequency, total/tariff energy and the writable ID, baud, parity, S0, tariff and combination-code settings.

This page lists 40 Modbus registers for the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.

Manufacturer
inepro Metering
Model
PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
Equipment type
Energy meter
Registers
40 (8 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy
Source document
PRO2 Series MID Single phase energy meter - User manual · Version 2.18-6
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)

Integration in brief

Wire RS485 to terminals 10 and 11, poll unit 1 at 9600 baud 8E1 with function 03 and decode each value as a high-word-first float. Live values sit at 5000h-502Bh, energy at 6000h-604Ah.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20480VoltageFLOAT32 ABCDVoltageRead
HR 20490CurrentFLOAT32 ABCDCurrentRead
HR 20498Total active powerFLOAT32 ABCDTotal active power (kW)Read
HR 20522Power factorFLOAT32 ABCDPower factorRead
HR 20488Grid frequencyFLOAT32 ABCDGrid frequencyRead
HR 24588Forward active energyFLOAT32 ABCDForward (import) active energyRead
HR 24600Reverse active energyFLOAT32 ABCDReverse (export) active energyRead

Enable Modbus control & writes

Modbus is on the -Mod version only. Set the ID in Program mode 2 and baud/parity in Program mode 3 (4-digit password, default 0000), or over Modbus at 4003h/4004h/4011h.

Byte order & addressing

Network setup

Watch out for

inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

40 of 40 shown
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR16387doc 4003Modbus IDSlave address 1-247 (default 1); write with function 06.INT16Read/write
HR16388doc 4004Baud rateBaud rate as a plain number, e.g. 9600 = 0x2580.INT16Read/write
HR16389doc 4005Protocol versionFLOAT32ABCDRead
HR16391doc 4007Software versionFLOAT32ABCDRead
HR16393doc 4009Hardware versionFLOAT32ABCDRead
HR16395doc 400BMeter ampsCurrent rating of the meter.INT16ARead
HR16397doc 400DS0 output ratePulse output rate; write both registers with function 16.FLOAT32ABCDimp/kWhRead/write
HR16399doc 400FCombination codeHow total energy combines forward and reverse.INT16Read/write1 = Forward only; 4 = Reverse only; 5 = Forward + reverse; 6 = Reverse - forward; 9 = Forward - reverse; 10 = Forward - reverse
HR16401doc 4011Parity settingINT16Read/write1 = Even; 2 = None; 3 = Odd
HR16406doc 4016Power down counterNumber of times the meter lost power; write 0 to reset.INT16Read/write
HR16407doc 4017Present quadrantPresent operating quadrant.INT16Read
HR20480doc 5000VoltageFLOAT32ABCDVRead
HR20482doc 5002L1 voltageFLOAT32ABCDVRead
HR20488doc 5008Grid frequencyFLOAT32ABCDHzRead
HR20490doc 500ACurrentFLOAT32ABCDARead
HR20492doc 500CL1 currentFLOAT32ABCDARead
HR20498doc 5012Total active powerFLOAT32ABCDkWRead
HR20506doc 501ATotal reactive powerFLOAT32ABCDkvarRead
HR20514doc 5022Total apparent powerFLOAT32ABCDkVARead
HR20522doc 502APower factorFLOAT32ABCDRead
HR24576doc 6000Total active energyForward and reverse combined per the combination code (400Fh).FLOAT32ABCDkWhRead
HR24578doc 6002T1 total active energyFLOAT32ABCDkWhRead
HR24580doc 6004T2 total active energyFLOAT32ABCDkWhRead
HR24588doc 600CForward active energyFLOAT32ABCDkWhRead
HR24590doc 600ET1 forward active energyFLOAT32ABCDkWhRead
HR24592doc 6010T2 forward active energyFLOAT32ABCDkWhRead
HR24600doc 6018Reverse active energyFLOAT32ABCDkWhRead
HR24602doc 601AT1 reverse active energyFLOAT32ABCDkWhRead
HR24604doc 601CT2 reverse active energyFLOAT32ABCDkWhRead
HR24612doc 6024Total reactive energyFLOAT32ABCDkvarhRead
HR24614doc 6026T1 total reactive energyFLOAT32ABCDkvarhRead
HR24616doc 6028T2 total reactive energyFLOAT32ABCDkvarhRead
HR24624doc 6030Forward reactive energyFLOAT32ABCDkvarhRead
HR24626doc 6032T1 forward reactive energyFLOAT32ABCDkvarhRead
HR24628doc 6034T2 forward reactive energyFLOAT32ABCDkvarhRead
HR24636doc 603CReverse reactive energyFLOAT32ABCDkvarhRead
HR24638doc 603ET1 reverse reactive energyFLOAT32ABCDkvarhRead
HR24640doc 6040T2 reverse reactive energyFLOAT32ABCDkvarhRead
HR24648doc 6048TariffActive tariff; 11/12 switch tariff without saving it.INT16Read/write1 = T1; 2 = T2; 11 = T1 (not saved); 12 = T2 (not saved)
HR24649doc 6049Resettable day counterForward energy since last reset; write 0.0 with function 16 to reset.FLOAT32ABCDkWhRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)

What Modbus registers does the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) have?

This map lists 40 registers: 40 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints hex addresses that go into the request unchanged; the manual's example frames are 01 06 4003 000A (set Modbus ID) and 01 06 6048 0002 (set tariff). So 5012h (total active power) is wire address 20498. Do not enter the hex numbers as decimal.

What byte order does the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)?

Start with HR 20480 Voltage (Voltage); HR 20490 Current (Current); HR 20498 Total active power (Total active power (kW)); HR 20522 Power factor (Power factor); HR 20488 Grid frequency (Grid frequency); HR 24588 Forward active energy (Forward (import) active energy); HR 24600 Reverse active energy (Reverse (export) active energy).

How do I enable Modbus control of the inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)?

Modbus is on the -Mod version only. Set the ID in Program mode 2 and baud/parity in Program mode 3 (4-digit password, default 0000), or over Modbus at 4003h/4004h/4011h.

Where is the official inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6) Modbus documentation?

The source is PRO2 Series MID Single phase energy meter - User manual (Version 2.18-6), published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/667ec2f1562208b2b57c5742_PRO2%20User%20manual.pdf.

More inepro Metering Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PRO2 Series MID Single phase energy meter - User manual · Version 2.18-6. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.