- PRO1 single-phase energy meter (2026 PRO line)
Energy meter · Modbus register map
inepro Metering PRO1 single-phase energy meter (2026 PRO line) Modbus register map
Updated 17 November 2026
The PRO1 is a MID-certified single-phase 45 A DIN-rail energy meter from inepro's 2026 PRO line; the -Mod versions add an RS485 Modbus RTU port. Live values are IEEE 754 floats (high word first) in input registers from hex 5000h, energy counters sit from 6000h and settings from 4000h. This map covers the default register map: instantaneous values, THD, demand peaks, energy totals and tariff registers (as floats) and the main communication and display settings.
This page lists 104 Modbus registers for the inepro Metering PRO1 single-phase energy meter (2026 PRO line) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from inepro Metering’s own free documentation (linked below) and checked against it.
- Manufacturer
- inepro Metering
- Model
- PRO1 single-phase energy meter (2026 PRO line)
- Equipment type
- Energy meter
- Registers
- 104 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102
Integration notes: inepro Metering PRO1 single-phase energy meter (2026 PRO line)
Wire RS485 to terminals 8 (A) and 10 (B), poll unit 1 at 9600 baud 8E1 with function 04 and decode live values as high-word-first floats from 5000h. Write 2 to 4026h once (function 06) so the 6000h energy registers come back as floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 20482 | Voltage L1 | FLOAT32 ABCD | Voltage L1 | Read |
| IR 20492 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| IR 20498 | Total Active Power | FLOAT32 ABCD | Total active power (kW) | Read |
| IR 20522 | Total Power Factor | FLOAT32 ABCD | Total power factor | Read |
| IR 20488 | Grid Frequency | FLOAT32 ABCD | Grid frequency | Read |
| IR 24588 | Total Forward Active Energy | FLOAT32 ABCD | Total forward (import) active energy | Read |
| IR 24600 | Total Reverse Active Energy | FLOAT32 ABCD | Total reverse (export) active energy | Read |
| HR 16422 | Data format setting | UINT16 | Switch energy registers to float | Read/write |
Enable Modbus control & writes
Modbus is only on the -Mod and -Mod-Ba versions. Set ID, baud and parity on the display, with inepro's configuration software, or over Modbus at 4003h/4004h/4011h.
Byte order & addressing
- Addresses are hex: 5012h is decimal 20498 on the wire.
- Live values are input registers (function 04), not holding registers.
- Power is in kW/kvar/kVA, not W.
- Energy registers default to INT32; set 4026h = 2 for floats.
- Baud rate is written as a code (6 = 9600 ... 10 = 115200), not as the number.
Network setup
- Defaults: Modbus ID 1, 9600 baud, even parity, 1 stop bit.
- Parity codes at 4011h: 1 = even, 2 = none, 3 = odd; use 2 stop bits with no parity.
- Up to 60 devices per RS485 bus, 1200 m range, fewer at higher baud rates.
Watch out for
- Total active energy (6000h) depends on the combination code at 400Fh; read forward (600Ch) and reverse (6018h) for import and export.
- RTC tariff registers read 0 unless the meter is a -Mod-Ba.
inepro Metering PRO1 single-phase energy meter (2026 PRO line) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 16389doc 0X4005 | Protocol Version Number | FLOAT32 | ABCD | Read | ||||
| IR | 16391doc 0X4007 | Version Number | FLOAT32 | ABCD | Read | ||||
| IR | 16393doc 0X4009 | Hardware Version Number | FLOAT32 | ABCD | Read | ||||
| IR | 16395doc 0X400B | Maximum current | Current rating of the meter. | UINT16 | A | Read | |||
| IR | 16421doc 0X4025 | Product code | UINT16 | Read | |||||
| IR | 20096doc 0X4E80 | Year of manufacture | UINT16 | Read | |||||
| IR | 20482doc 0X5002 | Voltage L1 | FLOAT32 | ABCD | V | Read | |||
| IR | 20488doc 0X5008 | Grid Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 20490doc 0X500A | Current | FLOAT32 | ABCD | A | Read | |||
| IR | 20492doc 0X500C | Current L1 | FLOAT32 | ABCD | A | Read | |||
| IR | 20498doc 0X5012 | Total Active Power | FLOAT32 | ABCD | kW | Read | |||
| IR | 20500doc 0X5014 | Active Power L1 | FLOAT32 | ABCD | kW | Read | |||
| IR | 20506doc 0X501A | Total Reactive Power | FLOAT32 | ABCD | kvar | Read | |||
| IR | 20508doc 0X501C | Reactive Power L1 | FLOAT32 | ABCD | kvar | Read | |||
| IR | 20514doc 0X5022 | Total Apparent Power | FLOAT32 | ABCD | Read | ||||
| IR | 20516doc 0X5024 | Apparent Power L1 | FLOAT32 | ABCD | kVA | Read | |||
| IR | 20522doc 0X502A | Total Power Factor | FLOAT32 | ABCD | Read | ||||
| IR | 20524doc 0X502C | Power Factor L1 | FLOAT32 | ABCD | Read | ||||
| IR | 20542doc 0X503E | THD+N Voltage L1 | FLOAT32 | ABCD | % | Read | |||
| IR | 20548doc 0X5044 | THD+N Current L1 | FLOAT32 | ABCD | % | Read | |||
| IR | 20554doc 0X504A | THD+N Average Voltage | FLOAT32 | ABCD | % | Read | |||
| IR | 20556doc 0X504C | THD+N Average Current | FLOAT32 | ABCD | % | Read | |||
| IR | 20576doc 0X5060 | Forward Active Power Demand Peak | Read with function 04; reset by writing 0 here with function 16. | FLOAT32 | ABCD | kW | Read | ||
| IR | 20578doc 0X5062 | Reverse Active Power Demand Peak | Read with function 04; reset by writing 0 here with function 16. | FLOAT32 | ABCD | kW | Read | ||
| IR | 24576doc 0X6000 | Total Active Energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24578doc 0X6002 | Total Active Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24580doc 0X6004 | Total Active Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24588doc 0X600C | Total Forward Active Energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24590doc 0X600E | Total Forward Active Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24592doc 0X6010 | Total Forward Active Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24600doc 0X6018 | Total Reverse Active Energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24602doc 0X601A | Total Reverse Active Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24604doc 0X601C | Total Reverse Active Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24612doc 0X6024 | Total Reactive Energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24614doc 0X6026 | Total Reactive Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24616doc 0X6028 | Total Reactive Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24624doc 0X6030 | Total Forward Reactive energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24626doc 0X6032 | Total Forward Reactive Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24628doc 0X6034 | Total Forward Reactive Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24636doc 0X603C | Total Reverse Reactive energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24638doc 0X603E | Total Reverse Reactive Energy DS-T1 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24640doc 0X6040 | Total Reverse Reactive Energy DS-T2 | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24675doc 0X6063 | Import inductive reactive energy in Q1 (total) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24677doc 0X6065 | Import inductive reactive energy in Q1 (DS-T1) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24679doc 0X6067 | Import capacitive reactive energy in Q1 (DS-T2) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24685doc 0X606D | Import capacitive reactive energy in Q2 (total) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24687doc 0X606F | Export capacitive reactive energy in Q2 (DS-T1) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24689doc 0X6071 | Export inductive reactive energy in Q2 (DS-T2) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24695doc 0X6077 | Export inductive reactive energy in Q3 (total) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24697doc 0X6079 | Import capacitive reactive energy in Q3 (DS-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24699doc 0X607B | Import inductive reactive energy in Q3 (DS-T2) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24705doc 0X6081 | Export capacitive reactive energy in Q4 (total) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24707doc 0X6083 | Export inductive reactive energy in Q4 (DS-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24709doc 0X6085 | Export capacitive reactive energy in Q4 (DS-T2) | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24761doc 0X60B9 | Total Apparent energy | Float only after 4026h is set to 2. | FLOAT32 | ABCD | kVAh | Read | ||
| IR | 24873doc 0X6129 | Import inductive reactive energy in Q1 (RTC-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24891doc 0X613B | Import capacitive reactive energy in Q2 (RTC-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24893doc 0X613D | Export inductive reactive energy in Q3 (RTC-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24895doc 0X613F | Export capacitive reactive energy in Q4 (RTC-T1) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24897doc 0X6141 | Import inductive reactive energy in Q1 (RTC-T2) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24899doc 0X6143 | Import capacitive reactive energy in Q2 (RTC-T2) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24901doc 0X6145 | Export inductive reactive energy in Q3 (RTC-T2) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24903doc 0X6147 | Export capacitive reactive energy in Q4 (RTC-T2) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24905doc 0X6149 | Import inductive reactive energy in Q1 (RTC-T3) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24907doc 0X614B | Export inductive reactive energy in Q2 (RTC-T3) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24909doc 0X614D | Import capacitive reactive energy in Q3 (RTC-T3) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24911doc 0X614F | Export capacitive reactive energy in Q4 (RTC-T3) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24913doc 0X6151 | Import inductive reactive energy in Q1 (RTC-T4) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24915doc 0X6153 | Export inductive reactive energy in Q2 (RTC-T4) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24917doc 0X6155 | Import capacitive reactive energy in Q3 (RTC-T4) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24919doc 0X6157 | Export capacitive reactive energy in Q4 (RTC-T4) | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24921doc 0X6159 | Total Forward Active Energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24939doc 0X616B | Total Forward Active Energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24941doc 0X616D | Total Forward Active Energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24943doc 0X616F | Total Forward Active Energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24945doc 0X6171 | Total Reverse Active Energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24947doc 0X6173 | Total Reverse Active Energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24949doc 0X6175 | Total Reverse Active Energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24951doc 0X6177 | Total Reverse Active Energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24953doc 0X6179 | Total Forward Reactive energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24971doc 0X618B | Total Forward Reactive energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24973doc 0X618D | Total Forward Reactive energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24975doc 0X618F | Total Forward Reactive energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24977doc 0X6191 | Total Reverse Reactive Energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24979doc 0X6193 | Total Reverse Reactive Energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24981doc 0X6195 | Total Reverse Reactive Energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24983doc 0X6197 | Total Reverse Reactive Energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 24985doc 0X6199 | Total Active Energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24987doc 0X619B | Total Active Energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24989doc 0X619D | Total Active Energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 24991doc 0X619F | Total Active Energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 25089doc 0X6201 | Total Reactive Energy RTC-T1 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 25091doc 0X6203 | Total Reactive Energy RTC-T2 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 25093doc 0X6205 | Total Reactive Energy RTC-T3 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| IR | 25095doc 0X6207 | Total Reactive Energy RTC-T4 | Ba (RTC) variant only; float after 4026h = 2. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 16387doc 0X4003 | Modbus ID | Slave address 1-247; write with function 06. | UINT16 | Read/write | ||||
| HR | 16388doc 0X4004 | Baud rate | Baud rate code. | UINT16 | Read/write | 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | |||
| HR | 16399doc 0X400F | Combination code | How forward and reverse energy are combined into total energy. | UINT16 | Read/write | 1 = Forward only (mode C); 2 = Reverse only (mode D); 3 = Forward + reverse (mode A, default); 4 = Forward - reverse (mode B) | |||
| HR | 16400doc 0X4010 | LCD cycle time | Display scroll time 0-30 s; 0 keeps the home page. | UINT16 | s | Read/write | |||
| HR | 16401doc 0X4011 | Parity | UINT16 | Read/write | 1 = Even; 2 = None; 3 = Odd | ||||
| HR | 16422doc 0X4026 | Data format setting | Selects INT32 or float encoding for the energy registers. | UINT16 | Read/write | 1 = INT32 (default); 2 = FLOAT | |||
| HR | 16757doc 0X4175 | Demand interval | Power demand interval in minutes: 1, 5, 10, 15 (default), 20, 30 or 60. | UINT16 | min | Read/write | |||
| HR | 19458doc 0X4C02 | Backlight mode | UINT16 | Read/write | 0 = Always on; 1 = Off; 2 = On at button press (default) | ||||
| HR | 19460doc 0X4C04 | Backlight time | Backlight on-time after a button press (button mode only). | UINT16 | Read/write | 1 = 1 min (default); 2 = 2 min; 3 = 5 min; 4 = 10 min; 5 = 15 min; 6 = 30 min; 7 = 60 min |
Notes on this map
- This file covers only the 'Default' register map. The manual also prints an 'Extensive' map (from 0000h, W/var units) and a 'YTL' map (scaled integers and UINT64 counters) but does not say how either is selected, so they are left out.
- Energy registers are typed 'UINT32/Float ABCD' (or INT32/Float) with units 'Wh/kWh'. Register 4026h selects the format: 1 = INT32 (default), 2 = FLOAT. They are listed here as FLOAT32 in kWh/kvarh/kVAh, valid only after writing 2 to 4026h. The INT32 mode is not covered because the manual never states its scale explicitly.
- The INT32/FLOAT pairing with Wh/kWh follows the order printed in the type and unit columns ('UINT32/Float', 'Wh/kWh'); the same manual's Extensive map also gives float energy in kWh.
- Total reactive energy (6024h) is printed with unit 'vah/kvah' in the map; it is listed here as kvarh, matching its name and the DS-T1/DS-T2 reactive totals (6026h/6028h).
- Registers marked 'Only for Ba version with RTC' (RTC tariff and some quadrant energies) read 0 on meters without the RTC; the manual says unsupported registers stay readable and return 0.
- Left out: serial number, meter code and CRC (BCD/HEX/ASCII with no decoding given), RTC time and tariff tables (BCD blocks), current direction (ASCII), S0 output rate (typed UINT16 length 1 in the read map but FLOAT length 2 in the write table), CT ratio, tariff mode 6048h (listed twice with different meanings), LCD password and the resettable day counter (INT32 without a stated word order).
- Quadrant labels on the DS-T1/DS-T2 rows are copied as printed; some pair import/export with Q2/Q3 differently from the totals rows.
- Baud rates per the manual: 9600, 19200, 38400, 57600 and 115200. Stop bits: 1 with even/odd parity, 2 with no parity.
- This 2026 PRO line uses a different template from the older PRO1-Mod/PRO2-Mod (V3.x) and PRO380-Mod maps; do not mix them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the inepro Metering PRO1 single-phase energy meter (2026 PRO line)
What Modbus registers does the inepro Metering PRO1 single-phase energy meter (2026 PRO line) have?
This map lists 104 registers: 95 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the inepro Metering PRO1 single-phase energy meter (2026 PRO line) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints hex addresses that go into the request unchanged; the manual's example frames are 01 06 4003 000A (set Modbus ID) and 01 10 5060 0002 ... (reset demand peak). So 5012h is wire address 20498. Rows typed 'input' are read with function 04; rows typed 'input /holding' are listed here as holding registers (read 03, write 06/16).
What byte order does the inepro Metering PRO1 single-phase energy meter (2026 PRO line) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the inepro Metering PRO1 single-phase energy meter (2026 PRO line)?
Start with IR 20482 Voltage L1 (Voltage L1); IR 20492 Current L1 (Current L1); IR 20498 Total Active Power (Total active power (kW)); IR 20522 Total Power Factor (Total power factor); IR 20488 Grid Frequency (Grid frequency); IR 24588 Total Forward Active Energy (Total forward (import) active energy); IR 24600 Total Reverse Active Energy (Total reverse (export) active energy); HR 16422 Data format setting (Switch energy registers to float).
How do I enable Modbus control of the inepro Metering PRO1 single-phase energy meter (2026 PRO line)?
Modbus is only on the -Mod and -Mod-Ba versions. Set ID, baud and parity on the display, with inepro's configuration software, or over Modbus at 4003h/4004h/4011h.
Where is the official inepro Metering PRO1 single-phase energy meter (2026 PRO line) Modbus documentation?
The source is PRO1 energy meter - Full User Manual EN (User manual version 1.3), revision 2026, published free by inepro Metering at https://cdn.prod.website-files.com/6617f74190bf0a53bfd776e8/6aeca6163dcdf3a4b4b8ac7b_PRO1%20energy%20meter%20-%20Full%20User%20Manual%20EN.pdf.
More inepro Metering Modbus register maps
- Energy meter
inepro Metering 4PU / 4PS three-phase energy meter
4PU (meter code 1111) and 4PS (1112) MID three-phase DIN-rail meters with Modbus, user manual version 1.03 (2025).
Also known as: 4PU, 4PS, inepro 4PU, inepro 4PS - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Energy meter
inepro Metering PRO2-Mod single-phase energy meter (PRO2 series, manual 2.18-6)
PRO2-Mod of the PRO2 series (PRO2-S/-2T/-Mb/-Mod), register map of user manual version 2.18-6.
Also known as: PRO2-Mod, PRO2 Mod, PRO2 MID, inepro PRO2 legacy - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Energy meter
inepro Metering PRO380-Mod three-phase energy meter
PRO380-Mod and PRO380-Mod CT (RS485 Modbus RTU), current register map from PRO380 user manual version 2.18-8.
Also known as: PRO380 Mod, PRO380-Mod CT, PRO380-MOD, inepro PRO380, PRO380 MID
Other power & energy meters register maps
- Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power quality analyser)
KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
KMB systems panel and DIN-rail meters and analysers with firmware 4.x, per 'Modbus-TCP and Modbus-RTU protocol documentation' (revision of January 19, 2023). Which blocks a model supports depends on the instrument and its firmware modules.
Also known as: SMC 133, SMC 144, PA 144, SML 133, SMM 133, SMC 118, SMY 133, SMY 134, SMP 133, SMZ 133, SMC 235, SMC 233, ARTIQ 235, ARTIQ 233, BC 235, BCPM 233, EMU 3, SMZ 244 - Pump (chemical metering pump)
LMI Excel XR series electronic metering pump (Modbus RTU)
LMI Excel XR electronic metering pumps fitted with the Modbus RTU interface (manual 55312 rev 04).
Also known as: Excel XR, LMI Excel XR, Milton Roy Excel XR, Excel XR Modbus - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350
All power & energy meters Modbus register maps →
Source: PRO1 energy meter - Full User Manual EN · User manual version 1.3 · rev. 2026. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.