Power meter (power quality analyser) · Modbus register map
KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus register map
Updated 17 November 2026
KMB systems (Czech Republic) builds the SMC, SMY, SMZ, SML, PA and ARTIQ families of power meters and power-quality analysers. Firmware 4.x devices share one Modbus register map over RS-485 (Modbus RTU, auto-detected alongside KMB's own protocol) or Ethernet (Modbus TCP, port 502). This map covers the compact 19000-19121 block of the most-used values as IEEE floats with units, power factor, status and identification.
This page lists 41 Modbus registers for the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KMB systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- KMB systems
- Model
- SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
- Equipment type
- Power meter (power quality analyser)
- Registers
- 41 (0 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 4.x (document lists FW compatibility up to 4.x releases)
- Also known as
- SMC 133, SMC 144, PA 144, SML 133, SMM 133, SMC 118, SMY 133, SMY 134, SMP 133, SMZ 133, SMC 235, SMC 233, ARTIQ 235, ARTIQ 233, BC 235, BCPM 233, EMU 3, SMZ 244
Integration notes: KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
Read input registers (function 04) from 19000 for 27 floats: phase and line voltages, currents, P/Q/S per phase and total, CosPhi, frequency and phase order. Use function 03 on the same block if you want the averaged values.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 19000 | Voltage L1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| IR 19012 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| IR 19026 | Active power total | FLOAT32 ABCD | Total active power | Read |
| IR 19034 | Apparent power total | FLOAT32 ABCD | Total apparent power | Read |
| IR 19050 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 4864 | Power factor total | FLOAT32 ABCD | Total power factor | Read |
| IR 4097 | Error code | UINT32 ABCD | Instrument error flags (0 = OK) | Read |
Enable Modbus control & writes
Modbus TCP is on by default on Ethernet models (port 502, configurable with the TCP/IP settings). For RS-485 set the device address, baud rate and parity in the instrument (see its user manual); Modbus RTU is detected automatically.
Byte order & addressing
- Addresses are 0-based PDU addresses.
- Function 03 and 04 on the same address return average vs actual values.
- Floats are big-endian.
Network setup
- Device address 1-248 (0 and 249-255 reserved).
- At least three Modbus TCP masters can connect at once; each must wait for a reply before the next request.
Watch out for
- Multi-feeder devices answer feeder 2-12 data on extra Modbus addresses, not extra registers.
- The instrument replies within 200 ms; set master timeouts accordingly.
KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 520doc 520 (0x0208) | Props type (device family) | e.g. 0x0050 DIN-rail analysers, 0x0030 panel analysers, 0x0100 high-end PQ line, 0x0040 NOVAR. | UINT16 | Read | ||||
| IR | 521doc 521 (0x0209) | Device type | Exact instrument code within the family (see manual 3.4). | UINT16 | Read | ||||
| IR | 4096doc 4096 (0x1000) | Configuration change counter | Increments on every configuration change. | UINT16 | Read | ||||
| IR | 4097doc 4097 (0x1001) | Error code | 0 = all OK; bit set = possible problem. | UINT32 | ABCD | Read | bit 0 = RAM error; bit 1 = Instrument configuration error; bit 2 = Calibration error; bit 3 = Remote communication module error (WiFi/ZigBee); bit 4 = Clock (RTC) error; bit 7 = Archive error; bit 8 = Flash memory error; bit 9 = Display error | ||
| IR | 4864doc 4864 (0x1300) | Power factor total | FLOAT32 | ABCD | Read | ||||
| IR | 4870doc 4870 (0x1306) | Power factor L1 | FLOAT32 | ABCD | Read | ||||
| IR | 4872doc 4872 (0x1308) | Power factor L2 | FLOAT32 | ABCD | Read | ||||
| IR | 4874doc 4874 (0x130A) | Power factor L3 | FLOAT32 | ABCD | Read | ||||
| IR | 19000 | Voltage L1-N | FLOAT32 | ABCD | V | Read | |||
| IR | 19002 | Voltage L2-N | FLOAT32 | ABCD | V | Read | |||
| IR | 19004 | Voltage L3-N | FLOAT32 | ABCD | V | Read | |||
| IR | 19006 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| IR | 19008 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| IR | 19010 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| IR | 19012 | Current L1 | FLOAT32 | ABCD | A | Read | |||
| IR | 19014 | Current L2 | FLOAT32 | ABCD | A | Read | |||
| IR | 19016 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| IR | 19018 | Neutral current (calculated) | FLOAT32 | ABCD | A | Read | |||
| IR | 19020 | Active power L1 | FLOAT32 | ABCD | W | Read | |||
| IR | 19022 | Active power L2 | FLOAT32 | ABCD | W | Read | |||
| IR | 19024 | Active power L3 | FLOAT32 | ABCD | W | Read | |||
| IR | 19026 | Active power total | FLOAT32 | ABCD | W | Read | |||
| IR | 19028 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| IR | 19030 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| IR | 19032 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| IR | 19034 | Apparent power total | FLOAT32 | ABCD | VA | Read | |||
| IR | 19036 | Reactive power L1 | FLOAT32 | ABCD | var | Read | |||
| IR | 19038 | Reactive power L2 | FLOAT32 | ABCD | var | Read | |||
| IR | 19040 | Reactive power L3 | FLOAT32 | ABCD | var | Read | |||
| IR | 19042 | Reactive power total | FLOAT32 | ABCD | var | Read | |||
| IR | 19044 | CosPhi L1 | FLOAT32 | ABCD | Read | ||||
| IR | 19046 | CosPhi L2 | FLOAT32 | ABCD | Read | ||||
| IR | 19048 | CosPhi L3 | FLOAT32 | ABCD | Read | ||||
| IR | 19050 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 19052 | Phase order | 1 = correct 1-2-3, -1 = inverted 1-3-2, 0 = unknown (as a float). | FLOAT32 | ABCD | Read | |||
| IR | 19110 | THD voltage L1 | FLOAT32 | ABCD | % | Read | |||
| IR | 19112 | THD voltage L2 | FLOAT32 | ABCD | % | Read | |||
| IR | 19114 | THD voltage L3 | FLOAT32 | ABCD | % | Read | |||
| IR | 19116 | THD current L1 | FLOAT32 | ABCD | % | Read | |||
| IR | 19118 | THD current L2 | FLOAT32 | ABCD | % | Read | |||
| IR | 19120 | THD current L3 | FLOAT32 | ABCD | % | Read |
Notes on this map
- Encoding (2.3): multi-byte values are big-endian and 32/64-bit values run MSB to LSB across consecutive registers, so floats are ABCD. The modpoll example reads voltages around 236 V as big-endian floats.
- Function 04 (input registers) returns actual 200 ms values; function 03 (holding registers) on the same addresses returns the averaged values set up in the instrument. Registers are listed here as input registers.
- Left out: the energy rows of the 19000 block (19054-19108). Their unit column says Wh / VAh / varh while the block's introduction says the registers give total kWh/kvarh counts, so the unit is ambiguous. The 0x2000 energy block (64-bit doubles) has no unit stated, so it is left out as well.
- Left out: the device number (528, printed only as '32b' with no signed/unsigned type), the detailed actual-data blocks 0x1100-0x13xx (no units printed), harmonics, archives, aggregated min/max blocks, RCM, PQ and NOVAR power-factor-controller registers, and the configuration/reset blocks.
- Multi-feeder instruments use the device address for feeder 1 and mirror the map for feeders 2-12 at address (X-1) x 20 + base address; their base address is limited to 1-20.
- Over RS-485 the device recognises Modbus RTU and KMB's own protocol automatically. The manual says KMB devices default to no parity; device address and baud must be set per the user manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
What Modbus registers does the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) have?
This map lists 41 registers: 41 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in decimal and hex as PDU (wire) addresses. The manual's modpoll examples use the -0 switch ('Modbus PDU addressing') with -r 528 for the device number and -r 4352 for the voltages, and a footnote says that without -0 every address would need +1.
What byte order does the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)?
Start with IR 19000 Voltage L1-N (Voltage L1-N); IR 19012 Current L1 (Current L1); IR 19026 Active power total (Total active power); IR 19034 Apparent power total (Total apparent power); IR 19050 Frequency (Frequency); IR 4864 Power factor total (Total power factor); IR 4097 Error code (Instrument error flags (0 = OK)).
How do I enable Modbus control of the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)?
Modbus TCP is on by default on Ethernet models (port 502, configurable with the TCP/IP settings). For RS-485 set the device address, baud rate and parity in the instrument (see its user manual); Modbus RTU is detected automatically.
Where is the official KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus documentation?
The source is Modbus-TCP and Modbus-RTU protocol documentation for panel meters, power quality analyzers and power factor controllers (Modbus manual v4.0 EN rev 1.8), revision 2023-01-19, published free by KMB systems at https://kmb.cz/en/download/download-documents/4-application-notes?download=200:modbus-manual-v4-0-en.
Other power & energy meters register maps
- Pump (chemical metering pump)
LMI Excel XR series electronic metering pump (Modbus RTU)
LMI Excel XR electronic metering pumps fitted with the Modbus RTU interface (manual 55312 rev 04).
Also known as: Excel XR, LMI Excel XR, Milton Roy Excel XR, Excel XR Modbus - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350 - Energy meter module
Peacefair PZEM-014 / PZEM-016
Peacefair PZEM-014 (10 A shunt) and PZEM-016 (100 A CT) single-phase AC RS485 modules; the PZEM-004T V3.0 (TTL UART) datasheet prints the identical register map.
Also known as: PZEM-014, PZEM-016, PZEM-004T V3.0, PZEM-004T-10A, PZEM-004T-100A - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS
All power & energy meters Modbus register maps →
Source: Modbus-TCP and Modbus-RTU protocol documentation for panel meters, power quality analyzers and power factor controllers · Modbus manual v4.0 EN rev 1.8 · rev. 2023-01-19. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.