Power meter (power quality analyser) · Modbus register map

KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus register map

Updated 17 November 2026

Short answer

KMB systems (Czech Republic) builds the SMC, SMY, SMZ, SML, PA and ARTIQ families of power meters and power-quality analysers. Firmware 4.x devices share one Modbus register map over RS-485 (Modbus RTU, auto-detected alongside KMB's own protocol) or Ethernet (Modbus TCP, port 502). This map covers the compact 19000-19121 block of the most-used values as IEEE floats with units, power factor, status and identification.

This page lists 41 Modbus registers for the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KMB systems’s own free documentation (linked below) and checked against it.

Manufacturer
KMB systems
Model
SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
Equipment type
Power meter (power quality analyser)
Registers
41 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
4.x (document lists FW compatibility up to 4.x releases)
Also known as
SMC 133, SMC 144, PA 144, SML 133, SMM 133, SMC 118, SMY 133, SMY 134, SMP 133, SMZ 133, SMC 235, SMC 233, ARTIQ 235, ARTIQ 233, BC 235, BCPM 233, EMU 3, SMZ 244
Source document
Modbus-TCP and Modbus-RTU protocol documentation for panel meters, power quality analyzers and power factor controllers · Modbus manual v4.0 EN rev 1.8 · rev. 2023-01-19
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)

Integration in brief

Read input registers (function 04) from 19000 for 27 floats: phase and line voltages, currents, P/Q/S per phase and total, CosPhi, frequency and phase order. Use function 03 on the same block if you want the averaged values.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
IR 19012Current L1FLOAT32 ABCDCurrent L1Read
IR 19026Active power totalFLOAT32 ABCDTotal active powerRead
IR 19034Apparent power totalFLOAT32 ABCDTotal apparent powerRead
IR 19050FrequencyFLOAT32 ABCDFrequencyRead
IR 4864Power factor totalFLOAT32 ABCDTotal power factorRead
IR 4097Error codeUINT32 ABCDInstrument error flags (0 = OK)Read

Enable Modbus control & writes

Modbus TCP is on by default on Ethernet models (port 502, configurable with the TCP/IP settings). For RS-485 set the device address, baud rate and parity in the instrument (see its user manual); Modbus RTU is detected automatically.

Byte order & addressing

Network setup

Watch out for

KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

41 of 41 shown
KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR520doc 520 (0x0208)Props type (device family)e.g. 0x0050 DIN-rail analysers, 0x0030 panel analysers, 0x0100 high-end PQ line, 0x0040 NOVAR.UINT16Read
IR521doc 521 (0x0209)Device typeExact instrument code within the family (see manual 3.4).UINT16Read
IR4096doc 4096 (0x1000)Configuration change counterIncrements on every configuration change.UINT16Read
IR4097doc 4097 (0x1001)Error code0 = all OK; bit set = possible problem.UINT32ABCDReadbit 0 = RAM error; bit 1 = Instrument configuration error; bit 2 = Calibration error; bit 3 = Remote communication module error (WiFi/ZigBee); bit 4 = Clock (RTC) error; bit 7 = Archive error; bit 8 = Flash memory error; bit 9 = Display error
IR4864doc 4864 (0x1300)Power factor totalFLOAT32ABCDRead
IR4870doc 4870 (0x1306)Power factor L1FLOAT32ABCDRead
IR4872doc 4872 (0x1308)Power factor L2FLOAT32ABCDRead
IR4874doc 4874 (0x130A)Power factor L3FLOAT32ABCDRead
IR19000Voltage L1-NFLOAT32ABCDVRead
IR19002Voltage L2-NFLOAT32ABCDVRead
IR19004Voltage L3-NFLOAT32ABCDVRead
IR19006Voltage L1-L2FLOAT32ABCDVRead
IR19008Voltage L2-L3FLOAT32ABCDVRead
IR19010Voltage L3-L1FLOAT32ABCDVRead
IR19012Current L1FLOAT32ABCDARead
IR19014Current L2FLOAT32ABCDARead
IR19016Current L3FLOAT32ABCDARead
IR19018Neutral current (calculated)FLOAT32ABCDARead
IR19020Active power L1FLOAT32ABCDWRead
IR19022Active power L2FLOAT32ABCDWRead
IR19024Active power L3FLOAT32ABCDWRead
IR19026Active power totalFLOAT32ABCDWRead
IR19028Apparent power L1FLOAT32ABCDVARead
IR19030Apparent power L2FLOAT32ABCDVARead
IR19032Apparent power L3FLOAT32ABCDVARead
IR19034Apparent power totalFLOAT32ABCDVARead
IR19036Reactive power L1FLOAT32ABCDvarRead
IR19038Reactive power L2FLOAT32ABCDvarRead
IR19040Reactive power L3FLOAT32ABCDvarRead
IR19042Reactive power totalFLOAT32ABCDvarRead
IR19044CosPhi L1FLOAT32ABCDRead
IR19046CosPhi L2FLOAT32ABCDRead
IR19048CosPhi L3FLOAT32ABCDRead
IR19050FrequencyFLOAT32ABCDHzRead
IR19052Phase order1 = correct 1-2-3, -1 = inverted 1-3-2, 0 = unknown (as a float).FLOAT32ABCDRead
IR19110THD voltage L1FLOAT32ABCD%Read
IR19112THD voltage L2FLOAT32ABCD%Read
IR19114THD voltage L3FLOAT32ABCD%Read
IR19116THD current L1FLOAT32ABCD%Read
IR19118THD current L2FLOAT32ABCD%Read
IR19120THD current L3FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)

What Modbus registers does the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) have?

This map lists 41 registers: 41 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in decimal and hex as PDU (wire) addresses. The manual's modpoll examples use the -0 switch ('Modbus PDU addressing') with -r 528 for the device number and -r 4352 for the voltages, and a footnote says that without -0 every address would need +1.

What byte order does the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)?

Start with IR 19000 Voltage L1-N (Voltage L1-N); IR 19012 Current L1 (Current L1); IR 19026 Active power total (Total active power); IR 19034 Apparent power total (Total apparent power); IR 19050 Frequency (Frequency); IR 4864 Power factor total (Total power factor); IR 4097 Error code (Instrument error flags (0 = OK)).

How do I enable Modbus control of the KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)?

Modbus TCP is on by default on Ethernet models (port 502, configurable with the TCP/IP settings). For RS-485 set the device address, baud rate and parity in the instrument (see its user manual); Modbus RTU is detected automatically.

Where is the official KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0) Modbus documentation?

The source is Modbus-TCP and Modbus-RTU protocol documentation for panel meters, power quality analyzers and power factor controllers (Modbus manual v4.0 EN rev 1.8), revision 2023-01-19, published free by KMB systems at https://kmb.cz/en/download/download-documents/4-application-notes?download=200:modbus-manual-v4-0-en.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus-TCP and Modbus-RTU protocol documentation for panel meters, power quality analyzers and power factor controllers · Modbus manual v4.0 EN rev 1.8 · rev. 2023-01-19. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.