- NMID11 / NMID12 / NMID13 single-phase energy meter
Energy meter (DIN-rail, single-phase, MID) · Modbus register map
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter Modbus register map
Updated 17 November 2026
Single-phase MID energy meters with an RS-485 Modbus RTU port. Values are IEEE-754 floats in two registers, high word first, readable as input registers (3X) and mirrored as holding registers (4X). This map covers the 3X measurement table: instantaneous values, demands, total, tariff and partial energies with overflow counters.
This page lists 86 Modbus registers for the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- NMID11 / NMID12 / NMID13 single-phase energy meter
- Equipment type
- Energy meter (DIN-rail, single-phase, MID)
- Registers
- 86 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- NMID11, NMID12, NMID13
Integration notes: Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Poll input registers 0x00-0x1F with function 04 for voltage, current, powers and power factor, then 0x6C and 0x70 for import/export energy. Each value is a float in two registers, high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | Voltage | Read |
| IR 6 | Current | FLOAT32 ABCD | Current | Read |
| IR 12 | Active Power | FLOAT32 ABCD | Active power | Read |
| IR 30 | Power Factor | FLOAT32 ABCD | Power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 108 | Active Import Energy | FLOAT32 ABCD | Active import energy | Read |
| IR 112 | Active Export Energy | FLOAT32 ABCD | Active export energy | Read |
Enable Modbus control & writes
Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.
Byte order & addressing
- Read two registers per value and never start a read in the middle of a float (exception 02).
- Keep one request to 40 parameters (80 registers) or fewer.
Network setup
- Factory settings: address 1, 9600 baud, no parity, 1 stop bit (nonE1).
- Parity choices are nonE1, nonE2, EVEn and odd.
- Broadcast address 0 is not supported.
Watch out for
- Energy needs the overflow counter for very large totals.
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 (0x0000) | Voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 6doc 30007 (0x0006) | Current | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 (0x000C) | Active Power | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 (0x0012) | Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 (0x0018) | Reactive Power | FLOAT32 | ABCD | VAr | Read | |||
| IR | 30doc 30031 (0x001E) | Power Factor | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 (0x0046) | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 (0x0048) | W Import Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 74doc 30075 (0x004A) | W Import Max Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 76doc 30077 (0x004C) | W Export Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 78doc 30079 (0x004E) | W Exp. Max Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 80doc 30081 (0x0050) | var Imp. / Ind Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 82doc 30083 (0x0052) | var Imp. / Ind Max Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 86doc 30087 (0x0056) | var Exp. / Cap Max Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 88doc 30089 (0x0058) | va Imp. Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 90doc 30091 (0x005A) | va Imp. Max Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 92doc 30093 (0x005C) | va Exp. Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 94doc 30095 (0x005E) | va Exp. Max Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 96doc 30097 (0x0060) | Current Imp. Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 98doc 30099 (0x0062) | Current Imp Max. Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 106doc 30107 (0x006A) | Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 (0x006C) | Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 110doc 30111 (0x006E) | Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 (0x0070) | Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 114doc 30115 (0x0072) | Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 (0x0074) | Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 118doc 30119 (0x0076) | Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 (0x0078) | Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 122doc 30123 (0x007A) | Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 (0x007C) | Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 130doc 30131 (0x0082) | Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 (0x0084) | Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 134doc 30135 (0x0086) | Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 (0x0088) | Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 138doc 30139 (0x008A) | Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 (0x008C) | Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 142doc 30143 (0x008E) | T1 Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 (0x0090) | T1 Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 146doc 30147 (0x0092) | T1 Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 (0x0094) | T1 Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 150doc 30151 (0x0096) | T1 Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 (0x0098) | T1 Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 154doc 30155 (0x009A) | T1 Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 (0x009C) | T1 Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 158doc 30159 (0x009E) | T1 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 (0x00A0) | T1 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 166doc 30167 (0x00A6) | T1 Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 168doc 30169 (0x00A8) | T1 Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 170doc 30171 (0x00AA) | T1 Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 (0x00AC) | T1 Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 174doc 30175 (0x00AE) | T1 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 176doc 30177 (0x00B0) | T1 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 178doc 30179 (0x00B2) | T2 Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 (0x00B4) | T2 Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 182doc 30183 (0x00B6) | T2 Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 (0x00B8) | T2 Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 186doc 30187 (0x00BA) | T2 Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 (0x00BC) | T2 Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 190doc 30191 (0x00BE) | T2 Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 (0x00C0) | T2 Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 194doc 30195 (0x00C2) | T2 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 196doc 30197 (0x00C4) | T2 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 202doc 30203 (0x00CA) | T2 Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 (0x00CC) | T2 Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 206doc 30207 (0x00CE) | T2 Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 (0x00D0) | T2 Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 210doc 30211 (0x00D2) | T2 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 212doc 30213 (0x00D4) | T2 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 214doc 30215 (0x00D6) | Partial Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 (0x00DA) | Partial Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 (0x00DC) | Partial Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 222doc 30223 (0x00DE) | Partial Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 (0x00E0) | Partial Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 226doc 30227 (0x00E2) | partial Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 (0x00E4) | Partial Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 230doc 30231 (0x00E6) | Partial Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 (0x00E8) | Partial Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 238doc 30239 (0x00EE) | Partial Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 (0x00F0) | Partial Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 242doc 30243 (0x00F2) | Partial Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 (0x00F6) | Partial Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 (0x00F8) | Partial Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 254doc 30255 (0x00FE) | No of Interrupts | FLOAT32 | ABCD | Read | ||||
| IR | 256doc 30257 (0x0100) | Impulse Rate | FLOAT32 | ABCD | Read | ||||
| IR | 260doc 30261 (0x0104) | Tariff Status | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 (0x0106) | Current Direction | 0 = current flows the right way, 1 = reversed. | FLOAT32 | ABCD | Read |
Notes on this map
- Format is stated as 4 bytes per parameter, IEEE-754 float, most significant byte first; the example frames return 43 66 00 00 for 230 V and 40 A0 00 00 for 5 A, which settles high word first.
- The same values sit in the 4X (holding register) area at the same addresses; this map lists the 3X copy only.
- Left out: 0x54 (labelled the same as 0x56), 0xD8 (Partial Active Import Energy, printed with unit 'Wh' unlike its neighbours) and 0xF4 (Partial Total Reactive Energy, unit printed 'kArh'); the long-energy table 5 because its format is not spelled out; the 4X setup table and the assignable area.
- Energy registers count up to 99999.999 and the matching overflow register counts the roll-overs.
- Table 4 uses the label 'Total Apparent Energy' twice (0x7A/0x7C and 0x8A/0x8C), and likewise for the T1, T2 and partial groups; both copies are listed as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
What Modbus registers does the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter have?
This map lists 86 registers: 86 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The measurement table prints Modicon numbers (30001) next to the hex start address (00 00). The hex column is the wire address, so 30001 is register 0 and power factor 30031 is 0x1E.
What byte order does the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter?
Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active Power (Active power); IR 30 Power Factor (Power factor); IR 70 Frequency (Frequency); IR 108 Active Import Energy (Active import energy); IR 112 Active Export Energy (Active export energy).
How do I enable Modbus control of the Lumel NMID11 / NMID12 / NMID13 single-phase energy meter?
Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.
Where is the official Lumel NMID11 / NMID12 / NMID13 single-phase energy meter Modbus documentation?
The source is NMID11, NMID12, NMID13 DIN rail mount single phase energy meter - User Manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/liczniki%20energii/NMID11_NMID12_NMID13_user_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350 - Energy meter module
Peacefair PZEM-014 / PZEM-016
Peacefair PZEM-014 (10 A shunt) and PZEM-016 (100 A CT) single-phase AC RS485 modules; the PZEM-004T V3.0 (TTL UART) datasheet prints the identical register map.
Also known as: PZEM-014, PZEM-016, PZEM-004T V3.0, PZEM-004T-10A, PZEM-004T-100A - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II
All power & energy meters Modbus register maps →
Source: NMID11, NMID12, NMID13 DIN rail mount single phase energy meter - User Manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.