Energy meter · Modbus register map

Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus register map

Updated 19 November 2026

Short answer

The RISH EM 3490 DS is a three-phase panel energy meter that keeps separate energy, run-hour and interruption counts for utility and generator supply. It has an RS-485 Modbus RTU port. Every measured value and every setting is an IEEE 32-bit float spread over two registers: readings are input registers (FC04) from 30001, settings are holding registers (FC03 read, FC16 write) from 40005. This map covers the full measured-value table including the utility/generator counters, the setup registers and the word-order switch.

This page lists 78 Modbus registers for the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH EM 3490 DS dual-source (utility/generator) energy meter
Equipment type
Energy meter
Registers
78 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH EM 3490 DS, EM3490DS, EM 3490DS
Source document
EM 3490 DS Dual Source Energy Meter Operating Manual · 15000191 Rev. G · rev. 2012-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter

Integration in brief

Read 30001-30082 with FC04 in one or two requests (max 20 floats each) and decode each pair as a big-endian float. Settings live in 40005-40071 and are written with FC16 as floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Volts 1FLOAT32 ABCDVoltage phase 1Read
IR 6Current 1FLOAT32 ABCDCurrent phase 1Read
IR 52Watts sumFLOAT32 ABCDTotal active powerRead
IR 62PF averageFLOAT32 ABCDAverage power factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 72Wh (utility)FLOAT32 ABCDActive energyRead

Enable Modbus control & writes

Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

78 of 78 shown
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Volts 1L1-N (4-wire) or L1-L2 (3-wire) voltage.FLOAT32ABCDRead
IR2doc 30003Volts 2L2-N (4-wire) or L2-L3 (3-wire) voltage.FLOAT32ABCDRead
IR4doc 30005Volts 3L3-N (4-wire) or L3-L1 (3-wire) voltage.FLOAT32ABCDRead
IR6doc 30007Current 1FLOAT32ABCDRead
IR8doc 30009Current 2FLOAT32ABCDRead
IR10doc 30011Current 3FLOAT32ABCDRead
IR12doc 30013W13-phase 4-wire only.FLOAT32ABCDRead
IR14doc 30015W23-phase 4-wire only.FLOAT32ABCDRead
IR16doc 30017W33-phase 4-wire only.FLOAT32ABCDRead
IR18doc 30019VA13-phase 4-wire only.FLOAT32ABCDRead
IR20doc 30021VA23-phase 4-wire only.FLOAT32ABCDRead
IR22doc 30023VA33-phase 4-wire only.FLOAT32ABCDRead
IR24doc 30025VAr13-phase 4-wire only.FLOAT32ABCDRead
IR26doc 30027VAr23-phase 4-wire only.FLOAT32ABCDRead
IR28doc 30029VAr33-phase 4-wire only.FLOAT32ABCDRead
IR30doc 30031PF13-phase 4-wire only.FLOAT32ABCDRead
IR32doc 30033PF23-phase 4-wire only.FLOAT32ABCDRead
IR34doc 30035PF33-phase 4-wire only.FLOAT32ABCDRead
IR36doc 30037Phase angle 13-phase 4-wire only.FLOAT32ABCDRead
IR38doc 30039Phase angle 23-phase 4-wire only.FLOAT32ABCDRead
IR40doc 30041Phase angle 33-phase 4-wire only.FLOAT32ABCDRead
IR42doc 30043Volts averageFLOAT32ABCDRead
IR44doc 30045Volts sumFLOAT32ABCDRead
IR46doc 30047Current averageFLOAT32ABCDRead
IR48doc 30049Current sumFLOAT32ABCDRead
IR50doc 30051Watts averageFLOAT32ABCDRead
IR52doc 30053Watts sumFLOAT32ABCDRead
IR54doc 30055VA averageFLOAT32ABCDRead
IR56doc 30057VA sumFLOAT32ABCDRead
IR58doc 30059VAr averageFLOAT32ABCDRead
IR60doc 30061VAr sumFLOAT32ABCDRead
IR62doc 30063PF averageFLOAT32ABCDRead
IR64doc 30065PF sum3-phase 4-wire only.FLOAT32ABCDRead
IR66doc 30067Phase angle averageFLOAT32ABCDRead
IR68doc 30069Phase angle sum3-phase 4-wire only.FLOAT32ABCDRead
IR70doc 30071FrequencyFLOAT32ABCDRead
IR72doc 30073Wh (utility)Unit follows 40005 (Wh/kWh/MWh).FLOAT32ABCDRead
IR80doc 30081VAh (utility)Unit follows 40005.FLOAT32ABCDRead
IR200doc 30201VL1-2 (calculated)3-phase 4-wire only.FLOAT32ABCDRead
IR202doc 30203VL2-3 (calculated)3-phase 4-wire only.FLOAT32ABCDRead
IR204doc 30205VL3-1 (calculated)3-phase 4-wire only.FLOAT32ABCDRead
IR226doc 30227Run hour (utility)FLOAT32ABCDRead
IR228doc 30229On hour (utility)FLOAT32ABCDRead
IR230doc 30231No. of interrupts (utility)FLOAT32ABCDRead
IR232doc 30233Wh (generator)Unit follows 40005.FLOAT32ABCDRead
IR234doc 30235VAh (generator)Unit follows 40005.FLOAT32ABCDRead
IR236doc 30237Run hour (generator)FLOAT32ABCDRead
IR238doc 30239On hour (generator)FLOAT32ABCDRead
IR240doc 30241No. of interrupts (generator)FLOAT32ABCDRead
IR242doc 30243Total run hourFLOAT32ABCDRead
IR244doc 30245Total on hourFLOAT32ABCDRead
IR246doc 30247Old kWh (utility)FLOAT32ABCDRead
IR248doc 30249Old kWh (generator)FLOAT32ABCDRead
IR250doc 30251Old run hour (utility)FLOAT32ABCDRead
IR252doc 30253Old run hour (generator)FLOAT32ABCDRead
IR254doc 30255Old on hour (utility)FLOAT32ABCDRead
IR256doc 30257Old on hour (generator)FLOAT32ABCDRead
IR258doc 30259Old total run hour (generator)FLOAT32ABCDRead
IR260doc 30261Old total on hourFLOAT32ABCDRead
IR262doc 30263Old no. of interruptions (utility)FLOAT32ABCDRead
IR264doc 30265Old no. of interruptions (generator)FLOAT32ABCDRead
HR4doc 40005Energy display on ModbusUnit of the energy registers 30073/30081.FLOAT32ABCDRead/write1 = Wh; 2 = kWh; 3 = MWh
HR6doc 40007System voltageNominal system voltage.FLOAT32ABCDRead
HR8doc 40009System currentNominal system current.FLOAT32ABCDRead
HR10doc 40011System typeFLOAT32ABCDRead/write2 = 3-phase 3-wire; 3 = 3-phase 4-wire
HR12doc 40013Pulse width of relayFLOAT32ABCDRead/write60 = 60 ms; 100 = 100 ms; 200 = 200 ms
HR14doc 40015Reset energy counterWrite 0 to clear the energy counters.FLOAT32ABCDWrite
HR16doc 40017Run/on hour and interruption resetWrite 0 to clear run/on hours and interruption counts.FLOAT32ABCDWrite
HR18doc 40019RS485 set-up codeBaud, parity and stop bits in one code.FLOAT32ABCDRead/write0 = 2400 bps, no parity, 1 stop; 1 = 2400 bps, no parity, 2 stop; 2 = 2400 bps, even, 1 stop; 3 = 2400 bps, odd, 1 stop; 4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop
HR20doc 40021Node address1-247.FLOAT32ABCDRead/write
HR22doc 40023Pulse divisorFLOAT32ABCDRead/write1 = Divisor 1; 10 = Divisor 10; 100 = Divisor 100; 1000 = Divisor 1000
HR32doc 40033PT primaryIn volts, e.g. 2000 for 2 kV.FLOAT32ABCDRead/write
HR34doc 40035CT primaryUp to 9999.FLOAT32ABCDRead/write
HR36doc 40037System powerNominal power from nominal volts and current.FLOAT32ABCDRead
HR38doc 40039Energy digit rollover (reset) countNumber of digits before energy rolls over to zero.FLOAT32ABCDRead/write
HR40doc 40041Register order / word orderWrite 2141.0 in the wanted order to switch normal/reversed float word order.FLOAT32ABCDRead/write
HR44doc 40045PT secondaryRange per manual section 3.2.1.3.FLOAT32ABCDRead/write
HR70doc 40071Password0000-9999; reads 0 when locked, 1 when unlocked.FLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter

What Modbus registers does the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter have?

This map lists 78 registers: 61 input registers, 17 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style register numbers next to the hex start address that goes on the wire (30001 = 00 00, 40011 = 00 0A). Wire address = printed number - 30001 or - 40001; every row was checked against the printed hex.

What byte order does the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter?

Start with IR 0 Volts 1 (Voltage phase 1); IR 6 Current 1 (Current phase 1); IR 52 Watts sum (Total active power); IR 62 PF average (Average power factor); IR 70 Frequency (Frequency); IR 72 Wh (utility) (Active energy).

How do I enable Modbus control of the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter?

Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.

Where is the official Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus documentation?

The source is EM 3490 DS Dual Source Energy Meter Operating Manual (15000191 Rev. G), revision 2012-08, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/dual-source-energy-meter-em3490ds-151/EM_3490_DS_MANUAL_REV-G.pdf.