Energy meter · Modbus register map
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus register map
Updated 19 November 2026
The RISH EM 3490 DS is a three-phase panel energy meter that keeps separate energy, run-hour and interruption counts for utility and generator supply. It has an RS-485 Modbus RTU port. Every measured value and every setting is an IEEE 32-bit float spread over two registers: readings are input registers (FC04) from 30001, settings are holding registers (FC03 read, FC16 write) from 40005. This map covers the full measured-value table including the utility/generator counters, the setup registers and the word-order switch.
This page lists 78 Modbus registers for the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH EM 3490 DS dual-source (utility/generator) energy meter
- Equipment type
- Energy meter
- Registers
- 78 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH EM 3490 DS, EM3490DS, EM 3490DS
Integration notes: Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Read 30001-30082 with FC04 in one or two requests (max 20 floats each) and decode each pair as a big-endian float. Settings live in 40005-40071 and are written with FC16 as floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Volts 1 | FLOAT32 ABCD | Voltage phase 1 | Read |
| IR 6 | Current 1 | FLOAT32 ABCD | Current phase 1 | Read |
| IR 52 | Watts sum | FLOAT32 ABCD | Total active power | Read |
| IR 62 | PF average | FLOAT32 ABCD | Average power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Wh (utility) | FLOAT32 ABCD | Active energy | Read |
Enable Modbus control & writes
Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.
Byte order & addressing
- Settings are floats too: system type 3 reads back as 40 40 00 00, and writing 2 (3-phase 3-wire) sends 40 00 00 00.
- Reading or writing only part of a float returns exception 02 (illegal data address).
- 40041 switches the float word order for every register; write 2141.0 in the order you want to use.
Network setup
- RS485 set-up code (40019) packs baud, parity and stop bits; see the value list.
- If a password is set, write it to 40071 before changing any 4X register.
Watch out for
- The energy unit (Wh/kWh/MWh) is a setting, so scale energy values according to 40005.
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Volts 1 | L1-N (4-wire) or L1-L2 (3-wire) voltage. | FLOAT32 | ABCD | Read | |||
| IR | 2doc 30003 | Volts 2 | L2-N (4-wire) or L2-L3 (3-wire) voltage. | FLOAT32 | ABCD | Read | |||
| IR | 4doc 30005 | Volts 3 | L3-N (4-wire) or L3-L1 (3-wire) voltage. | FLOAT32 | ABCD | Read | |||
| IR | 6doc 30007 | Current 1 | FLOAT32 | ABCD | Read | ||||
| IR | 8doc 30009 | Current 2 | FLOAT32 | ABCD | Read | ||||
| IR | 10doc 30011 | Current 3 | FLOAT32 | ABCD | Read | ||||
| IR | 12doc 30013 | W1 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 14doc 30015 | W2 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 16doc 30017 | W3 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | VA1 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | VA2 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | VA3 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | VAr1 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 26doc 30027 | VAr2 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | VAr3 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | PF1 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | PF2 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | PF3 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Phase angle 1 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Phase angle 2 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Phase angle 3 | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Volts average | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Volts sum | FLOAT32 | ABCD | Read | ||||
| IR | 46doc 30047 | Current average | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Current sum | FLOAT32 | ABCD | Read | ||||
| IR | 50doc 30051 | Watts average | FLOAT32 | ABCD | Read | ||||
| IR | 52doc 30053 | Watts sum | FLOAT32 | ABCD | Read | ||||
| IR | 54doc 30055 | VA average | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | VA sum | FLOAT32 | ABCD | Read | ||||
| IR | 58doc 30059 | VAr average | FLOAT32 | ABCD | Read | ||||
| IR | 60doc 30061 | VAr sum | FLOAT32 | ABCD | Read | ||||
| IR | 62doc 30063 | PF average | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 | PF sum | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Phase angle average | FLOAT32 | ABCD | Read | ||||
| IR | 68doc 30069 | Phase angle sum | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Frequency | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Wh (utility) | Unit follows 40005 (Wh/kWh/MWh). | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | VAh (utility) | Unit follows 40005. | FLOAT32 | ABCD | Read | |||
| IR | 200doc 30201 | VL1-2 (calculated) | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | VL2-3 (calculated) | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | VL3-1 (calculated) | 3-phase 4-wire only. | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Run hour (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 228doc 30229 | On hour (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 230doc 30231 | No. of interrupts (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 232doc 30233 | Wh (generator) | Unit follows 40005. | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | VAh (generator) | Unit follows 40005. | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Run hour (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 238doc 30239 | On hour (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 240doc 30241 | No. of interrupts (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 242doc 30243 | Total run hour | FLOAT32 | ABCD | Read | ||||
| IR | 244doc 30245 | Total on hour | FLOAT32 | ABCD | Read | ||||
| IR | 246doc 30247 | Old kWh (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 248doc 30249 | Old kWh (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 250doc 30251 | Old run hour (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 252doc 30253 | Old run hour (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 254doc 30255 | Old on hour (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 256doc 30257 | Old on hour (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 258doc 30259 | Old total run hour (generator) | FLOAT32 | ABCD | Read | ||||
| IR | 260doc 30261 | Old total on hour | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 | Old no. of interruptions (utility) | FLOAT32 | ABCD | Read | ||||
| IR | 264doc 30265 | Old no. of interruptions (generator) | FLOAT32 | ABCD | Read | ||||
| HR | 4doc 40005 | Energy display on Modbus | Unit of the energy registers 30073/30081. | FLOAT32 | ABCD | Read/write | 1 = Wh; 2 = kWh; 3 = MWh | ||
| HR | 6doc 40007 | System voltage | Nominal system voltage. | FLOAT32 | ABCD | Read | |||
| HR | 8doc 40009 | System current | Nominal system current. | FLOAT32 | ABCD | Read | |||
| HR | 10doc 40011 | System type | FLOAT32 | ABCD | Read/write | 2 = 3-phase 3-wire; 3 = 3-phase 4-wire | |||
| HR | 12doc 40013 | Pulse width of relay | FLOAT32 | ABCD | Read/write | 60 = 60 ms; 100 = 100 ms; 200 = 200 ms | |||
| HR | 14doc 40015 | Reset energy counter | Write 0 to clear the energy counters. | FLOAT32 | ABCD | Write | |||
| HR | 16doc 40017 | Run/on hour and interruption reset | Write 0 to clear run/on hours and interruption counts. | FLOAT32 | ABCD | Write | |||
| HR | 18doc 40019 | RS485 set-up code | Baud, parity and stop bits in one code. | FLOAT32 | ABCD | Read/write | 0 = 2400 bps, no parity, 1 stop; 1 = 2400 bps, no parity, 2 stop; 2 = 2400 bps, even, 1 stop; 3 = 2400 bps, odd, 1 stop; 4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop | ||
| HR | 20doc 40021 | Node address | 1-247. | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Pulse divisor | FLOAT32 | ABCD | Read/write | 1 = Divisor 1; 10 = Divisor 10; 100 = Divisor 100; 1000 = Divisor 1000 | |||
| HR | 32doc 40033 | PT primary | In volts, e.g. 2000 for 2 kV. | FLOAT32 | ABCD | Read/write | |||
| HR | 34doc 40035 | CT primary | Up to 9999. | FLOAT32 | ABCD | Read/write | |||
| HR | 36doc 40037 | System power | Nominal power from nominal volts and current. | FLOAT32 | ABCD | Read | |||
| HR | 38doc 40039 | Energy digit rollover (reset) count | Number of digits before energy rolls over to zero. | FLOAT32 | ABCD | Read/write | |||
| HR | 40doc 40041 | Register order / word order | Write 2141.0 in the wanted order to switch normal/reversed float word order. | FLOAT32 | ABCD | Read/write | |||
| HR | 44doc 40045 | PT secondary | Range per manual section 3.2.1.3. | FLOAT32 | ABCD | Read/write | |||
| HR | 70doc 40071 | Password | 0000-9999; reads 0 when locked, 1 when unlocked. | FLOAT32 | ABCD | Read/write |
Notes on this map
- All registers are IEEE 754 32-bit floats in two consecutive registers, most significant byte first (stated in the data-format table). The read example for Volts 3 returns 43 5B 41 21 (219.25 V), most significant word first, so ABCD is the default; 40041 can switch the meter to reversed order.
- The register table has no unit column, so units are left blank. The manual notes active energy reads in Wh and apparent energy in VAh, while 40005 lets you change the energy unit to kWh or MWh.
- Rows marked '3-phase 4-wire only' are not available on a meter set to 3-phase 3-wire.
- Up to 20 parameters (40 registers) per read; larger requests return an exception.
- Left out: the 20 user-assignable registers (30513-30551, mapped through 40513-40534), which mirror any 3X value; see the manual's Tables 9 and 10.
- Serial defaults are not printed in the manual; baud is selectable 2400-19200 bps (40019 or front panel).
- 30225 (parameter 113) has no name in the table and is left out. Run/on hour units are not printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
What Modbus registers does the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter have?
This map lists 78 registers: 61 input registers, 17 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style register numbers next to the hex start address that goes on the wire (30001 = 00 00, 40011 = 00 0A). Wire address = printed number - 30001 or - 40001; every row was checked against the printed hex.
What byte order does the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter?
Start with IR 0 Volts 1 (Voltage phase 1); IR 6 Current 1 (Current phase 1); IR 52 Watts sum (Total active power); IR 62 PF average (Average power factor); IR 70 Frequency (Frequency); IR 72 Wh (utility) (Active energy).
How do I enable Modbus control of the Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter?
Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.
Where is the official Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter Modbus documentation?
The source is EM 3490 DS Dual Source Energy Meter Operating Manual (15000191 Rev. G), revision 2012-08, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/dual-source-energy-meter-em3490ds-151/EM_3490_DS_MANUAL_REV-G.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Other power & energy meters register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Power meter
Accuenergy Acuvim II Series
Accuenergy Acuvim II series multifunction power meters (manual 1040E1303, V3.2.16 revised September 2026).
Also known as: Acuvim IIR, Acuvim IIW
All power & energy meters Modbus register maps →
Source: EM 3490 DS Dual Source Energy Meter Operating Manual · 15000191 Rev. G · rev. 2012-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.