- RISH PFC 96 / PFC 144 automatic power factor controller
Power meter (power factor controller) · Modbus register map
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller Modbus register map
Updated 19 November 2026
The RISH PFC 96 and PFC 144 are panel automatic power factor controllers that switch up to 12 capacitor banks while metering the line. Their RS-485 port speaks Modbus RTU and every value is an IEEE 754 float in two registers. This map covers the metering, demand, energy, max/min, THD, run-hour and per-bank kvar and switching-count registers (30001-30317) plus the main controller and communication settings.
This page lists 144 Modbus registers for the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH PFC 96 / PFC 144 automatic power factor controller
- Equipment type
- Power meter (power factor controller)
- Registers
- 144 (33 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Integration notes: Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Read 30001-30038 and 30071-30108 with FC04 for line values, demand and energy, and 30245-30317 for bank data, decoding each register pair as a big-endian float. Controller settings are floats in the 4X area written with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Line Voltage | FLOAT32 ABCD | Line voltage | Read |
| IR 6 | Line Current | FLOAT32 ABCD | Line current | Read |
| IR 30 | Power Factor | FLOAT32 ABCD | Power factor | Read |
| IR 24 | Reactive Power | FLOAT32 ABCD | Reactive power | Read |
| IR 244 | Difference to Power Factor | FLOAT32 ABCD | Difference to target power factor | Read |
| IR 218 | System Voltage THD % | FLOAT32 ABCD | Voltage THD | Read |
Enable Modbus control & writes
Set the RS-485 address and baud/parity in the controller's communication menu or via 40021/40019.
Byte order & addressing
- Reading or writing half a float returns exception 02.
- Settings marked WP are write-protected: send the basic password (40071) or, for advanced settings, the advanced password (40205) first if one is set.
Network setup
- Default setup code 5 = 9600 bps, no parity, 2 stop bits; device address 1.
Watch out for
- Capacitor discharge time (40129) must match the installed capacitors before banks are switched remotely.
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Line Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 6doc 30007 | Line Current | FLOAT32 | ABCD | Read | ||||
| IR | 12doc 30013 | Active Power | FLOAT32 | ABCD | Read | ||||
| IR | 18doc 30019 | Apparent Power | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | Reactive Power | FLOAT32 | ABCD | Read | ||||
| IR | 30doc 30031 | Power Factor | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Phase Angle | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Frequency | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Active Import Energy | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Active Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | Inductive Reactive Energy | FLOAT32 | ABCD | Read | ||||
| IR | 78doc 30079 | Capacitive Reactive Energy | FLOAT32 | ABCD | Read | ||||
| IR | 80doc 30081 | Apparent Energy | FLOAT32 | ABCD | Read | ||||
| IR | 84doc 30085 | Active Import Demand | FLOAT32 | ABCD | Read | ||||
| IR | 86doc 30087 | Maximum Active Import Demand | FLOAT32 | ABCD | Read | ||||
| IR | 88doc 30089 | Active Export Demand | FLOAT32 | ABCD | Read | ||||
| IR | 90doc 30091 | Maximum Active Export Demand | FLOAT32 | ABCD | Read | ||||
| IR | 92doc 30093 | Old Max Active Import Demand | FLOAT32 | ABCD | Read | ||||
| IR | 94doc 30095 | Old Max Active Export Demand | FLOAT32 | ABCD | Read | ||||
| IR | 96doc 30097 | Old Max Apparent Demand | FLOAT32 | ABCD | Read | ||||
| IR | 98doc 30099 | Old Max Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 100doc 30101 | Apparent Demand | FLOAT32 | ABCD | Read | ||||
| IR | 102doc 30103 | Max Apparent Demand | FLOAT32 | ABCD | Read | ||||
| IR | 104doc 30105 | Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | Max Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 108doc 30109 | Active Import Energy Overflow Count | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Active Export Energy Overflow Count | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Reactive Inductive Energy Overflow Count | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Reactive Capacitive Energy Overflow Count | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Apparent Energy Overflow Count | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | System temperature | FLOAT32 | ABCD | Read | ||||
| IR | 144doc 30145 | Active Import Energy on update Rate | Refreshed at the energy update rate (40081). | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Active Export Energy on update Rate | Refreshed at the energy update rate (40081). | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Reactive Inductive Energy on update Rate | Refreshed at the energy update rate (40081). | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Reactive Capacitive Energy on update Rate | Refreshed at the energy update rate (40081). | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Apparent Energy on update Rate | Refreshed at the energy update rate (40081). | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Active Import Energy Overflow on update Rate | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Active Export Energy Overflow on update Rate | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Reactive Inductive Energy Overflow on update Rate | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Reactive Capacitive Energy Overflow on update Rate | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Apparent Energy Overflow on update Rate | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 | Old Active Export Energy Overflow | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 174doc 30175 | Old Active Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 176doc 30177 | Old Reactive Import Energy Overflow | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 178doc 30179 | Old Reactive Import Energy | FLOAT32 | ABCD | Read | ||||
| IR | 180doc 30181 | Old Reactive Export Energy Overflow | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 182doc 30183 | Old Reactive Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 184doc 30185 | Old Apparent Energy Overflow | Roll-over count of the matching energy register. | FLOAT32 | ABCD | Read | |||
| IR | 186doc 30187 | Old Apparent Energy | FLOAT32 | ABCD | Read | ||||
| IR | 188doc 30189 | Maximum System Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 190doc 30191 | Maximum System Current | FLOAT32 | ABCD | Read | ||||
| IR | 192doc 30193 | Maximum Active Import Power | FLOAT32 | ABCD | Read | ||||
| IR | 194doc 30195 | Maximum Active Export Power | FLOAT32 | ABCD | Read | ||||
| IR | 196doc 30197 | Maximum Inductive Reactive Power | FLOAT32 | ABCD | Read | ||||
| IR | 198doc 30199 | Maximum Capacitive Reactive Power | FLOAT32 | ABCD | Read | ||||
| IR | 200doc 30201 | Maximum Apparent Power | FLOAT32 | ABCD | Read | ||||
| IR | 202doc 30203 | Maximum Voltage THD | FLOAT32 | ABCD | Read | ||||
| IR | 204doc 30205 | Maximum Current THD | FLOAT32 | ABCD | Read | ||||
| IR | 206doc 30207 | Maximum Frequency | FLOAT32 | ABCD | Read | ||||
| IR | 208doc 30209 | Maximum Temperature | FLOAT32 | ABCD | Read | ||||
| IR | 210doc 30211 | Minimum System Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 212doc 30213 | Minimum System Current | FLOAT32 | ABCD | Read | ||||
| IR | 214doc 30215 | Minimum Frequency | FLOAT32 | ABCD | Read | ||||
| IR | 216doc 30217 | Minimum Temperature | FLOAT32 | ABCD | Read | ||||
| IR | 218doc 30219 | System Voltage THD % | FLOAT32 | ABCD | Read | ||||
| IR | 220doc 30221 | System Current THD % | FLOAT32 | ABCD | Read | ||||
| IR | 222doc 30223 | Old Run Hour | FLOAT32 | ABCD | Read | ||||
| IR | 224doc 30225 | Old ON Hour | FLOAT32 | ABCD | Read | ||||
| IR | 226doc 30227 | Run Hour | FLOAT32 | ABCD | Read | ||||
| IR | 228doc 30229 | ON Hour | FLOAT32 | ABCD | Read | ||||
| IR | 230doc 30231 | Power Down Interruption Count | FLOAT32 | ABCD | Read | ||||
| IR | 232doc 30233 | Power Down Interruption Time | FLOAT32 | ABCD | Read | ||||
| IR | 234doc 30235 | Power Down Interruption Date | FLOAT32 | ABCD | Read | ||||
| IR | 244doc 30245 | Difference to Power Factor | FLOAT32 | ABCD | Read | ||||
| IR | 246doc 30247 | Capacitor Bank 1 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 248doc 30249 | Capacitor Bank 2 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 250doc 30251 | Capacitor Bank 3 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 252doc 30253 | Capacitor Bank 4 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 254doc 30255 | Capacitor Bank 5 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 256doc 30257 | Capacitor Bank 6 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 258doc 30259 | Capacitor Bank 7 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 260doc 30261 | Capacitor Bank 8 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 | Capacitor Bank 9 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 264doc 30265 | Capacitor Bank 10 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 266doc 30267 | Capacitor Bank 11 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 268doc 30269 | Capacitor Bank 12 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 270doc 30271 | Test Run Capacitor Bank 1 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 272doc 30273 | Test Run Capacitor Bank 2 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 274doc 30275 | Test Run Capacitor Bank 3 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 276doc 30277 | Test Run Capacitor Bank 4 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 278doc 30279 | Test Run Capacitor Bank 5 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 280doc 30281 | Test Run Capacitor Bank 6 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 282doc 30283 | Test Run Capacitor Bank 7 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 284doc 30285 | Test Run Capacitor Bank 8 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 286doc 30287 | Test Run Capacitor Bank 9 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 288doc 30289 | Test Run Capacitor Bank 10 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 290doc 30291 | Test Run Capacitor Bank 11 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 292doc 30293 | Test Run Capacitor Bank 12 KVAr value | FLOAT32 | ABCD | Read | ||||
| IR | 294doc 30295 | Bank 1 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 296doc 30297 | Bank 2 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 298doc 30299 | Bank 3 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 300doc 30301 | Bank 4 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 302doc 30303 | Bank 5 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 304doc 30305 | Bank 6 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 306doc 30307 | Bank 7 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 308doc 30309 | Bank 8 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 310doc 30311 | Bank 9 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 312doc 30313 | Bank 10 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 314doc 30315 | Bank 11 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| IR | 316doc 30317 | Bank 12 No. of Switching operations | FLOAT32 | ABCD | Read | ||||
| HR | 2doc 40003 | Demand integration time | FLOAT32 | ABCD | Read/write | 8 = 8 min; 15 = 15 min; 20 = 20 min; 30 = 30 min | |||
| HR | 4doc 40005 | Energy unit | Default 2. | FLOAT32 | ABCD | Read/write | 1 = Wh; 2 = kWh; 3 = MWh | ||
| HR | 6doc 40007 | System nominal voltage | 50-550 V AC; default 240. | FLOAT32 | ABCD | Read/write | |||
| HR | 10doc 40011 | System type | Default 1. | FLOAT32 | ABCD | Read/write | 0 = 1 phase; 1 = 3 phase | ||
| HR | 14doc 40015 | Reset parameters | 11-22 reset one bank's switching count, 23-34 one bank's operation time. | FLOAT32 | ABCD | Read/write | 1 = Energy; 2 = Demand; 3 = Minimum values; 4 = Maximum values; 5 = Run hour / on hour; 6 = Power down interruption; 7 = All bank switching counts; 8 = All bank operation times; 10 = All (energy, max, min, run/on hour) | ||
| HR | 18doc 40019 | RS 485 setup code | Baud, parity and stop bits in one code; default 5. | FLOAT32 | ABCD | Read/write | 0 = 4800 bps, no parity, 1 stop; 1 = 4800 bps, no parity, 2 stop; 2 = 4800 bps, even, 1 stop; 3 = 4800 bps, odd, 1 stop; 4 = 9600 bps, no parity, 1 stop; 5 = 9600 bps, no parity, 2 stop; 6 = 9600 bps, even, 1 stop; 7 = 9600 bps, odd, 1 stop; 8 = 19200 bps, no parity, 1 stop; 9 = 19200 bps, no parity, 2 stop; 10 = 19200 bps, even, 1 stop; 11 = 19200 bps, odd, 1 stop; 12 = 38400 bps, no parity, 1 stop; 13 = 38400 bps, no parity, 2 stop; 14 = 38400 bps, even, 1 stop; 15 = 38400 bps, odd, 1 stop; 16 = 57600 bps, no parity, 1 stop; 17 = 57600 bps, no parity, 2 stop; 18 = 57600 bps, even, 1 stop; 19 = 57600 bps, odd, 1 stop | ||
| HR | 20doc 40021 | Device address | 1-247; default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 34doc 40035 | CT primary | 1-9999 A; default 1000. | FLOAT32 | ABCD | Read/write | |||
| HR | 38doc 40039 | Energy digit reset count | 7-9; default 8. | FLOAT32 | ABCD | Read/write | |||
| HR | 40doc 40041 | Register order | Normal (most significant byte first) or reversed float order; default 0. | FLOAT32 | ABCD | Read/write | |||
| HR | 42doc 40043 | CT secondary | Default 5. | FLOAT32 | ABCD | Read/write | 1 = 1 A; 5 = 5 A | ||
| HR | 70doc 40071 | Basic password | Default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 80doc 40081 | Energy update rate on Modbus | Default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 92doc 40093 | Maximum switching kvar | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 98doc 40099 | Model number | Reads 4000. | FLOAT32 | ABCD | Read | |||
| HR | 124doc 40125 | Capacitor switch on time | Default 40. | FLOAT32 | ABCD | Read/write | |||
| HR | 126doc 40127 | Capacitor switch off time | Default 40. | FLOAT32 | ABCD | Read/write | |||
| HR | 128doc 40129 | Capacitor discharge time | Default 60; must match the capacitors. | FLOAT32 | ABCD | Read/write | |||
| HR | 132doc 40133 | Target power factor | Default 0.995. | FLOAT32 | ABCD | Read/write | |||
| HR | 134doc 40135 | No. of capacitor banks | Default 8. | FLOAT32 | ABCD | Read/write | |||
| HR | 138doc 40139 | Bank switching threshold | Default 66. | FLOAT32 | ABCD | Read/write | |||
| HR | 142doc 40143 | Capacitor bank 1 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 144doc 40145 | Capacitor bank 2 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 146doc 40147 | Capacitor bank 3 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 148doc 40149 | Capacitor bank 4 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 150doc 40151 | Capacitor bank 5 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 152doc 40153 | Capacitor bank 6 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 154doc 40155 | Capacitor bank 7 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 156doc 40157 | Capacitor bank 8 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 158doc 40159 | Capacitor bank 9 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 160doc 40161 | Capacitor bank 10 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 162doc 40163 | Capacitor bank 11 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 164doc 40165 | Capacitor bank 12 kvar value | Default 25. | FLOAT32 | ABCD | Read/write | |||
| HR | 206doc 40207 | System frequency | Default 50. | FLOAT32 | ABCD | Read/write |
Notes on this map
- The data-format table states IEEE 754 floats, most significant byte first; the line-voltage example returns 43 6E FB 45. ABCD is the default and 40041 can reverse it.
- Rows whose printed hex start address does not match their register number were left out (30169 and 30171 'old active import energy', and 40235 alarm relay status). The RTC date/time rows (30131, 30133) use a packed two-digit format and are also left out.
- Left out: individual voltage/current harmonics (30321 onwards), alarm feature/set-point registers (Table 4), RTC set registers and display settings.
- No unit column is printed, so units are left blank; energy follows 40005 (default kWh).
- Register names drop the manual's superscript footnote markers (Imp = import, Exp = export, Ind = inductive, Cap = capacitive, OF = overflow).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
What Modbus registers does the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller have?
This map lists 144 registers: 110 input registers, 34 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The interface definition prints 3X/4X numbers next to the hex start address (30001 = 00 00, 30071 = 00 46, 40019 = 00 12). Wire address = number - 30001 (FC04) or - 40001 (FC03/FC16); every row here was checked against its printed hex.
What byte order does the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller?
Start with IR 0 Line Voltage (Line voltage); IR 6 Line Current (Line current); IR 30 Power Factor (Power factor); IR 24 Reactive Power (Reactive power); IR 244 Difference to Power Factor (Difference to target power factor); IR 218 System Voltage THD % (Voltage THD).
How do I enable Modbus control of the Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller?
Set the RS-485 address and baud/parity in the controller's communication menu or via 40021/40019.
Where is the official Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller Modbus documentation?
The source is Power Factor Controller PFC 144 - PFC 96 Interface Definition (Version D), revision 2018-12, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-pfc-12-228/PFC96_PFC144-Interface_Defination_REV_D1.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor
Other power & energy meters register maps
- Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Energy meter
Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)
Senva EM-RS485 three-phase energy meters with Senva CVT sensors, firmware v1.1.2, Modbus Protocol Guide 154-0023-0B (2017-04-10).
Also known as: EM-RS485, Senva EM-RS485, Senva protocol energy meter - Sensor (geotechnical: inclinometer, tiltmeter, piezometer, extensometer)
SISGEO SISGEO digital instruments, RS-485 Modbus (firmware 3.x normal mode)
SISGEO digital instruments with firmware 0x0300 or later running in normal (non-legacy) mode, protocol manual EN 05/20.
Also known as: SISGEO digital in-place inclinometer, SISGEO digital tiltmeter, SISGEO digital piezometer, SISGEO DEX, SISGEO digital extensometer - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS - Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200
All power & energy meters Modbus register maps →
Source: Power Factor Controller PFC 144 - PFC 96 Interface Definition · Version D · rev. 2018-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.