- EQ meter A41 / A42 (Modbus RTU)
Energy meter · Modbus register map
ABB EQ meter A41 / A42 (Modbus RTU) Modbus register map
Updated 17 November 2026
The A41 and A42 are meters of ABB's EQ A-series. With the RS-485 port set to Modbus they answer function 3/6/16 requests on holding registers whose hex numbers go on the wire as printed. The register layout is the common EQ mapping; quantities a variant does not measure answer with an invalid marker. This map covers energy (total, tariff, per phase, resettable), instantaneous values, I/O, identification, CT/VT settings, resets and the DMTME-compatible block.
This page lists 174 Modbus registers for the ABB EQ meter A41 / A42 (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- EQ meter A41 / A42 (Modbus RTU)
- Equipment type
- Energy meter
- Registers
- 174 (33 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- A41, A42, EQ A41, EQ A42
Integration notes: ABB EQ meter A41 / A42 (Modbus RTU)
Select Modbus for the RS-485 port in the meter's settings menu, then read holding registers with function 3 at the hex addresses as printed (0x5000 for total active import). Multi-register values are high word first; energies are 64-bit with 2 decimals.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20480 | Active import energy | UINT64 ABCD | Total active import energy (0.01 kWh) | Read |
| HR 20484 | Active export energy | UINT64 ABCD | Total active export energy | Read |
| HR 23296 | Voltage L1-N | UINT32 ABCD | Voltage L1-N | Read |
| HR 23308 | Current L1 | UINT32 ABCD | Current L1 | Read |
| HR 23316 | Active power Total | INT32 ABCD | Total active power (signed, 0.01 W) | Read |
| HR 23340 | Frequency | UINT16 | Frequency | Read |
| HR 23354 | Power factor Total | INT16 | Total power factor | Read |
| HR 35072 | Serial number | UINT32 ABCD | Serial number, quick comms check | Read |
Enable Modbus control & writes
In the meter's settings menu open the RS-485 communication page, choose Modbus (instead of EQ-Bus), then set baud rate, address and parity.
Byte order & addressing
- Addresses are hex wire addresses; no 40001 or minus-1 offset.
- Readable range is 0x1000-0x8EFF; reads outside it return exception 2.
- Unsupported quantities return FFFF / 7FFF... instead of an exception.
- Writes to a listed-but-unsupported register are silently ignored; read back to confirm.
Network setup
- Modbus address 1-247.
- Baud 1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200.
- Parity None, Odd or Even.
- Function codes 3, 6 and 16; broadcast works with 6 and 16.
Watch out for
- Modbus runs only on the RS-485 port; the IR side speaks M-Bus or EQ-Bus.
- In transformer-connected meters (A42) the energy registers hold primary values: the CT/VT ratios at 0x8C04-0x8C0A are already applied.
ABB EQ meter A41 / A42 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4098doc 1002 | DMTME phase voltage L1-N | UINT32 | ABCD | V | Read | |||
| HR | 4100doc 1004 | DMTME phase voltage L2-N | UINT32 | ABCD | V | Read | |||
| HR | 4102doc 1006 | DMTME phase voltage L3-N | UINT32 | ABCD | V | Read | |||
| HR | 4104doc 1008 | DMTME line voltage L1-L2 | UINT32 | ABCD | V | Read | |||
| HR | 4106doc 100A | DMTME line voltage L2-L3 | UINT32 | ABCD | V | Read | |||
| HR | 4108doc 100C | DMTME line voltage L1-L3 | UINT32 | ABCD | V | Read | |||
| HR | 4112doc 1010 | DMTME line current L1 | UINT32 | ABCD | mA | Read | |||
| HR | 4114doc 1012 | DMTME line current L2 | UINT32 | ABCD | mA | Read | |||
| HR | 4116doc 1014 | DMTME line current L3 | UINT32 | ABCD | mA | Read | |||
| HR | 4118doc 1016 | DMTME 3-phase system power factor | Published as PF x 1000. | INT32 | ABCD | × 0.001 | Read | ||
| HR | 4120doc 1018 | DMTME power factor L1 | Published as PF x 1000. | INT32 | ABCD | × 0.001 | Read | ||
| HR | 4122doc 101A | DMTME power factor L2 | Published as PF x 1000. | INT32 | ABCD | × 0.001 | Read | ||
| HR | 4124doc 101C | DMTME power factor L3 | Published as PF x 1000. | INT32 | ABCD | × 0.001 | Read | ||
| HR | 4134doc 1026 | DMTME 3-phase apparent power | UINT32 | ABCD | VA | Read | |||
| HR | 4136doc 1028 | DMTME apparent power L1 | UINT32 | ABCD | VA | Read | |||
| HR | 4138doc 102A | DMTME apparent power L2 | UINT32 | ABCD | VA | Read | |||
| HR | 4140doc 102C | DMTME apparent power L3 | UINT32 | ABCD | VA | Read | |||
| HR | 4166doc 1046 | DMTME frequency | UINT32 | ABCD | mHz | Read | |||
| HR | 20480doc 5000 | Active import energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kWh | Read | |
| HR | 20484doc 5004 | Active export energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kWh | Read | |
| HR | 20488doc 5008 | Active net energy | Import minus export, signed. | INT64 | ABCD | × 0.01 | kWh | Read | |
| HR | 20492doc 500C | Reactive import energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kvarh | Read | |
| HR | 20496doc 5010 | Reactive export energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kvarh | Read | |
| HR | 20500doc 5014 | Reactive net energy | Import minus export, signed. | INT64 | ABCD | × 0.01 | kvarh | Read | |
| HR | 20504doc 5018 | Apparent import energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kVAh | Read | |
| HR | 20508doc 501C | Apparent export energy | Meter total, 2 decimals. | UINT64 | ABCD | × 0.01 | kVAh | Read | |
| HR | 20512doc 5020 | Apparent net energy | Import minus export, signed. | INT64 | ABCD | × 0.01 | kVAh | Read | |
| HR | 20516doc 5024 | Active import CO2 | CO2 equivalent of imported active energy. | UINT64 | ABCD | × 0.001 | kg | Read | |
| HR | 20532doc 5034 | Active import currency | Cost equivalent of imported active energy. | UINT64 | ABCD | × 0.001 | currency | Read | |
| HR | 20848doc 5170 | Active import tariff 1 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20852doc 5174 | Active import tariff 2 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20856doc 5178 | Active import tariff 3 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20860doc 517C | Active import tariff 4 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20880doc 5190 | Active export tariff 1 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20884doc 5194 | Active export tariff 2 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20888doc 5198 | Active export tariff 3 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20892doc 519C | Active export tariff 4 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 20912doc 51B0 | Reactive import tariff 1 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20916doc 51B4 | Reactive import tariff 2 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20920doc 51B8 | Reactive import tariff 3 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20924doc 51BC | Reactive import tariff 4 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20944doc 51D0 | Reactive export tariff 1 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20948doc 51D4 | Reactive export tariff 2 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20952doc 51D8 | Reactive export tariff 3 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 20956doc 51DC | Reactive export tariff 4 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21600doc 5460 | Active import energy L1 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21604doc 5464 | Active import energy L2 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21608doc 5468 | Active import energy L3 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21612doc 546C | Active export energy L1 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21616doc 5470 | Active export energy L2 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21620doc 5474 | Active export energy L3 | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21624doc 5478 | Active net energy L1 | INT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21628doc 547C | Active net energy L2 | INT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21632doc 5480 | Active net energy L3 | INT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21636doc 5484 | Reactive import energy L1 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21640doc 5488 | Reactive import energy L2 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21644doc 548C | Reactive import energy L3 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21648doc 5490 | Reactive export energy L1 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21652doc 5494 | Reactive export energy L2 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21656doc 5498 | Reactive export energy L3 | UINT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21660doc 549C | Reactive net energy L1 | INT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21664doc 54A0 | Reactive net energy L2 | INT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21668doc 54A4 | Reactive net energy L3 | INT64 | ABCD | × 0.01 | kvarh | Read | ||
| HR | 21672doc 54A8 | Apparent import energy L1 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21676doc 54AC | Apparent import energy L2 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21680doc 54B0 | Apparent import energy L3 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21684doc 54B4 | Apparent export energy L1 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21688doc 54B8 | Apparent export energy L2 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21692doc 54BC | Apparent export energy L3 | UINT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21696doc 54C0 | Apparent net energy L1 | INT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21700doc 54C4 | Apparent net energy L2 | INT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21704doc 54C8 | Apparent net energy L3 | INT64 | ABCD | × 0.01 | kVAh | Read | ||
| HR | 21804doc 552C | Resettable active import | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 21808doc 5530 | Resettable active export | UINT64 | ABCD | × 0.01 | kWh | Read | ||
| HR | 23296doc 5B00 | Voltage L1-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23298doc 5B02 | Voltage L2-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23300doc 5B04 | Voltage L3-N | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23302doc 5B06 | Voltage L1-L2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23304doc 5B08 | Voltage L3-L2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23306doc 5B0A | Voltage L1-L3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 23308doc 5B0C | Current L1 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 23310doc 5B0E | Current L2 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 23312doc 5B10 | Current L3 | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 23314doc 5B12 | Current N | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 23316doc 5B14 | Active power Total | Signed, 2 decimals; tops out near 21 MW. | INT32 | ABCD | × 0.01 | W | Read | |
| HR | 23318doc 5B16 | Active power L1 | INT32 | ABCD | × 0.01 | W | Read | ||
| HR | 23320doc 5B18 | Active power L2 | INT32 | ABCD | × 0.01 | W | Read | ||
| HR | 23322doc 5B1A | Active power L3 | INT32 | ABCD | × 0.01 | W | Read | ||
| HR | 23324doc 5B1C | Reactive power Total | Signed, 2 decimals; tops out near 21 MW. | INT32 | ABCD | × 0.01 | var | Read | |
| HR | 23326doc 5B1E | Reactive power L1 | INT32 | ABCD | × 0.01 | var | Read | ||
| HR | 23328doc 5B20 | Reactive power L2 | INT32 | ABCD | × 0.01 | var | Read | ||
| HR | 23330doc 5B22 | Reactive power L3 | INT32 | ABCD | × 0.01 | var | Read | ||
| HR | 23332doc 5B24 | Apparent power Total | Signed, 2 decimals; tops out near 21 MW. | INT32 | ABCD | × 0.01 | VA | Read | |
| HR | 23334doc 5B26 | Apparent power L1 | INT32 | ABCD | × 0.01 | VA | Read | ||
| HR | 23336doc 5B28 | Apparent power L2 | INT32 | ABCD | × 0.01 | VA | Read | ||
| HR | 23338doc 5B2A | Apparent power L3 | INT32 | ABCD | × 0.01 | VA | Read | ||
| HR | 23340doc 5B2C | Frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 23341doc 5B2D | Phase angle power Total | Range -180 to +180. | INT16 | × 0.1 | ° | Read | ||
| HR | 23342doc 5B2E | Phase angle power L1 | Range -180 to +180. | INT16 | × 0.1 | ° | Read | ||
| HR | 23343doc 5B2F | Phase angle power L2 | Range -180 to +180. | INT16 | × 0.1 | ° | Read | ||
| HR | 23344doc 5B30 | Phase angle power L3 | Range -180 to +180. | INT16 | × 0.1 | ° | Read | ||
| HR | 23345doc 5B31 | Phase angle voltage L1 | INT16 | × 0.1 | ° | Read | |||
| HR | 23346doc 5B32 | Phase angle voltage L2 | INT16 | × 0.1 | ° | Read | |||
| HR | 23347doc 5B33 | Phase angle voltage L3 | INT16 | × 0.1 | ° | Read | |||
| HR | 23351doc 5B37 | Phase angle current L1 | INT16 | × 0.1 | ° | Read | |||
| HR | 23352doc 5B38 | Phase angle current L2 | INT16 | × 0.1 | ° | Read | |||
| HR | 23353doc 5B39 | Phase angle current L3 | INT16 | × 0.1 | ° | Read | |||
| HR | 23354doc 5B3A | Power factor Total | Range -1.000 to +1.000. | INT16 | × 0.001 | Read | |||
| HR | 23355doc 5B3B | Power factor L1 | Range -1.000 to +1.000. | INT16 | × 0.001 | Read | |||
| HR | 23356doc 5B3C | Power factor L2 | Range -1.000 to +1.000. | INT16 | × 0.001 | Read | |||
| HR | 23357doc 5B3D | Power factor L3 | Range -1.000 to +1.000. | INT16 | × 0.001 | Read | |||
| HR | 23358doc 5B3E | Current quadrant Total | UINT16 | Read | 1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4 | ||||
| HR | 23359doc 5B3F | Current quadrant L1 | UINT16 | Read | 1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4 | ||||
| HR | 23360doc 5B40 | Current quadrant L2 | UINT16 | Read | 1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4 | ||||
| HR | 23361doc 5B41 | Current quadrant L3 | UINT16 | Read | 1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4 | ||||
| HR | 25344doc 6300 | Output 1 | Exists only on articles with that output. | UINT16 | Read/write | 0 = OFF; 1 = ON | |||
| HR | 25345doc 6301 | Output 2 | Exists only on articles with that output. | UINT16 | Read/write | 0 = OFF; 1 = ON | |||
| HR | 25346doc 6302 | Output 3 | Exists only on articles with that output. | UINT16 | Read/write | 0 = OFF; 1 = ON | |||
| HR | 25347doc 6303 | Output 4 | Exists only on articles with that output. | UINT16 | Read/write | 0 = OFF; 1 = ON | |||
| HR | 25352doc 6308 | Input 1 current state | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 25353doc 6309 | Input 2 current state | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 25354doc 630A | Input 3 current state | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 25355doc 630B | Input 4 current state | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 25360doc 6310 | Input 1 stored state | Latched state; clear with the reset register. | UINT16 | Read | 0 = OFF; 1 = ON | |||
| HR | 25361doc 6311 | Input 2 stored state | Latched state; clear with the reset register. | UINT16 | Read | 0 = OFF; 1 = ON | |||
| HR | 25362doc 6312 | Input 3 stored state | Latched state; clear with the reset register. | UINT16 | Read | 0 = OFF; 1 = ON | |||
| HR | 25363doc 6313 | Input 4 stored state | Latched state; clear with the reset register. | UINT16 | Read | 0 = OFF; 1 = ON | |||
| HR | 25368doc 6318 | Input 1 pulse counter | UINT64 | ABCD | Read | ||||
| HR | 25372doc 631C | Input 2 pulse counter | UINT64 | ABCD | Read | ||||
| HR | 25376doc 6320 | Input 3 pulse counter | UINT64 | ABCD | Read | ||||
| HR | 25380doc 6324 | Input 4 pulse counter | UINT64 | ABCD | Read | ||||
| HR | 35072doc 8900 | Serial number | UINT32 | ABCD | Read | ||||
| HR | 35080doc 8908 | Meter firmware version | ASCII, three numbers with dots (e.g. 1.0.0); unused bytes 0. | STRING[16] | Read | ||||
| HR | 35088doc 8910 | Modbus mapping version | High byte = major, low byte = minor. | UINT16 | Read | ||||
| HR | 35168doc 8960 | Type designation | ASCII, 12 characters including the null terminator. | STRING[12] | Read | ||||
| HR | 35331doc 8A03 | Day of week | 1-7, Monday = 1. | UINT16 | Read | ||||
| HR | 35332doc 8A04 | DST active | UINT16 | Read | 0 = DST inactive; 1 = DST active | ||||
| HR | 35333doc 8A05 | Day type | 0-15 = day type 1-16. | UINT16 | Read | ||||
| HR | 35334doc 8A06 | Season | 0-3 = season 1-4. | UINT16 | Read | ||||
| HR | 35335doc 8A07 | Current tariff | Active tariff, 1 to 4. | UINT16 | Read/write | ||||
| HR | 35375doc 8A2F | Power fail counter | UINT16 | Read | |||||
| HR | 35400doc 8A48 | Reset count, resettable active energy import | How many times that resettable register was cleared. | UINT64 | ABCD | Read | |||
| HR | 35404doc 8A4C | Reset count, resettable active energy export | How many times that resettable register was cleared. | UINT64 | ABCD | Read | |||
| HR | 35408doc 8A50 | Reset count, resettable reactive energy import | How many times that resettable register was cleared. | UINT64 | ABCD | Read | |||
| HR | 35412doc 8A54 | Reset count, resettable reactive energy export | How many times that resettable register was cleared. | UINT64 | ABCD | Read | |||
| HR | 35844doc 8C04 | CT ratio primary current | UINT32 | ABCD | Read/write | ||||
| HR | 35846doc 8C06 | VT ratio primary voltage | UINT32 | ABCD | Read/write | ||||
| HR | 35848doc 8C08 | CT ratio secondary current | UINT32 | ABCD | Read/write | ||||
| HR | 35850doc 8C0A | VT ratio secondary voltage | UINT32 | ABCD | Read/write | ||||
| HR | 36064doc 8CE0 | CO2 conversion factor | UINT32 | ABCD | × 0.001 | kg/kWh | Read/write | ||
| HR | 36066doc 8CE2 | Currency conversion factor | UINT32 | ABCD | × 0.01 | Currency/kWh | Read/write | ||
| HR | 36068doc 8CE4 | LED source | UINT16 | Read/write | 0 = Active energy; 1 = Reactive energy | ||||
| HR | 36069doc 8CE5 | Number of elements | Measuring elements, 1-3. Read only. | UINT16 | Read | ||||
| HR | 36074doc 8CEA | DST enabled | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 36608doc 8F00 | Reset power fail counter | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36613doc 8F05 | Reset power outage time | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36619doc 8F0B | Reset input 1 counter | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36620doc 8F0C | Reset input 2 counter | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36621doc 8F0D | Reset input 3 counter | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36622doc 8F0E | Reset input 4 counter | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36627doc 8F13 | Reset input 1 stored state | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36628doc 8F14 | Reset input 2 stored state | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36629doc 8F15 | Reset input 3 stored state | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36630doc 8F16 | Reset input 4 stored state | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36635doc 8F1B | Reset resettable active import | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36636doc 8F1C | Reset resettable active export | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36637doc 8F1D | Reset resettable reactive import | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36638doc 8F1E | Reset resettable reactive export | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36639doc 8F1F | Reset previous values | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36640doc 8F20 | Reset demand | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36657doc 8F31 | Reset system log | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36658doc 8F32 | Reset event log | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36659doc 8F33 | Reset net quality log | Write 1 to perform it. | UINT16 | Write | ||||
| HR | 36720doc 8F70 | Freeze demand | Write 1 to freeze the demand values. | UINT16 | Write |
Notes on this map
- Addresses are hex wire addresses. All data is in holding registers: read with function 3 (up to 125 registers), write with 6 or 16.
- Multi-register values put the most significant byte in the high byte of the lowest register, so 32-bit and 64-bit values are ABCD.
- Quantities a given article does not measure still answer, filled with FFFF (unsigned) or the largest positive value (signed).
- Left out: resettable reactive import/export (5534, 5538 hex). The manual prints kWh as their unit, so the unit cannot be taken from the table as printed.
- Instantaneous power registers are signed 32-bit with 2 decimals (about +/-21 MW maximum); the manual points to the DMTME block for larger systems, but its power rows are left out here (see below).
- Left out: date/time and power-outage time (packed byte fields), the 64-bit error/information/warning/alarm flag strings, harmonics arrays, load-profile resets, DST start/end packed fields, the DMTME energy rows printed as 'Wh*100' / 'VArh*100', the DMTME CT/VT ratio rows, and the selector-based log and load-profile readout.
- I/O registers exist only on articles with matching inputs/outputs. Per-phase registers for phases a variant does not have return the invalid marker.
- Left out: the DMTME-block active and reactive power rows (102E-103C hex). This manual prints them Unsigned while the A43/A44 manual prints the same rows Signed, so their type is uncertain. Use 5B14-5B22 for signed power.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB EQ meter A41 / A42 (Modbus RTU)
What Modbus registers does the ABB EQ meter A41 / A42 (Modbus RTU) have?
This map lists 174 registers: 174 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB EQ meter A41 / A42 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every start register is printed in hex exactly as sent on the bus; the manual says not to subtract 40000 or 1. 5000 hex = 20480 decimal. The example request frame reads 0x5000 with function 3.
What byte order does the ABB EQ meter A41 / A42 (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB EQ meter A41 / A42 (Modbus RTU)?
Start with HR 20480 Active import energy (Total active import energy (0.01 kWh)); HR 20484 Active export energy (Total active export energy); HR 23296 Voltage L1-N (Voltage L1-N); HR 23308 Current L1 (Current L1); HR 23316 Active power Total (Total active power (signed, 0.01 W)); HR 23340 Frequency (Frequency); HR 23354 Power factor Total (Total power factor); HR 35072 Serial number (Serial number, quick comms check).
How do I enable Modbus control of the ABB EQ meter A41 / A42 (Modbus RTU)?
In the meter's settings menu open the RS-485 communication page, choose Modbus (instead of EQ-Bus), then set baud rate, address and parity.
Where is the official ABB EQ meter A41 / A42 (Modbus RTU) Modbus documentation?
The source is A41/A42 User Manual (2CMC484002M0201 Revision D), revision 2025-11-07, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=2CMC484002M0201&LanguageCode=en&DocumentPartId=&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other power & energy meters register maps
- Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Energy meter (heat / cooling meter)
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Modbus RTU plug-in communication module (Sylop M/N 11024, firmware 1.0) in a Diehl SHARKY 775 compact heat meter or SCYLAR INT 8 calculator.
Also known as: SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI
All power & energy meters Modbus register maps →
Source: A41/A42 User Manual · 2CMC484002M0201 Revision D · rev. 2025-11-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.