- SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
Power meter (DC circuit breaker trip unit) · Modbus register map
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) Modbus register map
Updated 19 November 2026
The PR122DC and PR123DC are the DC versions of ABB's Emax trip units. With the PR120/D-M module they talk Modbus RTU: pole currents, DC voltage, power and energy are input registers, and commands such as open, close and trip reset are written to two holding registers. 32-bit values are sent low word first.
This page lists 18 Modbus registers for the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
- Equipment type
- Power meter (DC circuit breaker trip unit)
- Registers
- 18 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- SW 3.01 and later
- Also known as
- PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC
Integration notes: ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
Read input registers 200-225 for currents, voltage, power and energy, and 101/107 for breaker state and trips. Open, close or reset with a function-16 write of command type and parameter to registers 0-1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 101 | State 2 - flags | BITMAP16 | CB open/closed, tripped, remote | Read |
| IR 107 | State 8 - latched trips | BITMAP16 | Which protection tripped | Read |
| IR 203 | IA current | UINT32 CDAB | Pole A current | Read |
| IR 217 | DC voltage | UINT16 | DC voltage | Read |
| IR 218 | Total active power | INT32 CDAB | Total active power | Read |
| HR 0 | Command type | UINT16 | Commands | Write |
Enable Modbus control & writes
Fit the PR120/D-M module and set the external bus address, baud and protocol on the trip unit. Remote mode (state 2 bit 9) is needed for open/close commands.
Byte order & addressing
- 32-bit values are low word first.
- Measures are input registers (function 4).
- Commands always need function 16 with both registers.
Network setup
- Set the external-bus address (1-247), baud (9600/19200), addressing type and frame format (E,8,1 / O,8,1 / N,8,2 / N,8,1) on the trip unit.
Watch out for
- Slave ID register 700 tells PR122DC (0x59) from PR123DC (0x58).
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 101doc 30102 (rel. 101) | State 2 - flags | Breaker position and remote/local. | BITMAP16 | Read | bit 0 = Any alarm / timing / warning; bit 1 = Any trip (latched); bit 2 = CB tripped; bit 3 = CB connected (0 = isolated); bit 4 = CB closed (0 = open); bit 5 = CB undefined; bit 6 = No communication on local bus; bit 7 = Springs charged; bit 8 = Trip command fail; bit 9 = Remote mode (0 = local); bit 10 = Programming OK; bit 11 = Programming failed; bit 12 = Internal bus programming session; bit 13 = Test bus programming session; bit 14 = Local bus programming session; bit 15 = System bus programming session | |||
| IR | 107doc 30108 (rel. 107) | State 8 - latched trips | Cleared by CB reset or trip reset. | BITMAP16 | Read | bit 0 = L tripped; bit 1 = S tripped; bit 2 = S2 tripped; bit 3 = I tripped (or MCR); bit 4 = Iinst tripped; bit 5 = G tripped; bit 7 = OT tripped; bit 9 = U tripped; bit 10 = UV tripped; bit 11 = OV tripped; bit 13 = RP tripped | |||
| IR | 200doc 30201-30202 (rel. 200) | Maximum current | 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 202doc 30203 (rel. 202) | Maximum current polarity | UINT16 | Read | 0 = Not available; 1 = IA; 2 = IA_2; 3 = IB; 4 = IB_2 | ||||
| IR | 203doc 30204-30205 (rel. 203) | IA current | 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 205doc 30206-30207 (rel. 205) | IA_2 current | 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 207doc 30208-30209 (rel. 207) | IB current | PR123DC. 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 209doc 30210-30211 (rel. 209) | IB_2 current | PR123DC. 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 211doc 30212-30213 (rel. 211) | Ground current | PR123DC. 2^32-1 = not available. | UINT32 | CDAB | A | Read | ||
| IR | 217doc 30218 (rel. 217) | DC voltage | PR123DC; 65535 = not available. | UINT16 | × 0.1 | V | Read | ||
| IR | 218doc 30219-30220 (rel. 218) | Total active power | PR123DC; 2^31-1 = not available. | INT32 | CDAB | × 0.1 | kW | Read | |
| IR | 220doc 30221-30222 (rel. 220) | Positive active energy | PR123DC. | INT32 | CDAB | kWh | Read | ||
| IR | 222doc 30223-30224 (rel. 222) | Negative active energy | PR123DC. | INT32 | CDAB | kWh | Read | ||
| IR | 224doc 30225-30226 (rel. 224) | Total active energy | PR123DC. | INT32 | CDAB | kWh | Read | ||
| IR | 700doc 30701 (rel. 700) | Slave ID | Identifies the trip unit model. | UINT16 | Read | 88 = PR123DC (0x58); 89 = PR122DC (0x59) | |||
| IR | 704doc 30705 (rel. 704) | Rated current In | 100-6300 A. | UINT16 | A | Read | |||
| HR | 0doc 40001 (rel. 0) | Command type | Write with the parameter in one function-16 request. | UINT16 | Write | 0 = Dummy; 1 = Trip reset; 2 = Signalling reset; 3 = Communication statistics reset; 4 = Log event reset; 5 = Start programming session; 6 = Abort programming session; 7 = Stop programming session; 8 = CB open; 9 = CB close; 10 = CB reset; 11 = Wink toggle; 12 = History measure reset; 13 = History energy reset; 14 = Datalogger trigger restart; 15 = Datalogger stop | |||
| HR | 1doc 40002 (rel. 1) | Command parameter | 0 when the command needs none. | UINT16 | Write |
Notes on this map
- The document states 4-byte values are sent with the low word at the lower address (LOW-HIGH), bytes within a word high first, so 32-bit registers are CDAB.
- External bus settings: 9600 or 19200 baud, address 1-247, Standard or ABB addressing, E,8,1 / O,8,1 / N,8,2 / N,8,1. The document does not state the external-bus factory values.
- IB, IB_2, ground current, voltage, power and energy are PR123DC only.
- Left out: state words other than 2 and 8, statistics, history, logger and parameter areas.
- Over the external bus, commands are accepted only in Remote mode (state 2 bit 9).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
What Modbus registers does the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) have?
This map lists 18 registers: 16 input registers, 2 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map gives relative addresses on 30001 (input registers, function 4) and 40001 (holding registers) bases; its example says run-time measures at offset 200 are 30201, relative address 200, which is the wire address with 'Standard' addressing.
What byte order does the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)?
Start with IR 101 State 2 - flags (CB open/closed, tripped, remote); IR 107 State 8 - latched trips (Which protection tripped); IR 203 IA current (Pole A current); IR 217 DC voltage (DC voltage); IR 218 Total active power (Total active power); HR 0 Command type (Commands).
How do I enable Modbus control of the ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)?
Fit the PR120/D-M module and set the external bus address, baud and protocol on the trip unit. Remote mode (state 2 bit 9) is needed for open/close commands.
Where is the official ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU) Modbus documentation?
The source is Communication System Interface for protection trip units PR122DC and PR123DC + PR120/D-M Com module (1SDH000841R0001 rev 02), revision 2014-04-04, published free by ABB at https://library.e.abb.com/public/14a57dd39209c59dc12578b100664838/1SDH000841R0001.pdf.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other power & energy meters register maps
- Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4 - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter
Crompton Instruments Integra 1530 / 1560 / 1580
Crompton Instruments (Tyco Electronics) Integra 1530, 1560 and 1580 panel meters fitted with the RS485 Modbus RTU option, per Integra Comms Issue 1 (Jan 2006).
Also known as: Integra 1530, Integra 1560, Integra 1580 - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI
All power & energy meters Modbus register maps →
Source: Communication System Interface for protection trip units PR122DC and PR123DC + PR120/D-M Com module · 1SDH000841R0001 rev 02 · rev. 2014-04-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.