Variable frequency drive · Modbus register map

ABB ACH550-UH HVAC drive (embedded Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

ABB's ACH550-UH HVAC drive has an RS-485 port that can run Modbus RTU (or N2, FLN, BACnet). Control bits and relay outputs are coils, status bits and digital inputs are discrete inputs, and all parameters plus the control/status words and references are 16-bit holding registers, with parameter NNNN at register 4NNNN. This map covers the control block, main operating data, fault and alarm words, fault history and the EFB set-up parameters.

This page lists 82 Modbus registers for the ABB ACH550-UH HVAC drive (embedded Modbus RTU) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
ACH550-UH HVAC drive (embedded Modbus RTU)
Equipment type
Variable frequency drive
Registers
82 (19 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
ACH550-UH, ACH550
Source document
ACH550-UH HVAC Drives User's Manual · 3AUA0000081823 Rev F
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB ACH550-UH HVAC drive (embedded Modbus RTU)

Integration in brief

Set 9802 = 1 (STD MODBUS), set 5302 and the line settings, then 5305 = 2 (ABB DRV FULL) and point 1001/1102/1103 at COMM. Write the control word and REF1 at 40001/40002, poll the status word 40004 and output frequency/current at 40103/40104.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Control word (ABB Drives)BITMAP16Control word: start/stop/resetRead/write
HR 1Reference 1INT16Reference 1 (20000 = 1105 REF1 MAX)Read/write
HR 3Status word (ABB Drives)BITMAP16Status wordRead
HR 1020103 Output freqUINT160103 Output frequency, 0.1 HzRead
HR 1030104 CurrentUINT160104 Current, 0.1 ARead
HR 1050106 PowerINT160106 Power, 0.1 kWRead
HR 4000401 Last faultUINT160401 Last faultRead
HR 3040305 Fault word 1BITMAP160305 Fault word 1Read

Enable Modbus control & writes

Set 9802 COMM PROT SEL = 1 (STD MODBUS); this loads Modbus defaults into group 53. Set 5302 station ID (a new address applies after a power cycle, or after setting 5302 to 0 and then the new value), 5303 baud and 5304 parity. For control set 1001 EXT1 COMMANDS = COMM, 1102 EXT1/EXT2 SEL and 1103 REF1 SELECT = COMM, and optionally 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Parameter writes are volatile until 1607 PARAM. SAVE = 1.

Communication loss & watchdog

3018 COMM FAULT FUNC (NOT SEL default / FAULT 28 SERIAL 1 ERR / CONST SP 7 / LAST SPEED with alarm 2005 I/O COMM) after 3019 COMM FAULT TIME (default 10.0 s).

Byte order & addressing

Network setup

Watch out for

ABB ACH550-UH HVAC drive (embedded Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

82 of 82 shown
ABB ACH550-UH HVAC drive (embedded Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO32doc 00033Relay output 1Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
CO33doc 00034Relay output 2Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
CO34doc 00035Relay output 3Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
CO35doc 00036Relay output 4Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
CO36doc 00037Relay output 5Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
CO37doc 00038Relay output 6Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.BITRead/write
DI0doc 10001Status bit 0: RDY_ONABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI1doc 10002Status bit 1: RDY_RUNABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI2doc 10003Status bit 2: RDY_REFABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI3doc 10004Status bit 3: TRIPPEDABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI4doc 10005Status bit 4: OFF_2_STA (active low)ABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI5doc 10006Status bit 5: OFF_3_STA (active low)ABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI6doc 10007Status bit 6: SWC_ON_INHIBABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI7doc 10008Status bit 7: ALARMABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI8doc 10009Status bit 8: AT_SETPOINTABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI9doc 10010Status bit 9: REMOTEABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI10doc 10011Status bit 10: ABOVE_LIMITABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI11doc 10012Status bit 11: EXT2ABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI12doc 10013Status bit 12: RUN_ENABLEABB Drives profile (5305 = 0 or 2) meaning.BITRead
DI32doc 10033DI1Digital input state.BITRead
DI33doc 10034DI2Digital input state.BITRead
DI34doc 10035DI3Digital input state.BITRead
DI35doc 10036DI4Digital input state.BITRead
DI36doc 10037DI5Digital input state.BITRead
DI37doc 10038DI6Digital input state.BITRead
HR0doc 40001Control word (ABB Drives)Only with 5305 = 0 or 2; copy in 5319.BITMAP16Read/writebit 0 = OFF1 CONTROL: 1 = ready to operate, 0 = ramp stop; bit 1 = OFF2 CONTROL: 0 = emergency off, coast to stop; bit 2 = OFF3 CONTROL: 0 = emergency stop (2208); bit 3 = INHIBIT OPERATION: 1 = operation enabled (needs run enable, 1601); bit 4 = RAMP_OUT_ZERO (ABB DRV FULL only): 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 0 = halt ramping; bit 6 = RAMP_IN_ZERO: 0 = force ramp input to zero; bit 7 = RESET: 0->1 = fault reset (1604 = COMM); bit 8 = Unused; bit 9 = Unused; bit 10 = REMOTE_CMD (ABB DRV FULL only): 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = EXT2, 0 = EXT1 (1102 = COMM); bit 12 = Unused; bit 13 = Unused; bit 14 = Unused; bit 15 = Unused
HR1doc 40002Reference 10...+/-20000 = 0...1105 REF1 MAX.INT16Read/write
HR2doc 40003Reference 20...+/-10000 = 0...1108 REF2 MAX.INT16Read/write
HR3doc 40004Status word (ABB Drives)Only with 5305 = 0 or 2; copy in 5320.BITMAP16Readbit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate; bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibit active; bit 7 = ALARM; bit 8 = AT_SETPOINT: actual equals reference; bit 9 = REMOTE: 1 = EXT1/EXT2, 0 = local; bit 10 = ABOVE_LIMIT: supervised value above limit (group 32); bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE received; bit 13 = Unused; bit 14 = Unused; bit 15 = Unused
HR4doc 40005Actual 1Default copy of 0103 output frequency (5310); 0.1 Hz with the default.INT16Read
HR5doc 40006Actual 2Default copy of 0104 current (5311); 0.1 A with the default.INT16Read
HR30doc 40031DCU control word LSWOnly with 5305 = 1 (see 0301).BITMAP16Read/write
HR31doc 40032DCU control word MSWOnly with 5305 = 1 (see 0302).BITMAP16Read
HR32doc 40033DCU status word LSWOnly with 5305 = 1 (see 0303).BITMAP16Read
HR33doc 40034DCU status word MSWOnly with 5305 = 1 (see 0304).BITMAP16Read
HR100doc 401010101 Speed & dirSigned motor speed; negative = reverse.INT16rpmRead
HR101doc 401020102 SpeedUINT16rpmRead
HR102doc 401030103 Output freqUINT16× 0.1HzRead
HR103doc 401040104 CurrentMeasured motor current.UINT16× 0.1ARead
HR104doc 401050105 TorquePercent of nominal motor torque.INT16× 0.1%Read
HR105doc 401060106 PowerMeasured motor power.INT16× 0.1kWRead
HR106doc 401070107 DC bus voltageUINT16VRead
HR108doc 401090109 Output voltageUINT16VRead
HR109doc 401100110 Drive tempPower transistor temperature.INT16× 0.1°CRead
HR111doc 401120112 External ref 2INT16× 0.1%Read
HR112doc 401130113 Ctrl locationUINT16Read0 = LOCAL; 1 = EXT1; 2 = EXT2
HR113doc 401140114 Run time (R)Resettable run hours.UINT16hRead
HR114doc 401150115 kWh counter (R)Rolls over at 65535; resettable.UINT16kWhRead
HR119doc 401200120 AI 1UINT16× 0.1%Read
HR120doc 401210121 AI 2UINT16× 0.1%Read
HR123doc 401240124 AO 1UINT16× 0.1mARead
HR139doc 401400140 Run timeThousands of hours.UINT16× 0.01khRead
HR140doc 401410141 MWh counterUINT16MWhRead
HR142doc 401430143 Drive on time hiPower-on days.UINT16daysRead
HR143doc 401440144 Drive on time lo2 s ticks within the day.UINT16× 2sRead
HR152doc 401530153 Mot therm stressMotor thermal load.UINT16× 0.1%Read
HR304doc 403050305 Fault word 1BITMAP16Readbit 0 = OVERCURRENT; bit 1 = DC OVERVOLT; bit 2 = DEV OVERTEMP; bit 3 = SHORT CIRC; bit 4 = Reserved; bit 5 = DC UNDERVOLT; bit 6 = AI1 LOSS; bit 7 = AI2 LOSS; bit 8 = MOT OVERTEMP; bit 9 = PANEL LOSS; bit 10 = ID RUN FAIL; bit 11 = MOTOR STALL; bit 12 = CB OVERTEMP; bit 13 = EXT FAULT 1; bit 14 = EXT FAULT 2; bit 15 = EARTH FAULT
HR305doc 403060306 Fault word 2BITMAP16Readbit 0 = Obsolete; bit 1 = THERM FAIL; bit 2 = OPEX LINK; bit 3 = OPEX PWR; bit 4 = CURR MEAS; bit 5 = SUPPLY PHASE; bit 6 = ENCODER ERR; bit 7 = OVERSPEED; bit 8 = Reserved; bit 9 = DRIVE ID; bit 10 = CONFIG FILE; bit 11 = SERIAL 1 ERR; bit 12 = EFB CON FILE; bit 13 = FORCE TRIP; bit 14 = MOTOR PHASE; bit 15 = OUTP WIRING
HR306doc 403070307 Fault word 3BITMAP16Readbit 0 = EFB 1; bit 1 = EFB 2; bit 2 = EFB 3; bit 3 = INCOMPATIBLE SW; bit 4 = USER LOAD CURVE; bit 5 = Reserved; bit 6 = Reserved; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = System error; bit 11 = System error; bit 12 = System error; bit 13 = System error; bit 14 = System error; bit 15 = Param. setting fault
HR307doc 403080308 Alarm word 1Write 0 to clear.BITMAP16Readbit 0 = OVERCURRENT; bit 1 = OVERVOLTAGE; bit 2 = UNDERVOLTAGE; bit 3 = DIR LOCK; bit 4 = IO COMM; bit 5 = AI1 LOSS; bit 6 = AI2 LOSS; bit 7 = PANEL LOSS; bit 8 = DEVICE OVERTEMP; bit 9 = MOTOR TEMP; bit 10 = Reserved; bit 11 = MOTOR STALL; bit 12 = AUTORESET; bit 13 = AUTOCHANGE; bit 14 = PFA I LOCK; bit 15 = Reserved
HR308doc 403090309 Alarm word 2Write 0 to clear.BITMAP16Readbit 0 = Reserved; bit 1 = PID SLEEP; bit 2 = ID RUN; bit 3 = Reserved; bit 4 = START ENABLE 1 MISSING; bit 5 = START ENABLE 2 MISSING; bit 6 = EMERGENCY STOP; bit 7 = ENCODER ERROR; bit 8 = FIRST START; bit 9 = Reserved; bit 10 = USER LOAD CURVE; bit 11 = START DELAY; bit 12 = Reserved; bit 13 = Reserved; bit 14 = Reserved; bit 15 = Reserved
HR400doc 404010401 Last faultLatest fault code; 0 = history clear.UINT16Read
HR403doc 404040404 Speed at fltINT16rpmRead
HR404doc 404050405 Freq at fltINT16× 0.1HzRead
HR405doc 404060406 Voltage at fltDC bus voltage at the fault.UINT16× 0.1VRead
HR406doc 404070407 Current at fltUINT16× 0.1ARead
HR407doc 404080408 Torque at fltINT16× 0.1%Read
HR411doc 404120412 Previous fault 1UINT16Read
HR412doc 404130413 Previous fault 2UINT16Read
HR1606doc 416071607 Param. saveWrite 1 to save parameters permanently.UINT16Read/write0 = DONE; 1 = SAVE
HR3017doc 430183018 Comm fault funcReaction to fieldbus loss.UINT16Read/write0 = NOT SEL; 1 = FAULT; 2 = CONST SP 7; 3 = LAST SPEED
HR3018doc 430193019 Comm fault time0.0-600.0 s, default 10.0 s.UINT16× 0.1sRead/write
HR5301doc 453025302 EFB station IDDefault 1 for Modbus.UINT16Read/write
HR5303doc 453045304 EFB parityUINT16Read/write0 = 8 NONE 1; 1 = 8 NONE 2; 2 = 8 EVEN 1; 3 = 8 ODD 1
HR5304doc 453055305 EFB ctrl profileUINT16Read/write0 = ABB DRV LIM; 1 = DCU PROFILE; 2 = ABB DRV FULL
HR5305doc 453065306 EFB OK messagesUINT16Read
HR5306doc 453075307 EFB CRC errorsUINT16Read
HR5307doc 453085308 EFB UART errorsUINT16Read
HR5308doc 453095309 EFB statusUINT16Read0 = IDLE; 1 = EXECUT INIT; 2 = TIME OUT; 3 = CONFIG ERROR; 4 = OFF-LINE; 5 = ON-LINE; 6 = RESET; 7 = LISTEN ONLY
HR5309doc 453105310 EFB par 10Parameter mapped to 40005.UINT16Read/write
HR5310doc 453115311 EFB par 11Parameter mapped to 40006.UINT16Read/write
HR9801doc 498029802 Comm prot selUINT16Read/write0 = NOT SEL; 1 = STD MODBUS; 2 = N2; 3 = FLN; 4 = Fieldbus adapter (slot 2); 5 = BACNET

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB ACH550-UH HVAC drive (embedded Modbus RTU)

What Modbus registers does the ABB ACH550-UH HVAC drive (embedded Modbus RTU) have?

This map lists 82 registers: 6 coils, 19 discrete inputs, 57 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB ACH550-UH HVAC drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states the drive uses zero-based Modbus addressing: holding register 40002 is sent as 0001 and coil 33 as 0032. So 40001 = wire 0, parameter NNNN = register 4NNNN = wire NNNN - 1 (e.g. 0103 -> 40103 -> 102); coils 00001-00016 are control-word bits, 00033+ relay outputs; discrete inputs 10001-10032 are status-word bits and 10033+ digital inputs; input registers 30001/30002 are AI1/AI2.

What are the minimum Modbus registers to integrate the ABB ACH550-UH HVAC drive (embedded Modbus RTU)?

Start with HR 0 Control word (ABB Drives) (Control word: start/stop/reset); HR 1 Reference 1 (Reference 1 (20000 = 1105 REF1 MAX)); HR 3 Status word (ABB Drives) (Status word); HR 102 0103 Output freq (0103 Output frequency, 0.1 Hz); HR 103 0104 Current (0104 Current, 0.1 A); HR 105 0106 Power (0106 Power, 0.1 kW); HR 400 0401 Last fault (0401 Last fault); HR 304 0305 Fault word 1 (0305 Fault word 1).

How do I enable Modbus control of the ABB ACH550-UH HVAC drive (embedded Modbus RTU)?

Set 9802 COMM PROT SEL = 1 (STD MODBUS); this loads Modbus defaults into group 53. Set 5302 station ID (a new address applies after a power cycle, or after setting 5302 to 0 and then the new value), 5303 baud and 5304 parity. For control set 1001 EXT1 COMMANDS = COMM, 1102 EXT1/EXT2 SEL and 1103 REF1 SELECT = COMM, and optionally 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Parameter writes are volatile until 1607 PARAM. SAVE = 1.

What happens when the ABB ACH550-UH HVAC drive (embedded Modbus RTU) loses Modbus communication?

3018 COMM FAULT FUNC (NOT SEL default / FAULT 28 SERIAL 1 ERR / CONST SP 7 / LAST SPEED with alarm 2005 I/O COMM) after 3019 COMM FAULT TIME (default 10.0 s).

Where is the official ABB ACH550-UH HVAC drive (embedded Modbus RTU) Modbus documentation?

The source is ACH550-UH HVAC Drives User's Manual (3AUA0000081823 Rev F), published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AUA0000081823&LanguageCode=en&DocumentPartId=&Action=Launch.

More ABB Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: ACH550-UH HVAC Drives User's Manual · 3AUA0000081823 Rev F. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.