Energy meter · Modbus register map

ABB EQ meter A43 / A44 (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The A43 and A44 are the top-line three-phase DIN-rail meters of ABB's EQ family. With the RS-485 port set to Modbus they answer function 3/6/16 requests on holding registers whose hex numbers go on the wire as printed. This map covers total, tariff, per-phase and resettable energy, instantaneous values, I/O states and pulse counters, identification, CT/VT settings, reset commands and the DMTME-compatible block.

This page lists 182 Modbus registers for the ABB EQ meter A43 / A44 (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
EQ meter A43 / A44 (Modbus RTU)
Equipment type
Energy meter
Registers
182 (33 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
A43, A44, EQ A43, EQ A44
Source document
A43/A44 User Manual · 2CMC484001M0201 Revision E · rev. 2025-11-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB EQ meter A43 / A44 (Modbus RTU)

Integration in brief

Select Modbus for the RS-485 port in the meter's settings menu, then read holding registers with function 3 at the hex addresses as printed (0x5000 for total active import). Multi-register values are high word first; energies are 64-bit with 2 decimals.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20480Active import energyUINT64 ABCDTotal active import energy (0.01 kWh)Read
HR 20484Active export energyUINT64 ABCDTotal active export energyRead
HR 23296Voltage L1-NUINT32 ABCDVoltage L1-NRead
HR 23308Current L1UINT32 ABCDCurrent L1Read
HR 23316Active power TotalINT32 ABCDTotal active power (signed, 0.01 W)Read
HR 23340FrequencyUINT16FrequencyRead
HR 23354Power factor TotalINT16Total power factorRead
HR 35072Serial numberUINT32 ABCDSerial number, quick comms checkRead

Enable Modbus control & writes

In the meter's settings menu open the RS-485 communication page, choose Modbus (instead of EQ-Bus), then set baud rate, address and parity.

Byte order & addressing

Network setup

Watch out for

ABB EQ meter A43 / A44 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

182 of 182 shown
ABB EQ meter A43 / A44 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4098doc 1002DMTME phase voltage L1-NUINT32ABCDVRead
HR4100doc 1004DMTME phase voltage L2-NUINT32ABCDVRead
HR4102doc 1006DMTME phase voltage L3-NUINT32ABCDVRead
HR4104doc 1008DMTME line voltage L1-L2UINT32ABCDVRead
HR4106doc 100ADMTME line voltage L2-L3UINT32ABCDVRead
HR4108doc 100CDMTME line voltage L1-L3UINT32ABCDVRead
HR4112doc 1010DMTME line current L1UINT32ABCDmARead
HR4114doc 1012DMTME line current L2UINT32ABCDmARead
HR4116doc 1014DMTME line current L3UINT32ABCDmARead
HR4118doc 1016DMTME 3-phase system power factorPublished as PF x 1000.INT32ABCD× 0.001Read
HR4120doc 1018DMTME power factor L1Published as PF x 1000.INT32ABCD× 0.001Read
HR4122doc 101ADMTME power factor L2Published as PF x 1000.INT32ABCD× 0.001Read
HR4124doc 101CDMTME power factor L3Published as PF x 1000.INT32ABCD× 0.001Read
HR4134doc 1026DMTME 3-phase apparent powerUINT32ABCDVARead
HR4136doc 1028DMTME apparent power L1UINT32ABCDVARead
HR4138doc 102ADMTME apparent power L2UINT32ABCDVARead
HR4140doc 102CDMTME apparent power L3UINT32ABCDVARead
HR4142doc 102EDMTME 3-phase active powerWhole watts; use above 21 MW.INT32ABCDWRead
HR4144doc 1030DMTME active power L1INT32ABCDWRead
HR4146doc 1032DMTME active power L2INT32ABCDWRead
HR4148doc 1034DMTME active power L3INT32ABCDWRead
HR4150doc 1036DMTME 3-phase reactive powerINT32ABCDvarRead
HR4152doc 1038DMTME reactive power L1INT32ABCDvarRead
HR4154doc 103ADMTME reactive power L2INT32ABCDvarRead
HR4156doc 103CDMTME reactive power L3INT32ABCDvarRead
HR4166doc 1046DMTME frequencyUINT32ABCDmHzRead
HR20480doc 5000Active import energyMeter total, 2 decimals.UINT64ABCD× 0.01kWhRead
HR20484doc 5004Active export energyMeter total, 2 decimals.UINT64ABCD× 0.01kWhRead
HR20488doc 5008Active net energyImport minus export, signed.INT64ABCD× 0.01kWhRead
HR20492doc 500CReactive import energyMeter total, 2 decimals.UINT64ABCD× 0.01kvarhRead
HR20496doc 5010Reactive export energyMeter total, 2 decimals.UINT64ABCD× 0.01kvarhRead
HR20500doc 5014Reactive net energyImport minus export, signed.INT64ABCD× 0.01kvarhRead
HR20504doc 5018Apparent import energyMeter total, 2 decimals.UINT64ABCD× 0.01kVAhRead
HR20508doc 501CApparent export energyMeter total, 2 decimals.UINT64ABCD× 0.01kVAhRead
HR20512doc 5020Apparent net energyImport minus export, signed.INT64ABCD× 0.01kVAhRead
HR20516doc 5024Active import CO2CO2 equivalent of imported active energy.UINT64ABCD× 0.001kgRead
HR20532doc 5034Active import currencyCost equivalent of imported active energy.UINT64ABCD× 0.001currencyRead
HR20848doc 5170Active import tariff 1UINT64ABCD× 0.01kWhRead
HR20852doc 5174Active import tariff 2UINT64ABCD× 0.01kWhRead
HR20856doc 5178Active import tariff 3UINT64ABCD× 0.01kWhRead
HR20860doc 517CActive import tariff 4UINT64ABCD× 0.01kWhRead
HR20880doc 5190Active export tariff 1UINT64ABCD× 0.01kWhRead
HR20884doc 5194Active export tariff 2UINT64ABCD× 0.01kWhRead
HR20888doc 5198Active export tariff 3UINT64ABCD× 0.01kWhRead
HR20892doc 519CActive export tariff 4UINT64ABCD× 0.01kWhRead
HR20912doc 51B0Reactive import tariff 1UINT64ABCD× 0.01kvarhRead
HR20916doc 51B4Reactive import tariff 2UINT64ABCD× 0.01kvarhRead
HR20920doc 51B8Reactive import tariff 3UINT64ABCD× 0.01kvarhRead
HR20924doc 51BCReactive import tariff 4UINT64ABCD× 0.01kvarhRead
HR20944doc 51D0Reactive export tariff 1UINT64ABCD× 0.01kvarhRead
HR20948doc 51D4Reactive export tariff 2UINT64ABCD× 0.01kvarhRead
HR20952doc 51D8Reactive export tariff 3UINT64ABCD× 0.01kvarhRead
HR20956doc 51DCReactive export tariff 4UINT64ABCD× 0.01kvarhRead
HR21600doc 5460Active import energy L1UINT64ABCD× 0.01kWhRead
HR21604doc 5464Active import energy L2UINT64ABCD× 0.01kWhRead
HR21608doc 5468Active import energy L3UINT64ABCD× 0.01kWhRead
HR21612doc 546CActive export energy L1UINT64ABCD× 0.01kWhRead
HR21616doc 5470Active export energy L2UINT64ABCD× 0.01kWhRead
HR21620doc 5474Active export energy L3UINT64ABCD× 0.01kWhRead
HR21624doc 5478Active net energy L1INT64ABCD× 0.01kWhRead
HR21628doc 547CActive net energy L2INT64ABCD× 0.01kWhRead
HR21632doc 5480Active net energy L3INT64ABCD× 0.01kWhRead
HR21636doc 5484Reactive import energy L1UINT64ABCD× 0.01kvarhRead
HR21640doc 5488Reactive import energy L2UINT64ABCD× 0.01kvarhRead
HR21644doc 548CReactive import energy L3UINT64ABCD× 0.01kvarhRead
HR21648doc 5490Reactive export energy L1UINT64ABCD× 0.01kvarhRead
HR21652doc 5494Reactive export energy L2UINT64ABCD× 0.01kvarhRead
HR21656doc 5498Reactive export energy L3UINT64ABCD× 0.01kvarhRead
HR21660doc 549CReactive net energy L1INT64ABCD× 0.01kvarhRead
HR21664doc 54A0Reactive net energy L2INT64ABCD× 0.01kvarhRead
HR21668doc 54A4Reactive net energy L3INT64ABCD× 0.01kvarhRead
HR21672doc 54A8Apparent import energy L1UINT64ABCD× 0.01kVAhRead
HR21676doc 54ACApparent import energy L2UINT64ABCD× 0.01kVAhRead
HR21680doc 54B0Apparent import energy L3UINT64ABCD× 0.01kVAhRead
HR21684doc 54B4Apparent export energy L1UINT64ABCD× 0.01kVAhRead
HR21688doc 54B8Apparent export energy L2UINT64ABCD× 0.01kVAhRead
HR21692doc 54BCApparent export energy L3UINT64ABCD× 0.01kVAhRead
HR21696doc 54C0Apparent net energy L1INT64ABCD× 0.01kVAhRead
HR21700doc 54C4Apparent net energy L2INT64ABCD× 0.01kVAhRead
HR21704doc 54C8Apparent net energy L3INT64ABCD× 0.01kVAhRead
HR21804doc 552CResettable active importUINT64ABCD× 0.01kWhRead
HR21808doc 5530Resettable active exportUINT64ABCD× 0.01kWhRead
HR23296doc 5B00Voltage L1-NUINT32ABCD× 0.1VRead
HR23298doc 5B02Voltage L2-NUINT32ABCD× 0.1VRead
HR23300doc 5B04Voltage L3-NUINT32ABCD× 0.1VRead
HR23302doc 5B06Voltage L1-L2UINT32ABCD× 0.1VRead
HR23304doc 5B08Voltage L3-L2UINT32ABCD× 0.1VRead
HR23306doc 5B0AVoltage L1-L3UINT32ABCD× 0.1VRead
HR23308doc 5B0CCurrent L1UINT32ABCD× 0.01ARead
HR23310doc 5B0ECurrent L2UINT32ABCD× 0.01ARead
HR23312doc 5B10Current L3UINT32ABCD× 0.01ARead
HR23314doc 5B12Current NUINT32ABCD× 0.01ARead
HR23316doc 5B14Active power TotalSigned, 2 decimals; tops out near 21 MW.INT32ABCD× 0.01WRead
HR23318doc 5B16Active power L1INT32ABCD× 0.01WRead
HR23320doc 5B18Active power L2INT32ABCD× 0.01WRead
HR23322doc 5B1AActive power L3INT32ABCD× 0.01WRead
HR23324doc 5B1CReactive power TotalSigned, 2 decimals; tops out near 21 MW.INT32ABCD× 0.01varRead
HR23326doc 5B1EReactive power L1INT32ABCD× 0.01varRead
HR23328doc 5B20Reactive power L2INT32ABCD× 0.01varRead
HR23330doc 5B22Reactive power L3INT32ABCD× 0.01varRead
HR23332doc 5B24Apparent power TotalSigned, 2 decimals; tops out near 21 MW.INT32ABCD× 0.01VARead
HR23334doc 5B26Apparent power L1INT32ABCD× 0.01VARead
HR23336doc 5B28Apparent power L2INT32ABCD× 0.01VARead
HR23338doc 5B2AApparent power L3INT32ABCD× 0.01VARead
HR23340doc 5B2CFrequencyUINT16× 0.01HzRead
HR23341doc 5B2DPhase angle power TotalRange -180 to +180.INT16× 0.1°Read
HR23342doc 5B2EPhase angle power L1Range -180 to +180.INT16× 0.1°Read
HR23343doc 5B2FPhase angle power L2Range -180 to +180.INT16× 0.1°Read
HR23344doc 5B30Phase angle power L3Range -180 to +180.INT16× 0.1°Read
HR23345doc 5B31Phase angle voltage L1INT16× 0.1°Read
HR23346doc 5B32Phase angle voltage L2INT16× 0.1°Read
HR23347doc 5B33Phase angle voltage L3INT16× 0.1°Read
HR23351doc 5B37Phase angle current L1INT16× 0.1°Read
HR23352doc 5B38Phase angle current L2INT16× 0.1°Read
HR23353doc 5B39Phase angle current L3INT16× 0.1°Read
HR23354doc 5B3APower factor TotalRange -1.000 to +1.000.INT16× 0.001Read
HR23355doc 5B3BPower factor L1Range -1.000 to +1.000.INT16× 0.001Read
HR23356doc 5B3CPower factor L2Range -1.000 to +1.000.INT16× 0.001Read
HR23357doc 5B3DPower factor L3Range -1.000 to +1.000.INT16× 0.001Read
HR23358doc 5B3ECurrent quadrant TotalUINT16Read1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4
HR23359doc 5B3FCurrent quadrant L1UINT16Read1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4
HR23360doc 5B40Current quadrant L2UINT16Read1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4
HR23361doc 5B41Current quadrant L3UINT16Read1 = Quadrant 1; 2 = Quadrant 2; 3 = Quadrant 3; 4 = Quadrant 4
HR25344doc 6300Output 1Exists only on articles with that output.UINT16Read/write0 = OFF; 1 = ON
HR25345doc 6301Output 2Exists only on articles with that output.UINT16Read/write0 = OFF; 1 = ON
HR25346doc 6302Output 3Exists only on articles with that output.UINT16Read/write0 = OFF; 1 = ON
HR25347doc 6303Output 4Exists only on articles with that output.UINT16Read/write0 = OFF; 1 = ON
HR25352doc 6308Input 1 current stateUINT16Read0 = OFF; 1 = ON
HR25353doc 6309Input 2 current stateUINT16Read0 = OFF; 1 = ON
HR25354doc 630AInput 3 current stateUINT16Read0 = OFF; 1 = ON
HR25355doc 630BInput 4 current stateUINT16Read0 = OFF; 1 = ON
HR25360doc 6310Input 1 stored stateLatched state; clear with the reset register.UINT16Read0 = OFF; 1 = ON
HR25361doc 6311Input 2 stored stateLatched state; clear with the reset register.UINT16Read0 = OFF; 1 = ON
HR25362doc 6312Input 3 stored stateLatched state; clear with the reset register.UINT16Read0 = OFF; 1 = ON
HR25363doc 6313Input 4 stored stateLatched state; clear with the reset register.UINT16Read0 = OFF; 1 = ON
HR25368doc 6318Input 1 pulse counterUINT64ABCDRead
HR25372doc 631CInput 2 pulse counterUINT64ABCDRead
HR25376doc 6320Input 3 pulse counterUINT64ABCDRead
HR25380doc 6324Input 4 pulse counterUINT64ABCDRead
HR35072doc 8900Serial numberUINT32ABCDRead
HR35080doc 8908Meter firmware versionASCII, three numbers with dots (e.g. 1.0.0); unused bytes 0.STRING[16]Read
HR35088doc 8910Modbus mapping versionHigh byte = major, low byte = minor.UINT16Read
HR35168doc 8960Type designationASCII, 12 characters with null terminator, e.g. A43 552-100.STRING[12]Read
HR35331doc 8A03Day of week1-7, Monday = 1.UINT16Read
HR35332doc 8A04DST activeUINT16Read0 = DST inactive; 1 = DST active
HR35333doc 8A05Day type0-15 = day type 1-16.UINT16Read
HR35334doc 8A06Season0-3 = season 1-4.UINT16Read
HR35335doc 8A07Current tariffActive tariff, 1 to 4.UINT16Read/write
HR35375doc 8A2FPower fail counterUINT16Read
HR35400doc 8A48Reset count, resettable active energy importHow many times that resettable register was cleared.UINT64ABCDRead
HR35404doc 8A4CReset count, resettable active energy exportHow many times that resettable register was cleared.UINT64ABCDRead
HR35408doc 8A50Reset count, resettable reactive energy importHow many times that resettable register was cleared.UINT64ABCDRead
HR35412doc 8A54Reset count, resettable reactive energy exportHow many times that resettable register was cleared.UINT64ABCDRead
HR35844doc 8C04CT ratio primary currentUINT32ABCDRead/write
HR35846doc 8C06VT ratio primary voltageUINT32ABCDRead/write
HR35848doc 8C08CT ratio secondary currentUINT32ABCDRead/write
HR35850doc 8C0AVT ratio secondary voltageUINT32ABCDRead/write
HR36064doc 8CE0CO2 conversion factorUINT32ABCD× 0.001kg/kWhRead/write
HR36066doc 8CE2Currency conversion factorUINT32ABCD× 0.01Currency/kWhRead/write
HR36068doc 8CE4LED sourceUINT16Read/write0 = Active energy; 1 = Reactive energy
HR36069doc 8CE5Number of elementsMeasuring elements, 1-3. Read only.UINT16Read
HR36074doc 8CEADST enabledUINT16Read/write0 = Disabled; 1 = Enabled
HR36608doc 8F00Reset power fail counterWrite 1 to perform it.UINT16Write
HR36613doc 8F05Reset power outage timeWrite 1 to perform it.UINT16Write
HR36619doc 8F0BReset input 1 counterWrite 1 to perform it.UINT16Write
HR36620doc 8F0CReset input 2 counterWrite 1 to perform it.UINT16Write
HR36621doc 8F0DReset input 3 counterWrite 1 to perform it.UINT16Write
HR36622doc 8F0EReset input 4 counterWrite 1 to perform it.UINT16Write
HR36627doc 8F13Reset input 1 stored stateWrite 1 to perform it.UINT16Write
HR36628doc 8F14Reset input 2 stored stateWrite 1 to perform it.UINT16Write
HR36629doc 8F15Reset input 3 stored stateWrite 1 to perform it.UINT16Write
HR36630doc 8F16Reset input 4 stored stateWrite 1 to perform it.UINT16Write
HR36635doc 8F1BReset resettable active importWrite 1 to perform it.UINT16Write
HR36636doc 8F1CReset resettable active exportWrite 1 to perform it.UINT16Write
HR36637doc 8F1DReset resettable reactive importWrite 1 to perform it.UINT16Write
HR36638doc 8F1EReset resettable reactive exportWrite 1 to perform it.UINT16Write
HR36639doc 8F1FReset previous valuesWrite 1 to perform it.UINT16Write
HR36640doc 8F20Reset demandWrite 1 to perform it.UINT16Write
HR36657doc 8F31Reset system logWrite 1 to perform it.UINT16Write
HR36658doc 8F32Reset event logWrite 1 to perform it.UINT16Write
HR36659doc 8F33Reset net quality logWrite 1 to perform it.UINT16Write
HR36720doc 8F70Freeze demandWrite 1 to freeze the demand values.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB EQ meter A43 / A44 (Modbus RTU)

What Modbus registers does the ABB EQ meter A43 / A44 (Modbus RTU) have?

This map lists 182 registers: 182 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB EQ meter A43 / A44 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every start register is printed in hex exactly as sent on the bus; the manual says not to subtract 40000 or 1. 5000 hex = 20480 decimal. The example request frame reads 0x5000 with function 3.

What byte order does the ABB EQ meter A43 / A44 (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ABB EQ meter A43 / A44 (Modbus RTU)?

Start with HR 20480 Active import energy (Total active import energy (0.01 kWh)); HR 20484 Active export energy (Total active export energy); HR 23296 Voltage L1-N (Voltage L1-N); HR 23308 Current L1 (Current L1); HR 23316 Active power Total (Total active power (signed, 0.01 W)); HR 23340 Frequency (Frequency); HR 23354 Power factor Total (Total power factor); HR 35072 Serial number (Serial number, quick comms check).

How do I enable Modbus control of the ABB EQ meter A43 / A44 (Modbus RTU)?

In the meter's settings menu open the RS-485 communication page, choose Modbus (instead of EQ-Bus), then set baud rate, address and parity.

Where is the official ABB EQ meter A43 / A44 (Modbus RTU) Modbus documentation?

The source is A43/A44 User Manual (2CMC484001M0201 Revision E), revision 2025-11-07, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=2CMC484001M0201&LanguageCode=en&DocumentPartId=&Action=Launch.

More ABB Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: A43/A44 User Manual · 2CMC484001M0201 Revision E · rev. 2025-11-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.