Power meter (power quality analyzer) · Modbus register map
E-Mon (Honeywell) PowerSmart+ Advanced power quality meter Modbus register map
Updated 17 November 2026
The PowerSmart+ Advanced is a panel power quality meter sold under Honeywell's E-Mon brand; it reports device model ID 17500. Its 32-bit registers carry 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, THD, frequency, unbalance, demands, energy totals, digital I/O, basic setup, COM port settings, password and clear commands.
This page lists 109 Modbus registers for the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from E-Mon (Honeywell)’s own free documentation (linked below) and checked against it.
- Manufacturer
- E-Mon (Honeywell)
- Model
- PowerSmart+ Advanced power quality meter
- Equipment type
- Power meter (power quality analyzer)
- Registers
- 109 (17 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- E-Mon PowerSmart+ Advanced, PowerSmart Plus Advanced, Honeywell PowerSmart+, BG0545
Integration notes: E-Mon (Honeywell) PowerSmart+ Advanced power quality meter
Read 13952-14017 (phase values) and 14336-14361 (totals) with function 03; decode 32-bit integers low word first. Energy totals are at 14720 onward in whole kWh/kvarh.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1/V12 Voltage | UINT32 CDAB | V1/V12 voltage | Read |
| HR 13958 | I1 Current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 14722 | kWh export | UINT32 CDAB | kWh export | Read |
Enable Modbus control & writes
Choose the port protocol (Modbus RTU/ASCII) and address in the COM setup (2344-2359) or from the front panel; Modbus/TCP runs on the Ethernet option.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Voltage and power units change from 0.1 V / 1 W to 1 V / 1 kW when a PT ratio above 1 is set.
- 120 user-assignable registers (0-119, mapped by 120-239) let you pack scattered values into one read.
Network setup
- Set wiring mode, PT ratio and CT primary at 2304-2306 first (and the PT ratio factor at 2324 if used).
- Write the password to 2575 if protection is enabled.
Watch out for
- Changing the PT ratio from 1 changes the meaning of every voltage and power register.
- Broadcast (address 0) is not supported.
E-Mon (Honeywell) PowerSmart+ Advanced power quality meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2304 | Wiring mode | UINT16 | Read/write | 0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings | ||||
| HR | 2305 | PT ratio | 10-65000 = 1.0-6500.0; multiplied by the factor at 2324 (x1 or x10). | UINT16 | × 0.1 | Read/write | |||
| HR | 2306 | CT primary current | 1-50000 A. | UINT16 | A | Read/write | |||
| HR | 2315 | Nominal line frequency | 50 or 60. | UINT16 | Hz | Read/write | |||
| HR | 2344 | COM1 protocol | UINT16 | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII; 2 = DNP3.0; 5 = Profibus DP | ||||
| HR | 2345 | COM1 interface | UINT16 | Read/write | 0 = RS-232; 1 = RS-422; 2 = RS-485; 4 = Dial-up modem; 6 = Ethernet; 7 = Profibus; 8 = GSM/GPRS | ||||
| HR | 2346 | COM1 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 2347 | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 2348 | COM1 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity | ||||
| HR | 2354 | COM2 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 2355 | COM2 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 2356 | COM2 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity | ||||
| HR | 2560 | Warm restart | Write 0xFFFF to restart; reads 0. | UINT16 | Read/write | ||||
| HR | 2565 | Firmware version number | Two high decimal digits = major version, two low = minor. | UINT16 | Read | ||||
| HR | 2575 | Device authorization (password) | Write the 4-digit password before setup writes; reads 0 = allowed, -1 = password needed. | INT16 | Read/write | ||||
| HR | 11906doc 11906-11907 | Phase rotation order | UINT32 | CDAB | Read | 0 = Error; 1 = Positive (ABC); 2 = Negative (CBA) | |||
| HR | 12544doc 12544-12545 | Digital inputs (bitmap) | Bit 0 = DI1, bit 1 = DI2, and so on. | UINT32 | CDAB | Read | |||
| HR | 12800doc 12800-12801 | Relay outputs (bitmap) | Bit 0 = relay 1, bit 1 = relay 2, and so on. | UINT32 | CDAB | Read | |||
| HR | 13952doc 13952-13953 | V1/V12 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13954doc 13954-13955 | V2/V23 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13956doc 13956-13957 | V3/V31 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13958doc 13958-13959 | I1 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13960doc 13960-13961 | I2 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13962doc 13962-13963 | I3 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13966doc 13966-13967 | kW L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13968doc 13968-13969 | kW L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13970doc 13970-13971 | kvar L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13972doc 13972-13973 | kvar L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13974doc 13974-13975 | kvar L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13976doc 13976-13977 | kVA L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13978doc 13978-13979 | kVA L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13980doc 13980-13981 | kVA L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13988doc 13988-13989 | V1/V12 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13990doc 13990-13991 | V2/V23 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13992doc 13992-13993 | V3/V31 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13994doc 13994-13995 | I1 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13996doc 13996-13997 | I2 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13998doc 13998-13999 | I3 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14000doc 14000-14001 | I1 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14002doc 14002-14003 | I2 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14004doc 14004-14005 | I3 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14006doc 14006-14007 | I1 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14008doc 14008-14009 | I2 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14010doc 14010-14011 | I3 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14012doc 14012-14013 | V12 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14014doc 14014-14015 | V23 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14016doc 14016-14017 | V31 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14336doc 14336-14337 | Total kW | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14338doc 14338-14339 | Total kvar | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14340doc 14340-14341 | Total kVA | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14350doc 14350-14351 | Total kW export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14352doc 14352-14353 | Total kvar import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14354doc 14354-14355 | Total kvar export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14356doc 14356-14357 | 3-phase average L-N/L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14358doc 14358-14359 | 3-phase average L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14360doc 14360-14361 | 3-phase average current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14466doc 14466-14467 | In (neutral) Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14470doc 14470-14471 | Voltage unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14472doc 14472-14473 | Current unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14592doc 14592-14593 | V1/V12 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14594doc 14594-14595 | V2/V23 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14596doc 14596-14597 | V3/V31 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14598doc 14598-14599 | I1 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14600doc 14600-14601 | I2 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14602doc 14602-14603 | I3 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14604doc 14604-14605 | kW import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14606doc 14606-14607 | kvar import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14608doc 14608-14609 | kVA block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14610doc 14610-14611 | kW import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14612doc 14612-14613 | kvar import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14614doc 14614-14615 | kVA sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14622doc 14622-14623 | kW import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14624doc 14624-14625 | kvar import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14626doc 14626-14627 | kVA accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14634doc 14634-14635 | PF (import) at Max. kVA sliding window demand | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14636doc 14636-14637 | kW export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14638doc 14638-14639 | kvar export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14640doc 14640-14641 | kW export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14642doc 14642-14643 | kvar export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14644doc 14644-14645 | kW export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14646doc 14646-14647 | kvar export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14720doc 14720-14721 | kWh import | UINT32 | CDAB | kWh | Read | |||
| HR | 14722doc 14722-14723 | kWh export | UINT32 | CDAB | kWh | Read | |||
| HR | 14728doc 14728-14729 | kvarh import | UINT32 | CDAB | kvarh | Read | |||
| HR | 14730doc 14730-14731 | kvarh export | UINT32 | CDAB | kvarh | Read | |||
| HR | 14736doc 14736-14737 | kVAh total | UINT32 | CDAB | kVAh | Read | |||
| HR | 14742doc 14742-14743 | kVAh import | UINT32 | CDAB | kVAh | Read | |||
| HR | 14744doc 14744-14745 | kVAh export | UINT32 | CDAB | kVAh | Read | |||
| HR | 14756doc 14756-14757 | kvarh Q1 | UINT32 | CDAB | kvarh | Read | |||
| HR | 14758doc 14758-14759 | kvarh Q2 | UINT32 | CDAB | kvarh | Read | |||
| HR | 14760doc 14760-14761 | kvarh Q3 | UINT32 | CDAB | kvarh | Read | |||
| HR | 14762doc 14762-14763 | kvarh Q4 | UINT32 | CDAB | kvarh | Read | |||
| HR | 44102 | Clear energies | Write 0. | UINT16 | Write | ||||
| HR | 44103 | Clear maximum demands | UINT16 | Write | 0 = Clear all maximum demands; 1 = Clear power demands; 2 = Clear volt, ampere and harmonic demands | ||||
| HR | 44107 | Clear min/max log | Write 0. | UINT16 | Write | ||||
| HR | 46080doc 46080-46081 | Device serial number | UINT32 | CDAB | Read | ||||
| HR | 46082doc 46082-46083 | Device model ID | 17500 for PowerSmart+ Advanced. | UINT32 | CDAB | Read |
Notes on this map
- Addressing: the guide says to add 40001 to a register address to get the Modicon holding-register number (400001 above 9999), so printed addresses are 0-based wire addresses.
- Word order: 32-bit values are sent with the low-order word in the first (even) register and the high-order word in the second, so they are CDAB here.
- Units U1 (voltage) and U3 (power) depend on the PT ratio: with PT ratio = 1 they are 0.1 V and 0.001 kW/kvar/kVA (the scales used here); with PT ratio > 1 they become 1 V and 1 kW/kvar/kVA. U2 (current) is always 0.01 A.
- Function 04 can be used the same way as function 03.
- Voltage rows marked V1/V12 read line-to-neutral in 4LN3, 3LN3 and 3BLN3 wiring and line-to-line otherwise.
- Energy counters are whole kWh/kvarh/kVAh and roll over at the energy roll value set in the device options.
- Left out: 16-bit scaled registers (need per-site HI/LO scale arithmetic), 1-cycle and 1/2-cycle values, harmonics, min/max logs, TOU registers, the total PF lag/lead rows (printed as UINT16 in a two-register slot), setpoint, log and file-transfer registers.
- When password protection is on, write the password to 2575 before any setup or clear command, otherwise writes fail with exception 01.
- The SATEC PM175 guide (BG0416 Rev. A7, satec-global.com) lists the same model ID 17500 and the same addresses for every register in this map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter
What Modbus registers does the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter have?
This map lists 109 registers: 109 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers 0-65535 and says to add 40001 (or 400001 above 9999) for Modicon holding-register numbers, so the printed address goes straight into the frame: 13952 is wire address 13952 (Modicon 413953).
What byte order does the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter?
Start with HR 13952 V1/V12 Voltage (V1/V12 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).
How do I enable Modbus control of the E-Mon (Honeywell) PowerSmart+ Advanced power quality meter?
Choose the port protocol (Modbus RTU/ASCII) and address in the COM setup (2344-2359) or from the front panel; Modbus/TCP runs on the Ethernet option.
Where is the official E-Mon (Honeywell) PowerSmart+ Advanced power quality meter Modbus documentation?
The source is E-Mon PowerSmart+ Advanced Power Quality Meter - MODBUS Communications Protocol Reference Guide (BG0545 Rev. A1), revision 2013-07, published free by E-Mon (Honeywell) at https://prod-edam.honeywell.com/content/dam/honeywell-edam/hbt/en-us/documents/manuals-and-guides/reference-guides/hbt-bms-E-Mon-PowerSmart-Advanced-MODBUS-Reference-Guide-BG0545-REV-A1.pdf.
Other power & energy meters register maps
- Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Power meter (power quality meter)
GE Multilin Multilin PQMII power quality meter
Multilin PQMII per instruction manual GEK-113532 (communications guide chapter).
Also known as: PQM II, GE Multilin PQMII, PQM2 - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511
All power & energy meters Modbus register maps →
Source: E-Mon PowerSmart+ Advanced Power Quality Meter - MODBUS Communications Protocol Reference Guide · BG0545 Rev. A1 · rev. 2013-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.