- Home
- Modbus register maps
- Accuenergy
- AcuRev 1310 series DIN-rail power meter
Power meter · Modbus register map
Accuenergy AcuRev 1310 series DIN-rail power meter Modbus register map
Updated 17 November 2026
The AcuRev 1310 series are Accuenergy's DIN-rail power and energy meters with an RS-485 port that speaks Modbus RTU (or BACnet MS/TP). This map covers the float real-time block (currents, voltages, frequency, power, power factor, phase angles), the demand and neutral/residual block, per-phase and per-tariff energy counters, the meter status words and the dual-source energy feature. The SunSpec mirror blocks, peak-demand timestamps, monthly history and max/min logs in the same workbook are not repeated.
This page lists 150 Modbus registers for the Accuenergy AcuRev 1310 series DIN-rail power meter — 96 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Accuenergy’s own free documentation (linked below) and checked against it.
- Manufacturer
- Accuenergy
- Model
- AcuRev 1310 series DIN-rail power meter
- Equipment type
- Power meter
- Registers
- 150 (96 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310
Integration notes: Accuenergy AcuRev 1310 series DIN-rail power meter
Read the float block 2000H-2045H (8192-8261) for live values and the Int32 energy block 2046H-2085H for kWh-type counters; everything is big-endian, high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8194 | Phase A Current | FLOAT32 ABCD | Phase A current | Read |
| HR 8202 | Phase A Voltage | FLOAT32 ABCD | Phase A voltage | Read |
| HR 8216 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 8218 | Total Active Power | FLOAT32 ABCD | Total active power | Read |
| HR 8242 | Power Factor | FLOAT32 ABCD | Total power factor | Read |
| HR 8270 | Total Active Energy Imported | INT32 ABCD | Total active energy imported | Read/write |
| HR 8262 | Total Active Energy Exported | INT32 ABCD | Total active energy exported | Read/write |
Enable Modbus control & writes
Set the Modbus address and serial (or network) parameters on the meter; the workbook does not list the factory communication defaults.
Byte order & addressing
- Energy counters are signed Int32 even though import/export totals only count up; net counters can go negative.
- Load type is a float holding an ASCII code (67, 76 or 82).
Network setup
- See the AcuRev 1310 user manual for the front-panel communication settings.
Watch out for
- Energy registers are writable; a mistaken write with function 16 overwrites the counter.
Accuenergy AcuRev 1310 series DIN-rail power meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 256doc 0100H | The Result of Wiring Check | Result code; meaning listed in the maker's map. | UINT16 | Read | ||||
| HR | 257doc 0101H | Seals status | 0x0A = sealed; any other value = seal opened. | UINT16 | Read | ||||
| HR | 4608doc 1200H | Neutral Current | FLOAT32 | ABCD | A | Read | |||
| HR | 4610doc 1202H | Residual Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 4612doc 1204H | Temperature of chips | FLOAT32 | ABCD | °C | Read | |||
| HR | 4614doc 1206H | Load type | ASCII code as a float: 67 'C' capacitive, 76 'L' inductive, 82 'R' resistive. | FLOAT32 | ABCD | Read | |||
| HR | 4616doc 1208H | system active power demand | FLOAT32 | ABCD | W | Read | |||
| HR | 4618doc 120AH | system Reactive power demand | FLOAT32 | ABCD | var | Read | |||
| HR | 4620doc 120CH | system apparent power demand | FLOAT32 | ABCD | VA | Read | |||
| HR | 4622doc 120EH | Phase A current demand | FLOAT32 | ABCD | A | Read | |||
| HR | 4624doc 1210H | Phase B current demand | FLOAT32 | ABCD | A | Read | |||
| HR | 4626doc 1212H | Phase C current demand | FLOAT32 | ABCD | A | Read | |||
| HR | 4628doc 1214H | System Active Power Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | W | Read | ||
| HR | 4630doc 1216H | System Reactive Power Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | var | Read | ||
| HR | 4632doc 1218H | System Apparent Power Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | VA | Read | ||
| HR | 4634doc 121AH | Phase A Current Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | A | Read | ||
| HR | 4636doc 121CH | Phase B Current Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | A | Read | ||
| HR | 4638doc 121EH | Phase C Current Demand Prediction | Predicted demand for the current window. | FLOAT32 | ABCD | A | Read | ||
| HR | 4640doc 1220H | Residual Current | FLOAT32 | ABCD | A | Read | |||
| HR | 4864doc 1300H | Total Active Energy | INT32 | ABCD | Wh | Read/write | |||
| HR | 4866doc 1302H | Total Active Energy tariff 1 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4868doc 1304H | Total Active Energy tariff 2 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4870doc 1306H | Total Active Energy tariff 3 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4872doc 1308H | Total Active Energy tariff 4 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4874doc 130AH | Net Active Energy | Signed net value. | INT32 | ABCD | Wh | Read/write | ||
| HR | 4876doc 130CH | Net Active Energy tariff 1 | Signed net value. | INT32 | ABCD | Wh | Read/write | ||
| HR | 4878doc 130EH | Net Active Energy tariff 2 | Signed net value. | INT32 | ABCD | Wh | Read/write | ||
| HR | 4880doc 1310H | Net Active Energy tariff 3 | Signed net value. | INT32 | ABCD | Wh | Read/write | ||
| HR | 4882doc 1312H | Net Active Energy tariff 4 | Signed net value. | INT32 | ABCD | Wh | Read/write | ||
| HR | 4884doc 1314H | Imported Active Energy tariff 1 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4886doc 1316H | Imported Active Energy tariff 2 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4888doc 1318H | Imported Active Energy tariff 3 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4890doc 131AH | Imported Active Energy tariff 4 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4892doc 131CH | Exported Active Energy tariff 1 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4894doc 131EH | Exported Active Energy tariff 2 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4896doc 1320H | Exported Active Energy tariff 3 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4898doc 1322H | Exported Active Energy tariff 4 | INT32 | ABCD | Wh | Read/write | |||
| HR | 4900doc 1324H | Total Reactive Energy Imported | INT32 | ABCD | varh | Read/write | |||
| HR | 4902doc 1326H | Total Reactive Energy Imported tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4904doc 1328H | Total Reactive Energy Imported tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4906doc 132AH | Total Reactive Energy Imported tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4908doc 132CH | Total Reactive Energy Imported tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4910doc 132EH | Total Reactive Energy Exported | INT32 | ABCD | varh | Read/write | |||
| HR | 4912doc 1330H | Exported Reactive Energy tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4914doc 1332H | Exported Reactive Energy tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4916doc 1334H | Exported Reactive Energy tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4918doc 1336H | Exported Reactive Energy tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4920doc 1338H | Total Reactive Energy | INT32 | ABCD | varh | Read/write | |||
| HR | 4922doc 133AH | Total Reactive Energy tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4924doc 133CH | Total Reactive Energy tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4926doc 133EH | Total Reactive Energy tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4928doc 1340H | Total Reactive Energy tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4930doc 1342H | Net Reactive Energy | Signed net value. | INT32 | ABCD | varh | Read/write | ||
| HR | 4932doc 1344H | Net Reactive Energy tariff 1 | Signed net value. | INT32 | ABCD | varh | Read/write | ||
| HR | 4934doc 1346H | Net Reactive Energy tariff 2 | Signed net value. | INT32 | ABCD | varh | Read/write | ||
| HR | 4936doc 1348H | Net Reactive Energy tariff 3 | Signed net value. | INT32 | ABCD | varh | Read/write | ||
| HR | 4938doc 134AH | Net Reactive Energy tariff 4 | Signed net value. | INT32 | ABCD | varh | Read/write | ||
| HR | 4940doc 134CH | Total Reactive Energy Imported Q1 tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4942doc 134EH | Total Reactive Energy Imported Q1 tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4944doc 1350H | Total Reactive Energy Imported Q1 tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4946doc 1352H | Total Reactive Energy Imported Q1 tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4948doc 1354H | Total Reactive Energy Imported Q2 tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4950doc 1356H | Total Reactive Energy Imported Q2 tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4952doc 1358H | Total Reactive Energy Imported Q2 tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4954doc 135AH | Total Reactive Energy Imported Q2 tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4956doc 135CH | Total Reactive Energy Exported Q3 tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4958doc 135EH | Total Reactive Energy Exported Q3 tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4960doc 1360H | Total Reactive Energy Exported Q3 tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4962doc 1362H | Total Reactive Energy Exported Q3 tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 4964doc 1364H | Total Reactive Energy Exported Q4 tariff 1 | INT32 | ABCD | varh | Read/write | |||
| HR | 4966doc 1366H | Total Reactive Energy Exported Q4 tariff 2 | INT32 | ABCD | varh | Read/write | |||
| HR | 4968doc 1368H | Total Reactive Energy Exported Q4 tariff 3 | INT32 | ABCD | varh | Read/write | |||
| HR | 4970doc 136AH | Total Reactive Energy Exported Q4 tariff 4 | INT32 | ABCD | varh | Read/write | |||
| HR | 8192doc 2000H | Total Current | FLOAT32 | ABCD | A | Read | |||
| HR | 8194doc 2002H | Phase A Current | FLOAT32 | ABCD | A | Read | |||
| HR | 8196doc 2004H | Phase B Current | FLOAT32 | ABCD | A | Read | |||
| HR | 8198doc 2006H | Phase C Current | FLOAT32 | ABCD | A | Read | |||
| HR | 8200doc 2008H | Phase Average Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8202doc 200AH | Phase A Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8204doc 200CH | Phase B Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8206doc 200EH | Phase C Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8208doc 2010H | Line Average Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8210doc 2012H | Line AB Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8212doc 2014H | Line BC Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8214doc 2016H | Line CA Voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8216doc 2018H | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 8218doc 201AH | Total Active Power | FLOAT32 | ABCD | W | Read | |||
| HR | 8220doc 201CH | Phase A Active Power | FLOAT32 | ABCD | W | Read | |||
| HR | 8222doc 201EH | Phase B Active Power | FLOAT32 | ABCD | W | Read | |||
| HR | 8224doc 2020H | Phase C Active Power | FLOAT32 | ABCD | W | Read | |||
| HR | 8226doc 2022H | Total Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8228doc 2024H | Phase A Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8230doc 2026H | Phase B Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8232doc 2028H | Phase C Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8234doc 202AH | Total Reactive Power | FLOAT32 | ABCD | var | Read | |||
| HR | 8236doc 202CH | Phase A Reactive Power | FLOAT32 | ABCD | var | Read | |||
| HR | 8238doc 202EH | Phase B Reactive Power | FLOAT32 | ABCD | var | Read | |||
| HR | 8240doc 2030H | Phase C Reactive Power | FLOAT32 | ABCD | var | Read | |||
| HR | 8242doc 2032H | Power Factor | FLOAT32 | ABCD | Read | ||||
| HR | 8244doc 2034H | PF phase A | FLOAT32 | ABCD | Read | ||||
| HR | 8246doc 2036H | PF phase B | FLOAT32 | ABCD | Read | ||||
| HR | 8248doc 2038H | PF phase C | FLOAT32 | ABCD | Read | ||||
| HR | 8250doc 203AH | Phase Angle of V1 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8252doc 203CH | Phase Angle of V2 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8254doc 203EH | Phase Angle of V3 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8256doc 2040H | Phase Angle of I1 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8258doc 2042H | Phase Angle of I2 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8260doc 2044H | Phase Angle of I3 to V1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 8262doc 2046H | Total Active Energy Exported | INT32 | ABCD | Wh | Read/write | |||
| HR | 8264doc 2048H | Active Energy Exported in Phase A | INT32 | ABCD | Wh | Read/write | |||
| HR | 8266doc 204AH | Active Energy Exported in Phase B | INT32 | ABCD | Wh | Read/write | |||
| HR | 8268doc 204CH | Active Energy Exported in Phase C | INT32 | ABCD | Wh | Read/write | |||
| HR | 8270doc 204EH | Total Active Energy Imported | INT32 | ABCD | Wh | Read/write | |||
| HR | 8272doc 2050H | Active Energy Imported in Phase A | INT32 | ABCD | Wh | Read/write | |||
| HR | 8274doc 2052H | Active Energy Imported in Phase B | INT32 | ABCD | Wh | Read/write | |||
| HR | 8276doc 2054H | Active Energy Imported in Phase C | INT32 | ABCD | Wh | Read/write | |||
| HR | 8278doc 2056H | Total Apparent Energy Exported | INT32 | ABCD | VAh | Read/write | |||
| HR | 8280doc 2058H | Apparent Energy Exported in Phase A | INT32 | ABCD | VAh | Read/write | |||
| HR | 8282doc 205AH | Apparent Energy Exported in Phase B | INT32 | ABCD | VAh | Read/write | |||
| HR | 8284doc 205CH | Apparent Energy Exported in Phase C | INT32 | ABCD | VAh | Read/write | |||
| HR | 8286doc 205EH | Total Apparent Energy Imported | INT32 | ABCD | VAh | Read/write | |||
| HR | 8288doc 2060H | Apparent Energy Imported in Phase A | INT32 | ABCD | VAh | Read/write | |||
| HR | 8290doc 2062H | Apparent Energy Imported in Phase B | INT32 | ABCD | VAh | Read/write | |||
| HR | 8292doc 2064H | Apparent Energy Imported in Phase C | INT32 | ABCD | VAh | Read/write | |||
| HR | 8294doc 2066H | Total Reactive Imported Q1 | INT32 | ABCD | varh | Read/write | |||
| HR | 8296doc 2068H | Reactive Imported Q1 Phase A | INT32 | ABCD | varh | Read/write | |||
| HR | 8298doc 206AH | Reactive Imported Q1 Phase B | INT32 | ABCD | varh | Read/write | |||
| HR | 8300doc 206CH | Reactive Imported Q1 Phase C | INT32 | ABCD | varh | Read/write | |||
| HR | 8302doc 206EH | Total Reactive Imported Q2 | INT32 | ABCD | varh | Read/write | |||
| HR | 8304doc 2070H | Reactive Imported Q2 Phase A | INT32 | ABCD | varh | Read/write | |||
| HR | 8306doc 2072H | Reactive Imported Q2 Phase B | INT32 | ABCD | varh | Read/write | |||
| HR | 8308doc 2074H | Reactive Imported Q2 Phase C | INT32 | ABCD | varh | Read/write | |||
| HR | 8310doc 2076H | Total Reactive Energy Exported Q3 | INT32 | ABCD | varh | Read/write | |||
| HR | 8312doc 2078H | Reactive Energy Exported Q3 Phase A | INT32 | ABCD | varh | Read/write | |||
| HR | 8314doc 207AH | Reactive Energy Exported Q3 Phase B | INT32 | ABCD | varh | Read/write | |||
| HR | 8316doc 207CH | Reactive Energy Exported Q3 Phase C | INT32 | ABCD | varh | Read/write | |||
| HR | 8318doc 207EH | Total Reactive Energy Exported Q4 | INT32 | ABCD | varh | Read/write | |||
| HR | 8320doc 2080H | Reactive Energy Exported Q4 Phase A | INT32 | ABCD | varh | Read/write | |||
| HR | 8322doc 2082H | Reactive Energy Exported Q4 Phase B | INT32 | ABCD | varh | Read/write | |||
| HR | 8324doc 2084H | Reactive Energy Exported Q4 Phase C | INT32 | ABCD | varh | Read/write | |||
| HR | 12288doc 3000H | Dual-source enable | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 12289doc 3001H | Dual-source energy source | UINT16 | Read/write | 0 = From Grid; 1 = From alternative source | ||||
| HR | 12544doc 3100H | Clear dual-source energy | Write 0x0A to execute. | UINT16 | Write | ||||
| HR | 12545doc 3101H | Clear Dual-source change log | Write 0x0A to execute. | UINT16 | Write | ||||
| HR | 12800doc 3200H | Grid Active Energy | UINT32 | ABCD | Wh | Read/write | |||
| HR | 12802doc 3202H | Alternate Active Energy | UINT32 | ABCD | Wh | Read/write | |||
| HR | 12804doc 3204H | Grid Reactive Energy | UINT32 | ABCD | varh | Read/write | |||
| HR | 12806doc 3206H | Alternate Reactive Energy | UINT32 | ABCD | varh | Read/write | |||
| HR | 12808doc 3208H | Grid Apparent Energy | UINT32 | ABCD | VAh | Read/write | |||
| HR | 12810doc 320AH | Alternate Apparent Energy | UINT32 | ABCD | VAh | Read/write |
Notes on this map
- The Data Types sheet states high byte first within a register and the high-order register first for 32-bit values, so floats and 32-bit counters are ABCD.
- Energy counters are 32-bit integers in Wh, varh or VAh as labelled (revision 1.1 added these units); they can be written (function 16) to preset them.
- Function codes per block: 03 to read, 16 to write energy, dual-source settings and commands.
- Left out: the SunSpec blocks at 1000H and C350H (scaled duplicates of the same values), monthly energy history, peak-demand values with 6-byte timestamps, demand-reset/unseal/event records, max/min logs, and the dual-source change log records (packed timestamps).
- Register 0100H returns a wiring-check result code; the code list is referenced in the maker's map but not reproduced here.
- Transport and the 1312/1313/1314 model names come from the AcuRev 1310 user manual (https://www.accuenergy.com/wp-content/uploads/AcuRev-1310-User-Manual.pdf): Modbus RTU (factory default) or BACnet MS/TP on the built-in RS-485 port; no Modbus TCP.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Accuenergy AcuRev 1310 series DIN-rail power meter
What Modbus registers does the Accuenergy AcuRev 1310 series DIN-rail power meter have?
This map lists 150 registers: 150 holding registers. 96 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Accuenergy AcuRev 1310 series DIN-rail power meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The workbook states that its addresses are 0-based Modbus PDU addresses and prints each as hex and decimal (2000H = 8192). Request the decimal value as given.
What byte order does the Accuenergy AcuRev 1310 series DIN-rail power meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Accuenergy AcuRev 1310 series DIN-rail power meter?
Start with HR 8194 Phase A Current (Phase A current); HR 8202 Phase A Voltage (Phase A voltage); HR 8216 Frequency (Frequency); HR 8218 Total Active Power (Total active power); HR 8242 Power Factor (Total power factor); HR 8270 Total Active Energy Imported (Total active energy imported); HR 8262 Total Active Energy Exported (Total active energy exported).
How do I enable Modbus control of the Accuenergy AcuRev 1310 series DIN-rail power meter?
Set the Modbus address and serial (or network) parameters on the meter; the workbook does not list the factory communication defaults.
Where is the official Accuenergy AcuRev 1310 series DIN-rail power meter Modbus documentation?
The source is AcuRev 1310 Modbus Register Map (XLSX) (Revision 1.1), revision 2026-10-27, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-1310-Modbus-Map.xlsx.
More Accuenergy Modbus register maps
- Power meter
Accuenergy Acuvim II Series
Accuenergy Acuvim II series multifunction power meters (manual 1040E1303, V3.2.16 revised September 2026).
Also known as: Acuvim IIR, Acuvim IIW - Power meter
Accuenergy Acuvim-L Series
Accuenergy Acuvim-L series multifunction power and energy meters, user manual V4 (V 4.1.12, revised March 2026).
Also known as: Acuvim-CL, Acuvim-EL
Other power & energy meters register maps
- Power meter (universal measuring / power quality device)
Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)
SINEAX CAM with Ethernet (Modbus/TCP) bus card; document W 157471, change 2014-018. Instantaneous values, THD/TDD, system analysis, analog inputs, I/O states.
Also known as: SINEAX CAM, CAM - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Power meter (power analyzer)
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
WM14 Advanced (revision 5 onward) and CPT-DIN Advanced (revision 6 onward) with RS485 (or RS232 on CPT-DIN), protocol version 2 revision 2 (2008-01-09).
Also known as: WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter (power quality analyzer)
E-Mon (Honeywell) PowerSmart+ Advanced power quality meter
Honeywell E-Mon PowerSmart+ Advanced power quality meter, per Modbus reference guide BG0545 Rev. A1 (Jul 2013).
Also known as: E-Mon PowerSmart+ Advanced, PowerSmart Plus Advanced, Honeywell PowerSmart+, BG0545 - Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2
All power & energy meters Modbus register maps →
Source: AcuRev 1310 Modbus Register Map (XLSX) · Revision 1.1 · rev. 2026-10-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.