Accuenergy AcuRev 1310 series DIN-rail power meter Modbus register map

Updated 17 November 2026

Short answer

The AcuRev 1310 series are Accuenergy's DIN-rail power and energy meters with an RS-485 port that speaks Modbus RTU (or BACnet MS/TP). This map covers the float real-time block (currents, voltages, frequency, power, power factor, phase angles), the demand and neutral/residual block, per-phase and per-tariff energy counters, the meter status words and the dual-source energy feature. The SunSpec mirror blocks, peak-demand timestamps, monthly history and max/min logs in the same workbook are not repeated.

This page lists 150 Modbus registers for the Accuenergy AcuRev 1310 series DIN-rail power meter — 96 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Accuenergy’s own free documentation (linked below) and checked against it.

Manufacturer
Accuenergy
Model
AcuRev 1310 series DIN-rail power meter
Equipment type
Power meter
Registers
150 (96 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310
Source document
AcuRev 1310 Modbus Register Map (XLSX) · Revision 1.1 · rev. 2026-10-27
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Accuenergy AcuRev 1310 series DIN-rail power meter

Integration in brief

Read the float block 2000H-2045H (8192-8261) for live values and the Int32 energy block 2046H-2085H for kWh-type counters; everything is big-endian, high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8194Phase A CurrentFLOAT32 ABCDPhase A currentRead
HR 8202Phase A VoltageFLOAT32 ABCDPhase A voltageRead
HR 8216FrequencyFLOAT32 ABCDFrequencyRead
HR 8218Total Active PowerFLOAT32 ABCDTotal active powerRead
HR 8242Power FactorFLOAT32 ABCDTotal power factorRead
HR 8270Total Active Energy ImportedINT32 ABCDTotal active energy importedRead/write
HR 8262Total Active Energy ExportedINT32 ABCDTotal active energy exportedRead/write

Enable Modbus control & writes

Set the Modbus address and serial (or network) parameters on the meter; the workbook does not list the factory communication defaults.

Byte order & addressing

Network setup

Watch out for

Accuenergy AcuRev 1310 series DIN-rail power meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

150 of 150 shown
Accuenergy AcuRev 1310 series DIN-rail power meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR256doc 0100HThe Result of Wiring CheckResult code; meaning listed in the maker's map.UINT16Read
HR257doc 0101HSeals status0x0A = sealed; any other value = seal opened.UINT16Read
HR4608doc 1200HNeutral CurrentFLOAT32ABCDARead
HR4610doc 1202HResidual VoltageFLOAT32ABCDVRead
HR4612doc 1204HTemperature of chipsFLOAT32ABCD°CRead
HR4614doc 1206HLoad typeASCII code as a float: 67 'C' capacitive, 76 'L' inductive, 82 'R' resistive.FLOAT32ABCDRead
HR4616doc 1208Hsystem active power demandFLOAT32ABCDWRead
HR4618doc 120AHsystem Reactive power demandFLOAT32ABCDvarRead
HR4620doc 120CHsystem apparent power demandFLOAT32ABCDVARead
HR4622doc 120EHPhase A current demandFLOAT32ABCDARead
HR4624doc 1210HPhase B current demandFLOAT32ABCDARead
HR4626doc 1212HPhase C current demandFLOAT32ABCDARead
HR4628doc 1214HSystem Active Power Demand PredictionPredicted demand for the current window.FLOAT32ABCDWRead
HR4630doc 1216HSystem Reactive Power Demand PredictionPredicted demand for the current window.FLOAT32ABCDvarRead
HR4632doc 1218HSystem Apparent Power Demand PredictionPredicted demand for the current window.FLOAT32ABCDVARead
HR4634doc 121AHPhase A Current Demand PredictionPredicted demand for the current window.FLOAT32ABCDARead
HR4636doc 121CHPhase B Current Demand PredictionPredicted demand for the current window.FLOAT32ABCDARead
HR4638doc 121EHPhase C Current Demand PredictionPredicted demand for the current window.FLOAT32ABCDARead
HR4640doc 1220HResidual CurrentFLOAT32ABCDARead
HR4864doc 1300HTotal Active EnergyINT32ABCDWhRead/write
HR4866doc 1302HTotal Active Energy tariff 1INT32ABCDWhRead/write
HR4868doc 1304HTotal Active Energy tariff 2INT32ABCDWhRead/write
HR4870doc 1306HTotal Active Energy tariff 3INT32ABCDWhRead/write
HR4872doc 1308HTotal Active Energy tariff 4INT32ABCDWhRead/write
HR4874doc 130AHNet Active EnergySigned net value.INT32ABCDWhRead/write
HR4876doc 130CHNet Active Energy tariff 1Signed net value.INT32ABCDWhRead/write
HR4878doc 130EHNet Active Energy tariff 2Signed net value.INT32ABCDWhRead/write
HR4880doc 1310HNet Active Energy tariff 3Signed net value.INT32ABCDWhRead/write
HR4882doc 1312HNet Active Energy tariff 4Signed net value.INT32ABCDWhRead/write
HR4884doc 1314HImported Active Energy tariff 1INT32ABCDWhRead/write
HR4886doc 1316HImported Active Energy tariff 2INT32ABCDWhRead/write
HR4888doc 1318HImported Active Energy tariff 3INT32ABCDWhRead/write
HR4890doc 131AHImported Active Energy tariff 4INT32ABCDWhRead/write
HR4892doc 131CHExported Active Energy tariff 1INT32ABCDWhRead/write
HR4894doc 131EHExported Active Energy tariff 2INT32ABCDWhRead/write
HR4896doc 1320HExported Active Energy tariff 3INT32ABCDWhRead/write
HR4898doc 1322HExported Active Energy tariff 4INT32ABCDWhRead/write
HR4900doc 1324HTotal Reactive Energy ImportedINT32ABCDvarhRead/write
HR4902doc 1326HTotal Reactive Energy Imported tariff 1INT32ABCDvarhRead/write
HR4904doc 1328HTotal Reactive Energy Imported tariff 2INT32ABCDvarhRead/write
HR4906doc 132AHTotal Reactive Energy Imported tariff 3INT32ABCDvarhRead/write
HR4908doc 132CHTotal Reactive Energy Imported tariff 4INT32ABCDvarhRead/write
HR4910doc 132EHTotal Reactive Energy ExportedINT32ABCDvarhRead/write
HR4912doc 1330HExported Reactive Energy tariff 1INT32ABCDvarhRead/write
HR4914doc 1332HExported Reactive Energy tariff 2INT32ABCDvarhRead/write
HR4916doc 1334HExported Reactive Energy tariff 3INT32ABCDvarhRead/write
HR4918doc 1336HExported Reactive Energy tariff 4INT32ABCDvarhRead/write
HR4920doc 1338HTotal Reactive EnergyINT32ABCDvarhRead/write
HR4922doc 133AHTotal Reactive Energy tariff 1INT32ABCDvarhRead/write
HR4924doc 133CHTotal Reactive Energy tariff 2INT32ABCDvarhRead/write
HR4926doc 133EHTotal Reactive Energy tariff 3INT32ABCDvarhRead/write
HR4928doc 1340HTotal Reactive Energy tariff 4INT32ABCDvarhRead/write
HR4930doc 1342HNet Reactive EnergySigned net value.INT32ABCDvarhRead/write
HR4932doc 1344HNet Reactive Energy tariff 1Signed net value.INT32ABCDvarhRead/write
HR4934doc 1346HNet Reactive Energy tariff 2Signed net value.INT32ABCDvarhRead/write
HR4936doc 1348HNet Reactive Energy tariff 3Signed net value.INT32ABCDvarhRead/write
HR4938doc 134AHNet Reactive Energy tariff 4Signed net value.INT32ABCDvarhRead/write
HR4940doc 134CHTotal Reactive Energy Imported Q1 tariff 1INT32ABCDvarhRead/write
HR4942doc 134EHTotal Reactive Energy Imported Q1 tariff 2INT32ABCDvarhRead/write
HR4944doc 1350HTotal Reactive Energy Imported Q1 tariff 3INT32ABCDvarhRead/write
HR4946doc 1352HTotal Reactive Energy Imported Q1 tariff 4INT32ABCDvarhRead/write
HR4948doc 1354HTotal Reactive Energy Imported Q2 tariff 1INT32ABCDvarhRead/write
HR4950doc 1356HTotal Reactive Energy Imported Q2 tariff 2INT32ABCDvarhRead/write
HR4952doc 1358HTotal Reactive Energy Imported Q2 tariff 3INT32ABCDvarhRead/write
HR4954doc 135AHTotal Reactive Energy Imported Q2 tariff 4INT32ABCDvarhRead/write
HR4956doc 135CHTotal Reactive Energy Exported Q3 tariff 1INT32ABCDvarhRead/write
HR4958doc 135EHTotal Reactive Energy Exported Q3 tariff 2INT32ABCDvarhRead/write
HR4960doc 1360HTotal Reactive Energy Exported Q3 tariff 3INT32ABCDvarhRead/write
HR4962doc 1362HTotal Reactive Energy Exported Q3 tariff 4INT32ABCDvarhRead/write
HR4964doc 1364HTotal Reactive Energy Exported Q4 tariff 1INT32ABCDvarhRead/write
HR4966doc 1366HTotal Reactive Energy Exported Q4 tariff 2INT32ABCDvarhRead/write
HR4968doc 1368HTotal Reactive Energy Exported Q4 tariff 3INT32ABCDvarhRead/write
HR4970doc 136AHTotal Reactive Energy Exported Q4 tariff 4INT32ABCDvarhRead/write
HR8192doc 2000HTotal CurrentFLOAT32ABCDARead
HR8194doc 2002HPhase A CurrentFLOAT32ABCDARead
HR8196doc 2004HPhase B CurrentFLOAT32ABCDARead
HR8198doc 2006HPhase C CurrentFLOAT32ABCDARead
HR8200doc 2008HPhase Average VoltageFLOAT32ABCDVRead
HR8202doc 200AHPhase A VoltageFLOAT32ABCDVRead
HR8204doc 200CHPhase B VoltageFLOAT32ABCDVRead
HR8206doc 200EHPhase C VoltageFLOAT32ABCDVRead
HR8208doc 2010HLine Average VoltageFLOAT32ABCDVRead
HR8210doc 2012HLine AB VoltageFLOAT32ABCDVRead
HR8212doc 2014HLine BC VoltageFLOAT32ABCDVRead
HR8214doc 2016HLine CA VoltageFLOAT32ABCDVRead
HR8216doc 2018HFrequencyFLOAT32ABCDHzRead
HR8218doc 201AHTotal Active PowerFLOAT32ABCDWRead
HR8220doc 201CHPhase A Active PowerFLOAT32ABCDWRead
HR8222doc 201EHPhase B Active PowerFLOAT32ABCDWRead
HR8224doc 2020HPhase C Active PowerFLOAT32ABCDWRead
HR8226doc 2022HTotal Apparent PowerFLOAT32ABCDVARead
HR8228doc 2024HPhase A Apparent PowerFLOAT32ABCDVARead
HR8230doc 2026HPhase B Apparent PowerFLOAT32ABCDVARead
HR8232doc 2028HPhase C Apparent PowerFLOAT32ABCDVARead
HR8234doc 202AHTotal Reactive PowerFLOAT32ABCDvarRead
HR8236doc 202CHPhase A Reactive PowerFLOAT32ABCDvarRead
HR8238doc 202EHPhase B Reactive PowerFLOAT32ABCDvarRead
HR8240doc 2030HPhase C Reactive PowerFLOAT32ABCDvarRead
HR8242doc 2032HPower FactorFLOAT32ABCDRead
HR8244doc 2034HPF phase AFLOAT32ABCDRead
HR8246doc 2036HPF phase BFLOAT32ABCDRead
HR8248doc 2038HPF phase CFLOAT32ABCDRead
HR8250doc 203AHPhase Angle of V1 to V1FLOAT32ABCD°Read
HR8252doc 203CHPhase Angle of V2 to V1FLOAT32ABCD°Read
HR8254doc 203EHPhase Angle of V3 to V1FLOAT32ABCD°Read
HR8256doc 2040HPhase Angle of I1 to V1FLOAT32ABCD°Read
HR8258doc 2042HPhase Angle of I2 to V1FLOAT32ABCD°Read
HR8260doc 2044HPhase Angle of I3 to V1FLOAT32ABCD°Read
HR8262doc 2046HTotal Active Energy ExportedINT32ABCDWhRead/write
HR8264doc 2048HActive Energy Exported in Phase AINT32ABCDWhRead/write
HR8266doc 204AHActive Energy Exported in Phase BINT32ABCDWhRead/write
HR8268doc 204CHActive Energy Exported in Phase CINT32ABCDWhRead/write
HR8270doc 204EHTotal Active Energy ImportedINT32ABCDWhRead/write
HR8272doc 2050HActive Energy Imported in Phase AINT32ABCDWhRead/write
HR8274doc 2052HActive Energy Imported in Phase BINT32ABCDWhRead/write
HR8276doc 2054HActive Energy Imported in Phase CINT32ABCDWhRead/write
HR8278doc 2056HTotal Apparent Energy ExportedINT32ABCDVAhRead/write
HR8280doc 2058HApparent Energy Exported in Phase AINT32ABCDVAhRead/write
HR8282doc 205AHApparent Energy Exported in Phase BINT32ABCDVAhRead/write
HR8284doc 205CHApparent Energy Exported in Phase CINT32ABCDVAhRead/write
HR8286doc 205EHTotal Apparent Energy ImportedINT32ABCDVAhRead/write
HR8288doc 2060HApparent Energy Imported in Phase AINT32ABCDVAhRead/write
HR8290doc 2062HApparent Energy Imported in Phase BINT32ABCDVAhRead/write
HR8292doc 2064HApparent Energy Imported in Phase CINT32ABCDVAhRead/write
HR8294doc 2066HTotal Reactive Imported Q1INT32ABCDvarhRead/write
HR8296doc 2068HReactive Imported Q1 Phase AINT32ABCDvarhRead/write
HR8298doc 206AHReactive Imported Q1 Phase BINT32ABCDvarhRead/write
HR8300doc 206CHReactive Imported Q1 Phase CINT32ABCDvarhRead/write
HR8302doc 206EHTotal Reactive Imported Q2INT32ABCDvarhRead/write
HR8304doc 2070HReactive Imported Q2 Phase AINT32ABCDvarhRead/write
HR8306doc 2072HReactive Imported Q2 Phase BINT32ABCDvarhRead/write
HR8308doc 2074HReactive Imported Q2 Phase CINT32ABCDvarhRead/write
HR8310doc 2076HTotal Reactive Energy Exported Q3INT32ABCDvarhRead/write
HR8312doc 2078HReactive Energy Exported Q3 Phase AINT32ABCDvarhRead/write
HR8314doc 207AHReactive Energy Exported Q3 Phase BINT32ABCDvarhRead/write
HR8316doc 207CHReactive Energy Exported Q3 Phase CINT32ABCDvarhRead/write
HR8318doc 207EHTotal Reactive Energy Exported Q4INT32ABCDvarhRead/write
HR8320doc 2080HReactive Energy Exported Q4 Phase AINT32ABCDvarhRead/write
HR8322doc 2082HReactive Energy Exported Q4 Phase BINT32ABCDvarhRead/write
HR8324doc 2084HReactive Energy Exported Q4 Phase CINT32ABCDvarhRead/write
HR12288doc 3000HDual-source enableUINT16Read/write0 = Disable; 1 = Enable
HR12289doc 3001HDual-source energy sourceUINT16Read/write0 = From Grid; 1 = From alternative source
HR12544doc 3100HClear dual-source energyWrite 0x0A to execute.UINT16Write
HR12545doc 3101HClear Dual-source change logWrite 0x0A to execute.UINT16Write
HR12800doc 3200HGrid Active EnergyUINT32ABCDWhRead/write
HR12802doc 3202HAlternate Active EnergyUINT32ABCDWhRead/write
HR12804doc 3204HGrid Reactive EnergyUINT32ABCDvarhRead/write
HR12806doc 3206HAlternate Reactive EnergyUINT32ABCDvarhRead/write
HR12808doc 3208HGrid Apparent EnergyUINT32ABCDVAhRead/write
HR12810doc 320AHAlternate Apparent EnergyUINT32ABCDVAhRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Accuenergy AcuRev 1310 series DIN-rail power meter

What Modbus registers does the Accuenergy AcuRev 1310 series DIN-rail power meter have?

This map lists 150 registers: 150 holding registers. 96 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Accuenergy AcuRev 1310 series DIN-rail power meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The workbook states that its addresses are 0-based Modbus PDU addresses and prints each as hex and decimal (2000H = 8192). Request the decimal value as given.

What byte order does the Accuenergy AcuRev 1310 series DIN-rail power meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Accuenergy AcuRev 1310 series DIN-rail power meter?

Start with HR 8194 Phase A Current (Phase A current); HR 8202 Phase A Voltage (Phase A voltage); HR 8216 Frequency (Frequency); HR 8218 Total Active Power (Total active power); HR 8242 Power Factor (Total power factor); HR 8270 Total Active Energy Imported (Total active energy imported); HR 8262 Total Active Energy Exported (Total active energy exported).

How do I enable Modbus control of the Accuenergy AcuRev 1310 series DIN-rail power meter?

Set the Modbus address and serial (or network) parameters on the meter; the workbook does not list the factory communication defaults.

Where is the official Accuenergy AcuRev 1310 series DIN-rail power meter Modbus documentation?

The source is AcuRev 1310 Modbus Register Map (XLSX) (Revision 1.1), revision 2026-10-27, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-1310-Modbus-Map.xlsx.

More Accuenergy Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: AcuRev 1310 Modbus Register Map (XLSX) · Revision 1.1 · rev. 2026-10-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.