Power meter · Modbus register map
Circutor CVM-C5 Modbus register map
Updated 17 November 2026
The CVM-C5 is a compact panel power analyzer from Circutor with an RS-485 Modbus RTU port. Every measured value is a 32-bit integer in two registers with fixed scaling (V x10, mA, Hz x10, % x10), read with function 03 or 04, each with instantaneous, maximum and minimum copies. This map covers voltages, currents, reactive and apparent power, frequency, THD, demand and the two-tariff energy counters plus the tariff selector.
This page lists 108 Modbus registers for the Circutor CVM-C5 — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- CVM-C5
- Equipment type
- Power meter
- Registers
- 108 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485
- Source document
- CVM-C5 Instruction Manual · M026B01-03
Integration notes: Circutor CVM-C5
Read with function 04 from 0x00 in two-register steps (maximum 20 variables / 40 registers per frame). Values are 32-bit integers, high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | L1 phase-neutral voltage | UINT32 ABCD | L1 phase-neutral voltage (V x10) | Read |
| IR 2 | L1 current | UINT32 ABCD | L1 current (mA) | Read |
| IR 66 | Three-phase apparent power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 40 | Frequency | UINT32 ABCD | Frequency (Hz x10) | Read |
| IR 60 | Active energy tariff 1 | UINT32 ABCD | Active energy tariff 1 | Read |
| IR 108 | Active energy tariff 2 | UINT32 ABCD | Active energy tariff 2 | Read |
Enable Modbus control & writes
Modbus RTU is the only protocol. Set peripheral number, speed, parity and stop bits in the setup menu (sections 4.6.18-4.6.23).
Byte order & addressing
- The active tariff is selected by writing 0 or 1 to register 0x1388 with function 10.
- Each measurement has maximum and minimum copies at separate addresses.
Network setup
- Default: peripheral number 1, 9600 baud, no parity, 8 data bits, 1 stop bit.
- Speeds 1200-19200 baud; data bits fixed at 8.
Watch out for
- Limit each read to 20 variables (40 registers).
Circutor CVM-C5 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 00-01 | L1 phase-neutral voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 2doc 02-03 | L1 current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 10doc 0A-0B | L2 phase-neutral voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 12doc 0C-0D | L2 current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 20doc 14-15 | L3 phase-neutral voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 22doc 16-17 | L3 current | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 32doc 20-21 | Three-phase inductive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 34doc 22-23 | Three-phase capacitive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 40doc 28-29 | Frequency | Instantaneous value. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 42doc 2A-2B | L1-L2 voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 44doc 2C-2D | L2-L3 voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 46doc 2E-2F | L3-L1 voltage | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 48doc 30-31 | THD voltage L1 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 50doc 32-33 | THD voltage L2 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 52doc 34-35 | THD voltage L3 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 54doc 36-37 | THD current L1 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 56doc 38-39 | THD current L2 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 58doc 3A-3B | THD current L3 | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 60doc 3C-3D | Active energy tariff 1 | UINT32 | ABCD | Wh | Read | |||
| IR | 62doc 3E-3F | Inductive reactive energy tariff 1 | UINT32 | ABCD | varh | Read | |||
| IR | 64doc 40-41 | Capacitive reactive energy tariff 1 | UINT32 | ABCD | varh | Read | |||
| IR | 66doc 42-43 | Three-phase apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 70doc 46-47 | Three-phase current (average) | Instantaneous value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 82doc 52-53 | Maximum demand I2 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 84doc 54-55 | Maximum demand I3 | Present maximum-demand value. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 86doc 56-57 | Phase-phase voltage (average) | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 88doc 58-59 | Phase-neutral voltage (average) | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 96doc 60-61 | Generated active energy tariff 1 | UINT32 | ABCD | Wh | Read | |||
| IR | 98doc 62-63 | Generated inductive reactive energy tariff 1 | UINT32 | ABCD | varh | Read | |||
| IR | 100doc 64-65 | Generated capacitive reactive energy tariff 1 | UINT32 | ABCD | varh | Read | |||
| IR | 108doc 6C-6D | Active energy tariff 2 | UINT32 | ABCD | Wh | Read | |||
| IR | 110doc 6E-6F | Inductive reactive energy tariff 2 | UINT32 | ABCD | varh | Read | |||
| IR | 112doc 70-71 | Capacitive reactive energy tariff 2 | UINT32 | ABCD | varh | Read | |||
| IR | 116doc 74-75 | Generated active energy tariff 2 | UINT32 | ABCD | Wh | Read | |||
| IR | 118doc 76-77 | Generated inductive reactive energy tariff 2 | UINT32 | ABCD | varh | Read | |||
| IR | 120doc 78-79 | Generated capacitive reactive energy tariff 2 | UINT32 | ABCD | varh | Read | |||
| IR | 132doc 84-85 | L1 phase-neutral voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 134doc 86-87 | L1 current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 142doc 8E-8F | L2 phase-neutral voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 144doc 90-91 | L2 current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 152doc 98-99 | L3 phase-neutral voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 154doc 9A-9B | L3 current (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 164doc A4-A5 | Three-phase inductive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 166doc A6-A7 | Three-phase capacitive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 172doc AC-AD | Frequency (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 174doc AE-AF | L1-L2 voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 176doc B0-B1 | L2-L3 voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 178doc B2-B3 | L3-L1 voltage (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 180doc B4-B5 | THD voltage L1 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 182doc B6-B7 | THD voltage L2 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 184doc B8-B9 | THD voltage L3 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 186doc BA-BB | THD current L1 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 188doc BC-BD | THD current L2 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 190doc BE-BF | THD current L3 (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 198doc C6-C7 | Three-phase apparent power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 202doc CA-CB | Three-phase current (average) (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 218doc DA-DB | Phase-phase voltage (average) (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 220doc DC-DD | Phase-neutral voltage (average) (max) | Maximum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 256doc 100-101 | L1 phase-neutral voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 258doc 102-103 | L1 current (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 266doc 10A-10B | L2 phase-neutral voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 268doc 10C-10D | L2 current (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 276doc 114-115 | L3 phase-neutral voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 278doc 116-117 | L3 current (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 288doc 120-121 | Three-phase inductive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 290doc 122-123 | Three-phase capacitive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 296doc 128-129 | Frequency (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 298doc 12A-12B | L1-L2 voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 300doc 12C-12D | L2-L3 voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 302doc 12E-12F | L3-L1 voltage (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 304doc 130-131 | THD voltage L1 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 306doc 132-133 | THD voltage L2 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 308doc 134-135 | THD voltage L3 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 310doc 136-137 | THD current L1 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 312doc 138-139 | THD current L2 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 314doc 13A-13B | THD current L3 (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 322doc 142-143 | Three-phase apparent power (min) | Minimum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 326doc 146-147 | Three-phase current (average) (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 342doc 156-157 | Phase-phase voltage (average) (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 344doc 158-159 | Phase-neutral voltage (average) (min) | Minimum recorded since last reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 380doc 17C-17D | L1 inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 382doc 17E-17F | L2 inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 384doc 180-181 | L3 inductive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 386doc 182-183 | L1 capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 388doc 184-185 | L2 capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 390doc 186-187 | L3 capacitive reactive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 392doc 188-189 | L1 apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 394doc 18A-18B | L2 apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 396doc 18C-18D | L3 apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 398doc 18E-18F | L1 inductive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 400doc 190-191 | L2 inductive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 402doc 192-193 | L3 inductive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 404doc 194-195 | L1 capacitive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 406doc 196-197 | L2 capacitive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 408doc 198-199 | L3 capacitive reactive power (max) | Maximum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 410doc 19A-19B | L1 apparent power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 412doc 19C-19D | L2 apparent power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 414doc 19E-19F | L3 apparent power (max) | Maximum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 416doc 1A0-1A1 | L1 inductive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 418doc 1A2-1A3 | L2 inductive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 420doc 1A4-1A5 | L3 inductive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 422doc 1A6-1A7 | L1 capacitive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 424doc 1A8-1A9 | L2 capacitive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 426doc 1AA-1AB | L3 capacitive reactive power (min) | Minimum recorded since last reset. | UINT32 | ABCD | var | Read | ||
| IR | 428doc 1AC-1AD | L1 apparent power (min) | Minimum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 430doc 1AE-1AF | L2 apparent power (min) | Minimum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| IR | 432doc 1B0-1B1 | L3 apparent power (min) | Minimum recorded since last reset. | UINT32 | ABCD | VA | Read | ||
| HR | 5000doc 1388 | Active tariff | Write with function 10, read with function 04. | UINT16 | Read/write | 0 = Tariff T1; 1 = Tariff T2 |
Notes on this map
- Word order: the manual's example response gives register 1 = 0000 and register 2 = 084D for 212.5 V, so 32-bit values are high word first (ABCD). The manual states all parameters are 32 bits long.
- Left out: active power, signed reactive power, power factor and cos phi (per phase and three-phase), because the manual does not state whether those Modbus values are signed.
- Left out: the 'Maximum demand' register at 44-45, whose unit is printed as W/VA/mA, so its unit depends on the selected demand variable.
- Left out: apparent energy (consumed and generated) because the units column prints kVAh for one and VAh for the other; CO2, cost and hours per tariff.
- Energy counters are per tariff only (T1 and T2); there is no total register.
- Frequency is scaled x10 on this model (not x100 as on the CVM-C10).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor CVM-C5
What Modbus registers does the Circutor CVM-C5 have?
This map lists 108 registers: 107 input registers, 1 holding register. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor CVM-C5 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All Modbus addresses in the manual are hexadecimal wire addresses. The manual's example reads L1-L2 voltage at initial register 2A and receives 0000 084D = 212.5 V, which matches the table entry 2A-2B with V x10 scaling.
What byte order does the Circutor CVM-C5 use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor CVM-C5?
Start with IR 0 L1 phase-neutral voltage (L1 phase-neutral voltage (V x10)); IR 2 L1 current (L1 current (mA)); IR 66 Three-phase apparent power (Three-phase apparent power); IR 40 Frequency (Frequency (Hz x10)); IR 60 Active energy tariff 1 (Active energy tariff 1); IR 108 Active energy tariff 2 (Active energy tariff 2).
How do I enable Modbus control of the Circutor CVM-C5?
Modbus RTU is the only protocol. Set peripheral number, speed, parity and stop bits in the setup menu (sections 4.6.18-4.6.23).
Where is the official Circutor CVM-C5 Modbus documentation?
The source is CVM-C5 Instruction Manual (M026B01-03), published free by Circutor at https://docs.circutor.com/docs/M026B01-03.pdf.
More Circutor Modbus register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth - Power meter (earth leakage breaker with reclosing and metering)
Circutor RECmax-CVM
Circutor RECmax-CVM earth-leakage circuit breaker with automatic reclosing and built-in analyzer, manual M175B01-03-22A.
Other power & energy meters register maps
- Power meter (power quality analyzer)
E-Mon (Honeywell) PowerSmart+ Advanced power quality meter
Honeywell E-Mon PowerSmart+ Advanced power quality meter, per Modbus reference guide BG0545 Rev. A1 (Jul 2013).
Also known as: E-Mon PowerSmart+ Advanced, PowerSmart Plus Advanced, Honeywell PowerSmart+, BG0545 - Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Power meter (power quality meter)
GE Multilin Multilin PQMII power quality meter
Multilin PQMII per instruction manual GEK-113532 (communications guide chapter).
Also known as: PQM II, GE Multilin PQMII, PQM2 - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302
All power & energy meters Modbus register maps →
Source: CVM-C5 Instruction Manual · M026B01-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.