Power meter (power factor regulator with network analyzer) · Modbus register map
Circutor Computer SMART III Modbus register map
Updated 17 November 2026
The Computer SMART III is Circutor's power factor (capacitor bank) regulator with a built-in three-phase network analyzer and an RS-485 Modbus RTU port. Measurements are 32-bit integers in register pairs read with function 04. This map covers currents, reactive power split into consumed/generated and inductive/capacitive parts, apparent power, frequency, THD, energy counters and the quadrant sign registers.
This page lists 49 Modbus registers for the Circutor Computer SMART III — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- Computer SMART III
- Registers
- 49 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Computer SMART III 6, Computer SMART III 12, SMART III
- Source document
- Computer SMART III Instruction Manual · M015B01-03-25B
Integration notes: Circutor Computer SMART III
Read with function 04 in register pairs (high word first). Use the kW and kvar sign registers to tell consumed from generated and inductive from capacitive operation.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 80 | Three-phase current | UINT32 ABCD | Three-phase current (mA) | Read |
| IR 90 | Three-phase apparent power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 100 | Three-phase kW sign | INT32 ABCD | Three-phase kW sign | Read |
| IR 102 | Three-phase kvar sign | INT32 ABCD | Three-phase kvar sign | Read |
| IR 104 | Frequency | UINT32 ABCD | Frequency (Hz/10) | Read |
| IR 136 | Active energy consumed kWh | UINT32 ABCD | Active energy consumed kWh | Read |
Enable Modbus control & writes
Modbus RTU is available on the RS-485 port; peripheral number and serial settings are set in the setup menu.
Byte order & addressing
- Frames of more than 80 bytes are not accepted (sent or received); size reads so the reply stays within 80 bytes.
- Energy is split into a whole-unit register (kWh) and a remainder register (Wh).
Network setup
- Defaults: peripheral number 1, 19200 baud, no parity, 8 data bits, 1 stop bit; 9600 or 19200 can be chosen in the setup menu.
Watch out for
- Do not apply the CVM-series x10 voltage scaling blindly; this manual's voltage scaling is inconsistent, so verify voltages against the display.
Circutor Computer SMART III Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2doc 02-03 | L1 Current | Max at 202-203, min at 302-303. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 6doc 06-07 | L1 Inductive Reactive Power | Max at 206-207, min at 306-307. | UINT32 | ABCD | var | Read | ||
| IR | 8doc 08-09 | L1 Capacitive Reactive Power | Max at 208-209, min at 308-309. | UINT32 | ABCD | var | Read | ||
| IR | 12doc 0C-0D | L1 Apparent Power | Max at 20C-20D, min at 30C-30D. | UINT32 | ABCD | VA | Read | ||
| IR | 14doc 0E-0F | L1 Reactive Power Consumed | Max at 20E-20F, min at 30E-30F. | UINT32 | ABCD | var | Read | ||
| IR | 16doc 10-11 | L1 Reactive Power Generated | Max at 210-211, min at 310-311. | UINT32 | ABCD | var | Read | ||
| IR | 22doc 16-17 | L1 kW sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 24doc 18-19 | L1 kvar sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 28doc 1C-1D | L2 Current | Max at 21C-21D, min at 31C-31D. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 32doc 20-21 | L2 Inductive Reactive Power | Max at 220-221, min at 320-321. | UINT32 | ABCD | var | Read | ||
| IR | 34doc 22-23 | L2 Capacitive Reactive Power | Max at 222-223, min at 322-323. | UINT32 | ABCD | var | Read | ||
| IR | 38doc 26-27 | L2 Apparent Power | Max at 226-227, min at 326-327. | UINT32 | ABCD | VA | Read | ||
| IR | 40doc 28-29 | L2 Reactive Power Consumed | Max at 228-229, min at 328-329. | UINT32 | ABCD | var | Read | ||
| IR | 42doc 2A-2B | L2 Reactive Power Generated | Max at 22A-22B, min at 32A-32B. | UINT32 | ABCD | var | Read | ||
| IR | 48doc 30-31 | L2 kW sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 50doc 32-33 | L2 kvar sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 54doc 36-37 | L3 Current | Max at 236-237, min at 336-337. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 58doc 3A-3B | L3 Inductive Reactive Power | Max at 23A-23B, min at 33A-33B. | UINT32 | ABCD | var | Read | ||
| IR | 60doc 3C-3D | L3 Capacitive Reactive Power | Max at 23C-23D, min at 33C-33D. | UINT32 | ABCD | var | Read | ||
| IR | 64doc 40-41 | L3 Apparent Power | Max at 240-241, min at 340-341. | UINT32 | ABCD | VA | Read | ||
| IR | 66doc 42-43 | L3 Reactive Power Consumed | Max at 242-243, min at 342-343. | UINT32 | ABCD | var | Read | ||
| IR | 68doc 44-45 | L3 Reactive Power Generated | Max at 244-245, min at 344-345. | UINT32 | ABCD | var | Read | ||
| IR | 74doc 4A-4B | L3 kW sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 76doc 4C-4D | L3 kvar sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 80doc 50-51 | Three-phase current | Max at 250-251, min at 350-351. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 84doc 54-55 | Three-phase inductive power | Max at 254-255, min at 354-355. | UINT32 | ABCD | var | Read | ||
| IR | 86doc 56-57 | Three-phase capacitive power | Max at 256-257, min at 356-357. | UINT32 | ABCD | var | Read | ||
| IR | 90doc 5A-5B | Three-phase apparent power | Max at 25A-25B, min at 35A-35B. | UINT32 | ABCD | VA | Read | ||
| IR | 100doc 64-65 | Three-phase kW sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 102doc 66-67 | Three-phase kvar sign | +1 or -1; gives the quadrant together with PF/cos phi. | INT32 | ABCD | Read | 1 = +1; -1 = -1 | ||
| IR | 104doc 68-69 | Frequency | Max at 268-269, min at 368-369. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 112doc 70-71 | Neutral Current | Max at 270-271, min at 370-371. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 114doc 72-73 | Leakage Current | Max at 272-273, min at 372-373. | UINT32 | ABCD | × 0.001 | A | Read | |
| IR | 136doc 88-89 | Active energy consumed kWh | UINT32 | ABCD | kWh | Read | |||
| IR | 138doc 8A-8B | Active energy consumed Wh | UINT32 | ABCD | Wh | Read | |||
| IR | 140doc 8C-8D | Inductive energy consumed kvarLh | UINT32 | ABCD | kvarh | Read | |||
| IR | 142doc 8E-8F | Inductive energy consumed varLh | UINT32 | ABCD | varh | Read | |||
| IR | 144doc 90-91 | Capacitive energy consumed kvarCh | UINT32 | ABCD | kvarh | Read | |||
| IR | 146doc 92-93 | Capacitive energy consumed varCh | UINT32 | ABCD | varh | Read | |||
| IR | 148doc 94-95 | Apparent energy consumed kVAh | UINT32 | ABCD | kVAh | Read | |||
| IR | 150doc 96-97 | Apparent energy consumed VAh | UINT32 | ABCD | VAh | Read | |||
| IR | 152doc 98-99 | Active energy generated kWh | UINT32 | ABCD | kWh | Read | |||
| IR | 154doc 9A-9B | Active energy generated Wh | UINT32 | ABCD | Wh | Read | |||
| IR | 156doc 9C-9D | Inductive energy generated kvarLh | UINT32 | ABCD | kvarh | Read | |||
| IR | 158doc 9E-9F | Inductive energy generated varLh | UINT32 | ABCD | varh | Read | |||
| IR | 160doc A0-A1 | Capacitive energy generated kvarCh | UINT32 | ABCD | kvarh | Read | |||
| IR | 162doc A2-A3 | Capacitive energy generated varCh | UINT32 | ABCD | varh | Read | |||
| IR | 164doc A4-A5 | Apparent energy generated kVAh | UINT32 | ABCD | kVAh | Read | |||
| IR | 166doc A6-A7 | Apparent energy generated VAh | UINT32 | ABCD | VAh | Read |
Notes on this map
- Word order: the manual's function 04 example returns 0000 then 084D (high word first), so 32-bit values are ABCD.
- Left out: all voltage registers. The table gives the unit as V/100 but the worked example decodes the same register as V x10 (212.5 V), so the scaling is contradictory.
- Left out: active power, signed reactive power, power factor and cos phi. The manual pairs PF/cos phi with separate kW/kvar sign registers but does not state the type or scaling of the PF values or whether the power values are signed.
- Left out: THD (unit printed as % with no scaling factor), temperature (signedness not stated), harmonics, relay/alarm/output words and the configuration registers.
- The kW/kvar sign registers are typed INT32 because the documented values are +1 and -1.
- Communication defaults come from the programming-variables table (Table 17): peripheral number 1, speed code 1 = 19200, parity 0 = none, 8 data bits, 1 stop bit. Frames longer than 80 bytes are rejected.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor Computer SMART III
What Modbus registers does the Circutor Computer SMART III have?
This map lists 49 registers: 49 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor Computer SMART III Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses in the memory map are hexadecimal wire addresses; the manual's query example reads two registers from 0000 for L1 voltage.
What byte order does the Circutor Computer SMART III use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor Computer SMART III?
Start with IR 80 Three-phase current (Three-phase current (mA)); IR 90 Three-phase apparent power (Three-phase apparent power); IR 100 Three-phase kW sign (Three-phase kW sign); IR 102 Three-phase kvar sign (Three-phase kvar sign); IR 104 Frequency (Frequency (Hz/10)); IR 136 Active energy consumed kWh (Active energy consumed kWh).
How do I enable Modbus control of the Circutor Computer SMART III?
Modbus RTU is available on the RS-485 port; peripheral number and serial settings are set in the setup menu.
Where is the official Circutor Computer SMART III Modbus documentation?
The source is Computer SMART III Instruction Manual (M015B01-03-25B), published free by Circutor at https://docs.circutor.com/docs/M015B01-03.pdf.
More Circutor Modbus register maps
- Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth - Power meter (earth leakage breaker with reclosing and metering)
Circutor RECmax-CVM
Circutor RECmax-CVM earth-leakage circuit breaker with automatic reclosing and built-in analyzer, manual M175B01-03-22A.
Other power & energy meters register maps
- Power meter
Crompton Instruments Integra 1530 / 1560 / 1580
Crompton Instruments (Tyco Electronics) Integra 1530, 1560 and 1580 panel meters fitted with the RS485 Modbus RTU option, per Integra Comms Issue 1 (Jan 2006).
Also known as: Integra 1530, Integra 1560, Integra 1580 - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)
Eltako DSZ15DZMOD-3x80A MID bidirectional three-phase DIN-rail meter (art. no. 28380516), per Modbus-RTU protocol specification V1.6.
Also known as: DSZ15DZMOD, DSZ15DZMOD-3x80A, DSZ15DZMOD-3x80A MID, 28380516 - Energy meter
Finder 7M.38 three-phase energy meter (Modbus RS485)
Finder 7M.38 three-phase meters with serial RS485 communication (7M.38.8.400.XXXX serial versions); the 7M.24 single-phase meter in the same document is not covered.
Also known as: 7M.38, 7M38, 7M.38.8.400.0212, 7M3884000212, Finder 7M38 Modbus - Power meter
IME Nemo 96HDe multifunction meter (MF96E06)
IME Nemo 96HDe panel meter MF96E06 with RS-485, per protocol PR145.
Also known as: MF96E06, Nemo 96HDe - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy
All power & energy meters Modbus register maps →
Source: Computer SMART III Instruction Manual · M015B01-03-25B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.