Power meter (power factor regulator with network analyzer) · Modbus register map

Circutor Computer SMART III Modbus register map

Updated 17 November 2026

Short answer

The Computer SMART III is Circutor's power factor (capacitor bank) regulator with a built-in three-phase network analyzer and an RS-485 Modbus RTU port. Measurements are 32-bit integers in register pairs read with function 04. This map covers currents, reactive power split into consumed/generated and inductive/capacitive parts, apparent power, frequency, THD, energy counters and the quadrant sign registers.

This page lists 49 Modbus registers for the Circutor Computer SMART III — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.

Manufacturer
Circutor
Model
Computer SMART III
Equipment type
Power meter (power factor regulator with network analyzer)
Registers
49 (0 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
Computer SMART III 6, Computer SMART III 12, SMART III
Source document
Computer SMART III Instruction Manual · M015B01-03-25B
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Circutor Computer SMART III

Integration in brief

Read with function 04 in register pairs (high word first). Use the kW and kvar sign registers to tell consumed from generated and inductive from capacitive operation.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 80Three-phase currentUINT32 ABCDThree-phase current (mA)Read
IR 90Three-phase apparent powerUINT32 ABCDThree-phase apparent powerRead
IR 100Three-phase kW signINT32 ABCDThree-phase kW signRead
IR 102Three-phase kvar signINT32 ABCDThree-phase kvar signRead
IR 104FrequencyUINT32 ABCDFrequency (Hz/10)Read
IR 136Active energy consumed kWhUINT32 ABCDActive energy consumed kWhRead

Enable Modbus control & writes

Modbus RTU is available on the RS-485 port; peripheral number and serial settings are set in the setup menu.

Byte order & addressing

Network setup

Watch out for

Circutor Computer SMART III Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
Circutor Computer SMART III Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2doc 02-03L1 CurrentMax at 202-203, min at 302-303.UINT32ABCD× 0.001ARead
IR6doc 06-07L1 Inductive Reactive PowerMax at 206-207, min at 306-307.UINT32ABCDvarRead
IR8doc 08-09L1 Capacitive Reactive PowerMax at 208-209, min at 308-309.UINT32ABCDvarRead
IR12doc 0C-0DL1 Apparent PowerMax at 20C-20D, min at 30C-30D.UINT32ABCDVARead
IR14doc 0E-0FL1 Reactive Power ConsumedMax at 20E-20F, min at 30E-30F.UINT32ABCDvarRead
IR16doc 10-11L1 Reactive Power GeneratedMax at 210-211, min at 310-311.UINT32ABCDvarRead
IR22doc 16-17L1 kW sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR24doc 18-19L1 kvar sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR28doc 1C-1DL2 CurrentMax at 21C-21D, min at 31C-31D.UINT32ABCD× 0.001ARead
IR32doc 20-21L2 Inductive Reactive PowerMax at 220-221, min at 320-321.UINT32ABCDvarRead
IR34doc 22-23L2 Capacitive Reactive PowerMax at 222-223, min at 322-323.UINT32ABCDvarRead
IR38doc 26-27L2 Apparent PowerMax at 226-227, min at 326-327.UINT32ABCDVARead
IR40doc 28-29L2 Reactive Power ConsumedMax at 228-229, min at 328-329.UINT32ABCDvarRead
IR42doc 2A-2BL2 Reactive Power GeneratedMax at 22A-22B, min at 32A-32B.UINT32ABCDvarRead
IR48doc 30-31L2 kW sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR50doc 32-33L2 kvar sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR54doc 36-37L3 CurrentMax at 236-237, min at 336-337.UINT32ABCD× 0.001ARead
IR58doc 3A-3BL3 Inductive Reactive PowerMax at 23A-23B, min at 33A-33B.UINT32ABCDvarRead
IR60doc 3C-3DL3 Capacitive Reactive PowerMax at 23C-23D, min at 33C-33D.UINT32ABCDvarRead
IR64doc 40-41L3 Apparent PowerMax at 240-241, min at 340-341.UINT32ABCDVARead
IR66doc 42-43L3 Reactive Power ConsumedMax at 242-243, min at 342-343.UINT32ABCDvarRead
IR68doc 44-45L3 Reactive Power GeneratedMax at 244-245, min at 344-345.UINT32ABCDvarRead
IR74doc 4A-4BL3 kW sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR76doc 4C-4DL3 kvar sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR80doc 50-51Three-phase currentMax at 250-251, min at 350-351.UINT32ABCD× 0.001ARead
IR84doc 54-55Three-phase inductive powerMax at 254-255, min at 354-355.UINT32ABCDvarRead
IR86doc 56-57Three-phase capacitive powerMax at 256-257, min at 356-357.UINT32ABCDvarRead
IR90doc 5A-5BThree-phase apparent powerMax at 25A-25B, min at 35A-35B.UINT32ABCDVARead
IR100doc 64-65Three-phase kW sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR102doc 66-67Three-phase kvar sign+1 or -1; gives the quadrant together with PF/cos phi.INT32ABCDRead1 = +1; -1 = -1
IR104doc 68-69FrequencyMax at 268-269, min at 368-369.UINT32ABCD× 0.1HzRead
IR112doc 70-71Neutral CurrentMax at 270-271, min at 370-371.UINT32ABCD× 0.001ARead
IR114doc 72-73Leakage CurrentMax at 272-273, min at 372-373.UINT32ABCD× 0.001ARead
IR136doc 88-89Active energy consumed kWhUINT32ABCDkWhRead
IR138doc 8A-8BActive energy consumed WhUINT32ABCDWhRead
IR140doc 8C-8DInductive energy consumed kvarLhUINT32ABCDkvarhRead
IR142doc 8E-8FInductive energy consumed varLhUINT32ABCDvarhRead
IR144doc 90-91Capacitive energy consumed kvarChUINT32ABCDkvarhRead
IR146doc 92-93Capacitive energy consumed varChUINT32ABCDvarhRead
IR148doc 94-95Apparent energy consumed kVAhUINT32ABCDkVAhRead
IR150doc 96-97Apparent energy consumed VAhUINT32ABCDVAhRead
IR152doc 98-99Active energy generated kWhUINT32ABCDkWhRead
IR154doc 9A-9BActive energy generated WhUINT32ABCDWhRead
IR156doc 9C-9DInductive energy generated kvarLhUINT32ABCDkvarhRead
IR158doc 9E-9FInductive energy generated varLhUINT32ABCDvarhRead
IR160doc A0-A1Capacitive energy generated kvarChUINT32ABCDkvarhRead
IR162doc A2-A3Capacitive energy generated varChUINT32ABCDvarhRead
IR164doc A4-A5Apparent energy generated kVAhUINT32ABCDkVAhRead
IR166doc A6-A7Apparent energy generated VAhUINT32ABCDVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Circutor Computer SMART III

What Modbus registers does the Circutor Computer SMART III have?

This map lists 49 registers: 49 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Circutor Computer SMART III Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses in the memory map are hexadecimal wire addresses; the manual's query example reads two registers from 0000 for L1 voltage.

What byte order does the Circutor Computer SMART III use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Circutor Computer SMART III?

Start with IR 80 Three-phase current (Three-phase current (mA)); IR 90 Three-phase apparent power (Three-phase apparent power); IR 100 Three-phase kW sign (Three-phase kW sign); IR 102 Three-phase kvar sign (Three-phase kvar sign); IR 104 Frequency (Frequency (Hz/10)); IR 136 Active energy consumed kWh (Active energy consumed kWh).

How do I enable Modbus control of the Circutor Computer SMART III?

Modbus RTU is available on the RS-485 port; peripheral number and serial settings are set in the setup menu.

Where is the official Circutor Computer SMART III Modbus documentation?

The source is Computer SMART III Instruction Manual (M015B01-03-25B), published free by Circutor at https://docs.circutor.com/docs/M015B01-03.pdf.

More Circutor Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Computer SMART III Instruction Manual · M015B01-03-25B. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.