Power meter (earth leakage breaker with reclosing and metering) · Modbus register map
Circutor RECmax-CVM Modbus register map
Updated 19 November 2026
The RECmax-CVM combines an earth-leakage breaker that recloses on its own with a three-phase power analyzer. Its RS-485 port speaks Modbus RTU. Measurements are 32-bit integers in register pairs with fixed scaling, the leakage and reclosing counters are single registers, and setup lives in blocks around 0x2710 and 0xC360. This map covers voltages, currents, reactive and apparent power, THD, demand, energies, leakage data, status words, setup and reset commands; transformation ratios are left out.
This page lists 100 Modbus registers for the Circutor RECmax-CVM — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Circutor’s own free documentation (linked below) and checked against it.
- Manufacturer
- Circutor
- Model
- RECmax-CVM
- Registers
- 100 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
Integration notes: Circutor RECmax-CVM
Poll the block from 0x0000 with function 04 (at most 20 variables, 40 registers, per frame), then read the leakage registers C392-C399. All 32-bit values are high word first with fixed scale.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Phase voltage L1 | UINT32 ABCD | L1 phase voltage (V x10) | Read |
| IR 2 | Current L1 | UINT32 ABCD | L1 current (mA) | Read |
| IR 66 | Three-phase apparent power | UINT32 ABCD | Three-phase apparent power | Read |
| IR 40 | Frequency | UINT32 ABCD | Frequency (Hz x10) | Read |
| IR 60 | Consumed active energy III | UINT32 ABCD | Consumed active energy | Read |
| IR 50071 | Leakage current | UINT16 | Earth leakage current (mA) | Read |
| IR 50066 | Total reclosing operations | UINT16 | Total reclosing operations | Read |
| IR 50064 | Relay output status | BITMAP16 | Relay status | Read |
Enable Modbus control & writes
Modbus RTU is the standard protocol (Protocol register 0x2742 = 0). Set the peripheral number from the front panel (hold PROG for more than 3 s) or register 0x2743, and speed and framing with 0x2744-0x2747; reset the device for Modbus setup changes to apply.
Byte order & addressing
- A frame may carry at most 20 variables (40 registers).
- Energies come both as a single Wh/varh counter and as a whole-unit plus remainder pair; use the pair for large totals.
- Reset commands are coils written with function 05 and FF00.
- The trip/reset register C3AC operates the breaker remotely; treat it as a control point.
Network setup
- Defaults from the setup tables: peripheral number 1, 19200 baud, no parity, 8 data bits, 1 stop bit.
- Only 9600 and 19200 baud are offered.
- Up to 32 devices per RS-485 bus, 1200 m maximum.
Watch out for
- Writing C3AC = 1 trips the breaker and cuts the load.
Circutor RECmax-CVM Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 2105doc 839 | Start maximum demand | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2111doc 83F | Delete max demand maximum | Write FF00 with function 05. | BIT | Write | ||||
| CO | 2120doc 848 | Delete energies, max demand and max/min | Write FF00 with function 05. | BIT | Write | ||||
| IR | 0doc 00-01 | Phase voltage L1 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 2doc 02-03 | Current L1 | Instantaneous value. | UINT32 | ABCD | mA | Read | ||
| IR | 6doc 06-07 | Inductive reactive power L1 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 10doc 0A-0B | Phase voltage L2 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 12doc 0C-0D | Current L2 | Instantaneous value. | UINT32 | ABCD | mA | Read | ||
| IR | 16doc 10-11 | Inductive reactive power L2 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 20doc 14-15 | Phase voltage L3 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 22doc 16-17 | Current L3 | Instantaneous value. | UINT32 | ABCD | mA | Read | ||
| IR | 26doc 1A-1B | Inductive reactive power L3 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 32doc 20-21 | Three-phase inductive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 34doc 22-23 | Three-phase capacitive power | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 40doc 28-29 | Frequency | Instantaneous value. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 42doc 2A-2B | Voltage L1-L2 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 44doc 2C-2D | Voltage L2-L3 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 46doc 2E-2F | Voltage L3-L1 | Instantaneous value. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 48doc 30-31 | L1 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 50doc 32-33 | L2 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 52doc 34-35 | L3 voltage THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 54doc 36-37 | L1 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 56doc 38-39 | L2 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 58doc 3A-3B | L3 current THD | Instantaneous value. | UINT32 | ABCD | × 0.1 | % | Read | |
| IR | 60doc 3C-3D | Consumed active energy III | UINT32 | ABCD | Wh | Read | |||
| IR | 62doc 3E-3F | Consumed inductive reactive energy III | UINT32 | ABCD | varh | Read | |||
| IR | 64doc 40-41 | Consumed capacitive reactive energy III | UINT32 | ABCD | varh | Read | |||
| IR | 66doc 42-43 | Three-phase apparent power | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 68doc 44-45 | Maximum demand I L1 | Value from the table's instantaneous column for this maximum-demand row. | UINT32 | ABCD | mA | Read | ||
| IR | 72doc 48-49 | Neutral current | Instantaneous value. | UINT32 | ABCD | mA | Read | ||
| IR | 74doc 4A-4B | Apparent power L1 | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 76doc 4C-4D | Apparent power L2 | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 78doc 4E-4F | Apparent power L3 | Instantaneous value. | UINT32 | ABCD | VA | Read | ||
| IR | 82doc 52-53 | Maximum demand I L2 | Value from the table's instantaneous column for this maximum-demand row. | UINT32 | ABCD | mA | Read | ||
| IR | 84doc 54-55 | Maximum demand I L3 | Value from the table's instantaneous column for this maximum-demand row. | UINT32 | ABCD | mA | Read | ||
| IR | 86doc 56-57 | Consumed apparent energy III | UINT32 | ABCD | VAh | Read | |||
| IR | 88doc 58-59 | Generated active energy III | UINT32 | ABCD | Wh | Read | |||
| IR | 90doc 5A-5B | Generated inductive reactive energy III | UINT32 | ABCD | varh | Read | |||
| IR | 92doc 5C-5D | Generated capacitive reactive energy III | UINT32 | ABCD | varh | Read | |||
| IR | 94doc 5E-5F | Generated apparent energy III | UINT32 | ABCD | VAh | Read | |||
| IR | 96doc 60-61 | Phase voltage L1 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 98doc 62-63 | Current L1 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | mA | Read | ||
| IR | 106doc 6A-6B | Phase voltage L2 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 108doc 6C-6D | Current L2 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | mA | Read | ||
| IR | 116doc 74-75 | Phase voltage L3 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | × 0.1 | V | Read | |
| IR | 118doc 76-77 | Current L3 (max) | Highest value since the last max/min reset. | UINT32 | ABCD | mA | Read | ||
| IR | 302doc 12E-12F | Capacitive reactive power L1 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 308doc 134-135 | Capacitive reactive power L2 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 314doc 13A-13B | Capacitive reactive power L3 | Instantaneous value. | UINT32 | ABCD | var | Read | ||
| IR | 356doc 164-165 | Maximum demand kVA III | Value from the table's instantaneous column for this maximum-demand row. | UINT32 | ABCD | VA | Read | ||
| IR | 358doc 166-167 | Maximum demand I average | Value from the table's instantaneous column for this maximum-demand row. | UINT32 | ABCD | mA | Read | ||
| IR | 396doc 18C-18D | Consumed active energy III (kWh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kWh | Read | ||
| IR | 398doc 18E-18F | Consumed active energy III (Wh part) | Remainder below one whole unit. | UINT32 | ABCD | Wh | Read | ||
| IR | 400doc 190-191 | Consumed inductive reactive energy III (kvarh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 402doc 192-193 | Consumed inductive reactive energy III (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 404doc 194-195 | Consumed capacitive reactive energy III (kvarh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 406doc 196-197 | Consumed capacitive reactive energy III (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 408doc 198-199 | Consumed apparent energy III (kVAh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kVAh | Read | ||
| IR | 410doc 19A-19B | Consumed apparent energy III (VAh part) | Remainder below one whole unit. | UINT32 | ABCD | VAh | Read | ||
| IR | 416doc 1A0-1A1 | Generated active energy III (kWh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kWh | Read | ||
| IR | 418doc 1A2-1A3 | Generated active energy III (Wh part) | Remainder below one whole unit. | UINT32 | ABCD | Wh | Read | ||
| IR | 420doc 1A4-1A5 | Generated inductive reactive energy III (kvarh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 422doc 1A6-1A7 | Generated inductive reactive energy III (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 424doc 1A8-1A9 | Generated capacitive reactive energy III (kvarh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kvarh | Read | ||
| IR | 426doc 1AA-1AB | Generated capacitive reactive energy III (varh part) | Remainder below one whole unit. | UINT32 | ABCD | varh | Read | ||
| IR | 428doc 1AC-1AD | Generated apparent energy III (kVAh part) | Whole-unit counter; combine with the matching remainder register. | UINT32 | ABCD | kVAh | Read | ||
| IR | 430doc 1AE-1AF | Generated apparent energy III (VAh part) | Remainder below one whole unit. | UINT32 | ABCD | VAh | Read | ||
| IR | 436doc 1B4-1B5 | Hours per tariff | UINT32 | ABCD | s | Read | |||
| IR | 2001doc 07D1 | Power status | Quadrant flags. | BITMAP16 | Read | bit 0 = Consumed; bit 1 = Generated; bit 2 = Inductive; bit 3 = Capacitive | |||
| IR | 14000doc 36B0 | Measurement alarms | BITMAP16 | Read | bit 0 = Phase 1 voltage above 265 V; bit 1 = Phase 1 voltage below 160 V; bit 2 = Three-phase supply wiring error | ||||
| IR | 20001doc 4E21 | Digital output status | UINT16 | Read | 0 = Digital output OFF; 4 = Digital output ON | ||||
| IR | 50064doc C390 | Relay output status | BITMAP16 | Read | bit 0 = REC LOCKED relay ON; bit 1 = POSITIVE SAFE OUTPUT relay ON | ||||
| IR | 50066doc C392 | Total reclosing operations | UINT16 | Read | |||||
| IR | 50067doc C393 | Reclosings after earth-leakage trip | Partial counter. | UINT16 | Read | ||||
| IR | 50068doc C394 | Reclosings after circuit-breaker trip | Partial counter. | UINT16 | Read | ||||
| IR | 50069doc C395 | Total reclosings after earth-leakage trip | UINT16 | Read | |||||
| IR | 50070doc C396 | Total reclosings after circuit-breaker trip | UINT16 | Read | |||||
| IR | 50071doc C397 | Leakage current | Present earth leakage current. | UINT16 | mA | Read | |||
| IR | 50072doc C398 | Trip current | Leakage current that caused the last trip. | UINT16 | mA | Read | |||
| IR | 50073doc C399 | Network voltage | UINT16 | V | Read | ||||
| HR | 10050doc 2742 | Protocol | UINT16 | Read/write | 0 = Modbus (default) | ||||
| HR | 10051doc 2743 | Peripheral number | 0-255, default 1. | UINT16 | Read/write | ||||
| HR | 10052doc 2744 | Transmission speed | UINT16 | Read/write | 0 = 9600; 1 = 19200 (default) | ||||
| HR | 10053doc 2745 | Parity | UINT16 | Read/write | 0 = No parity (default); 1 = Odd; 2 = Even | ||||
| HR | 10054doc 2746 | Data bits | UINT16 | Read/write | 0 = 8 bits (default); 1 = 7 bits | ||||
| HR | 10055doc 2747 | Stop bits | UINT16 | Read/write | 0 = 1 stop bit (default); 1 = 2 stop bits | ||||
| HR | 10060doc 274C | Max demand integration period | 1-60, default 15. | UINT16 | min | Read/write | |||
| HR | 10061doc 274D | Max demand integration type | UINT16 | Read/write | 0 = Sliding (default); 1 = Fixed | ||||
| HR | 10100doc 2774 | THD calculation | UINT16 | Read/write | 0 = RMS (default); 1 = Fundamental | ||||
| HR | 11044doc 2B24 | Number of quadrants | Manual lists only function 04 here. | UINT16 | Read | 0 = 4 quadrants; 1 = 2 quadrants | |||
| HR | 50016doc C360 | Nominal frequency | UINT16 | Read/write | 50 = 50 Hz (0x32, default); 60 = 60 Hz (0x3C) | ||||
| HR | 50017doc C361 | Sensitivity current | UINT16 | Read/write | 0 = 30 mA (default); 1 = 0.1 A; 2 = 0.3 A; 3 = 0.5 A; 4 = 1 A | ||||
| HR | 50018doc C362 | Activation delay | UINT16 | Read/write | 0 = INS curve (default); 1 = SEL curve; 2 = 0.1 s; 3 = 0.2 s; 4 = 0.3 s; 5 = 0.4 s; 6 = 0.5 s; 7 = 0.75 s; 8 = 1.00 s | ||||
| HR | 50019doc C363 | Function of POSITIVE SAFE OUTPUT relay | Manual lists only function 04 here. | UINT16 | Read | 0 = Power supply error; 1 = Status of main switch; 2 = 50% of earth leakage; 3 = 60% of earth leakage; 4 = 70% of earth leakage; 5 = 80% of earth leakage; 6 = 85% of earth leakage | |||
| HR | 50022doc C366 | Contact type, REC LOCKED relay | UINT16 | Read/write | 0 = STD, no positive safety; 1 = POS, positive safety (default) | ||||
| HR | 50023doc C367 | Contact type, POSITIVE SAFE OUTPUT relay | UINT16 | Read/write | 0 = STD, no positive safety; 1 = POS, positive safety (default) | ||||
| HR | 50024doc C368 | Earth leakage reclosing sequence | 0-14 from the manual's sequence table, default 10. | UINT16 | Read/write | ||||
| HR | 50025doc C369 | Circuit breaker reclosing sequence | 0-8 from the manual's sequence table, default 5. | UINT16 | Read/write | ||||
| HR | 50065doc C391 | Enable reclosing | Manual lists only function 04 here. | UINT16 | Read | 0 = No; 1 = Yes (default) | |||
| HR | 50092doc C3AC | Trip or reset of the device | Command register. | UINT16 | Read/write | 1 = Trip; 2 = Reset; 3 = Reset of the device |
Notes on this map
- Word order: the read example returns register 1 = 0000 and register 2 = 084D for 212.5 V, so 32-bit values are high word first (ABCD).
- Left out: active power (per phase and three-phase), power factor, cos phi and the kW maximum demand. The device measures in four quadrants but the manual never says whether these Modbus values are signed, so their type cannot be fixed from the document.
- Voltages, currents, reactive and apparent powers, frequency, THD, demand values and energies are non-negative and are typed UINT32.
- Left out: minimum values, most maximum values, harmonics tables (0x1F4-0x367), CO2 and cost registers, digital output programming (0x2B0C-0x2B15), model and serial-number registers (type not stated) and the input-status word at C38F, whose bit list starts at bit 1 and ends with an unlabeled bit 9, so the bit positions are not certain.
- Measurement, energy and protection variables accept functions 03 and 04. Setup registers are listed as holding registers; the manual names function 0x10 for most of them, but for the number of quadrants (2B24), the POSITIVE SAFE OUTPUT function (C363) and enable reclosing (C391) it lists only function 04, so those are marked read-only.
- Setup changes take effect only after the device is reset, and an out-of-range value is replaced by the default without an error.
- Left out: the transformation ratios (2710-2714). The manual gives their addresses but no units, ranges or encoding, so the current secondary in particular could be a code rather than amps.
- Left out: the delete-energy (834) and delete-max/min (838) coils. Table 27 puts max/min deletion at 838, but the function 05 write example uses 0834 for the same action, so the two addresses contradict each other.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Circutor RECmax-CVM
What Modbus registers does the Circutor RECmax-CVM have?
This map lists 100 registers: 3 coils, 77 input registers, 20 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Circutor RECmax-CVM Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints every Modbus address in hexadecimal and they are the wire addresses. Its read example asks for initial register 0000 to get L1 phase voltage and receives 0000 084D (2125 = 212.5 V), which confirms the offset and the x10 voltage scale.
What byte order does the Circutor RECmax-CVM use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Circutor RECmax-CVM?
Start with IR 0 Phase voltage L1 (L1 phase voltage (V x10)); IR 2 Current L1 (L1 current (mA)); IR 66 Three-phase apparent power (Three-phase apparent power); IR 40 Frequency (Frequency (Hz x10)); IR 60 Consumed active energy III (Consumed active energy); IR 50071 Leakage current (Earth leakage current (mA)); IR 50066 Total reclosing operations (Total reclosing operations); IR 50064 Relay output status (Relay status).
How do I enable Modbus control of the Circutor RECmax-CVM?
Modbus RTU is the standard protocol (Protocol register 0x2742 = 0). Set the peripheral number from the front panel (hold PROG for more than 3 s) or register 0x2743, and speed and framing with 0x2744-0x2747; reset the device for Modbus setup changes to apply.
Where is the official Circutor RECmax-CVM Modbus documentation?
The source is RECmax-CVM Earth leakage circuit breaker with automatic reclosing and measurement system - Instruction Manual (M175B01-03-22A), revision 2022-05, published free by Circutor at https://docs.circutor.com/docs/M175B01-03.pdf.
More Circutor Modbus register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12 - Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth
Other power & energy meters register maps
- Energy meter
Eastron SDM120CT-40mA
Eastron SDM120CT-40mA single-phase CT-connected DIN-rail meter with RS485 Modbus RTU, user manual V1.0 (2026-07-16).
Also known as: SDM120CT-M-40mA, SDM120CT-M 40mA - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Sensor (clamp-on ultrasonic flowmeter)
Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)
Proline Prosonic Flow W 400 clamp-on flowmeter with the Modbus RS485 output, as described in GP01207D/06/EN/01.24.
Also known as: Prosonic Flow W 400 - Power meter
IME Nemo 72Le multifunction meter (MF724)
IME Nemo 72Le 72x72 panel meter MF724 with RS-485, per protocol PR141 (software 1.04).
Also known as: MF724, Nemo 72Le - Energy meter
inepro Metering 4PU / 4PS three-phase energy meter
4PU (meter code 1111) and 4PS (1112) MID three-phase DIN-rail meters with Modbus, user manual version 1.03 (2025).
Also known as: 4PU, 4PS, inepro 4PU, inepro 4PS - Energy meter
inepro Metering PRO380-Mod three-phase energy meter
PRO380-Mod and PRO380-Mod CT (RS485 Modbus RTU), current register map from PRO380 user manual version 2.18-8.
Also known as: PRO380 Mod, PRO380-Mod CT, PRO380-MOD, inepro PRO380, PRO380 MID
All power & energy meters Modbus register maps →
Source: RECmax-CVM Earth leakage circuit breaker with automatic reclosing and measurement system - Instruction Manual · M175B01-03-22A · rev. 2022-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.