- Nemo 96HDe multifunction meter (MF96E06)
Power meter · Modbus register map
IME Nemo 96HDe multifunction meter (MF96E06) Modbus register map
Updated 17 November 2026
The Nemo 96HDe is a 96x96 multifunction meter with an RS-485 Modbus/JBUS port (functions 03 and 0x10). Voltages and currents are integers in mV/mA; a fixed-unit block gives signed powers and Wh/MWh energy counters.
This page lists 110 Modbus registers for the IME Nemo 96HDe multifunction meter (MF96E06) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from IME’s own free documentation (linked below) and checked against it.
- Manufacturer
- IME
- Model
- Nemo 96HDe multifunction meter (MF96E06)
- Equipment type
- Power meter
- Registers
- 110 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MF96E06, Nemo 96HDe
Integration notes: IME Nemo 96HDe multifunction meter (MF96E06)
Read holding registers (function 03) from 0x1000 for voltages and currents in mV/mA, and from 0x1500 (or 0x1700) for signed powers and energies in fixed units. Double words are high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4096 | Phase 1: phase voltage | UINT32 ABCD | Phase 1 voltage | Read |
| HR 4102 | Phase 1: current | UINT32 ABCD | Phase 1 current | Read |
| HR 4134 | Frequency | UINT16 | Frequency | Read |
| HR 4132 | 3-phase: power factor | INT16 | 3-phase power factor | Read |
| HR 5400 | Signed 3-ph Active Power | INT32 ABCD | Signed 3-phase active power | Read |
| HR 5376 | Positive Active Energy - Low | UINT32 ABCD | Positive active energy (Wh part) | Read |
| HR 5378 | Positive Active Energy - High | UINT32 ABCD | Positive active energy (MWh part) | Read |
Enable Modbus control & writes
Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.
Byte order & addressing
- Only functions 03 and 0x10 are supported (no function 04).
- A single request may ask for at most 240 bytes of data.
- Voltages and currents are in mV and mA.
Network setup
- Baud rate and parity are programmable on the device; 8 data bits and 1 stop bit.
Watch out for
- Power registers in the 0x10xx block change scale with the CT/VT ratio; prefer the 0x15xx block.
IME Nemo 96HDe multifunction meter (MF96E06) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4096doc 0x1000 | Phase 1: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4098doc 0x1002 | Phase 2: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4100doc 0x1004 | Phase 3: phase voltage | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4102doc 0x1006 | Phase 1: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4104doc 0x1008 | Phase 2: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4106doc 0x100a | Phase 3: current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4108doc 0x100c | Neutral current | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4110doc 0x100e | Chained voltage: L1-L2 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4112doc 0x1010 | Chained voltage: L2-L3 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4114doc 0x1012 | Chained voltage: L3-L1 | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4122doc 0x101a | 3-phase: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4123doc 0x101b | 3-phase: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4132doc 0x1024 | 3-phase: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4133doc 0x1025 | 3-phase: sector of power factor (cap or ind) | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4134doc 0x1026 | Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 4139doc 0x102b | Time counter for average power | UINT16 | min | Read | ||||
| HR | 4146doc 0x1032 | Phase 1: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4147doc 0x1033 | Phase 2: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4148doc 0x1034 | Phase 3: sign of active power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4155doc 0x103b | Phase 1: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4156doc 0x103c | Phase 2: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4157doc 0x103d | Phase 3: sign of reactive power | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 4164doc 0x1044 | Phase 1: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4165doc 0x1045 | Phase 2: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4166doc 0x1046 | Phase 3: power factor | INT16 | × 0.01 | Read | ||||
| HR | 4167doc 0x1047 | Phase 1: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4168doc 0x1048 | Phase 2: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4169doc 0x1049 | Phase 3: power factor sector | UINT16 | Read | 0 = PF = 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 4170doc 0x104a | Phase 1: THD V1 | UINT16 | × 0.1 | % | Read | |||
| HR | 4171doc 0x104b | Phase 2: THD V2 | UINT16 | × 0.1 | % | Read | |||
| HR | 4172doc 0x104c | Phase 3: THD V3 | UINT16 | × 0.1 | % | Read | |||
| HR | 4173doc 0x104d | Phase 1: THD I1 | UINT16 | × 0.1 | % | Read | |||
| HR | 4174doc 0x104e | Phase 2: THD I2 | UINT16 | × 0.1 | % | Read | |||
| HR | 4175doc 0x104f | Phase 3: THD I3 | UINT16 | × 0.1 | % | Read | |||
| HR | 4176doc 0x1050 | Phase 1: I1 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4178doc 0x1052 | Phase 2: I2 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4180doc 0x1054 | Phase 3: I3 average | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4182doc 0x1056 | Phase 1: I1 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4184doc 0x1058 | Phase 2: I2 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4186doc 0x105a | Phase 3: I3 peak maximum | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4188doc 0x105c | (I1+I2+I3)/3 | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 4190doc 0x105e | Phase 1: V1 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4192doc 0x1060 | Phase 2: V2 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4194doc 0x1062 | Phase 3: V3 min | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4196doc 0x1064 | Phase 1: V1 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4198doc 0x1066 | Phase 2: V2 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4200doc 0x1068 | Phase 3: V3 max | UINT32 | ABCD | × 0.001 | V | Read | ||
| HR | 4206doc 0x106e | Run hour meter | UINT16 | h | Read | ||||
| HR | 4613doc 0x1205 | Voltages sequence diagnostic | UINT16 | Read | 1 = OK; 2 = Error | ||||
| HR | 5376doc 0x1500 | Positive Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5378doc 0x1502 | Positive Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5380doc 0x1504 | Positive Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5382doc 0x1506 | Positive Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5384doc 0x1508 | Negative Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5386doc 0x150A | Negative Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5388doc 0x150C | Negative Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5390doc 0x150E | Negative Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5392doc 0x1510 | Partial Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5394doc 0x1512 | Partial Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5396doc 0x1514 | Partial Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5398doc 0x1516 | Partial Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5400doc 0x1518 | Signed 3-ph Active Power | INT32 | ABCD | W | Read | |||
| HR | 5402doc 0x151A | Signed 3-ph Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5404doc 0x151C | Signed Phase1 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5406doc 0x151E | Signed Phase2 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5408doc 0x1520 | Signed Phase3 Active Power | INT32 | ABCD | W | Read | |||
| HR | 5410doc 0x1522 | Signed Phase1 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5412doc 0x1524 | Signed Phase2 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5414doc 0x1526 | Signed Phase3 Reactive Power | INT32 | ABCD | var | Read | |||
| HR | 5416doc 0x1528 | Signed 3-ph Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5418doc 0x152A | Signed Phase1 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5420doc 0x152C | Signed Phase2 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5422doc 0x152E | Signed Phase3 Power Factor | INT32 | ABCD | × 0.001 | Read | |||
| HR | 5424doc 0x1530 | Apparent power | UINT32 | ABCD | VA | Read | |||
| HR | 5426doc 0x1532 | 3-phase: active average power | UINT32 | ABCD | W | Read | |||
| HR | 5428doc 0x1534 | 3-phase: reactive average power | UINT32 | ABCD | var | Read | |||
| HR | 5430doc 0x1536 | 3-phase: apparent average power | UINT32 | ABCD | VA | Read | |||
| HR | 5432doc 0x1538 | 3-phase: active PMD power | UINT32 | ABCD | W | Read | |||
| HR | 5434doc 0x153a | 3-phase: reactive PMD power | UINT32 | ABCD | var | Read | |||
| HR | 5436doc 0x153c | 3-phase: apparent PMD power | UINT32 | ABCD | VA | Read | |||
| HR | 5888doc 0x1700 | Positive Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5890doc 0x1702 | Positive Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5892doc 0x1704 | Positive Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5894doc 0x1706 | Positive Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5896doc 0x1708 | Negative Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5898doc 0x170A | Negative Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5900doc 0x170C | Negative Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5902doc 0x170E | Negative Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5904doc 0x1710 | Partial+ Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5906doc 0x1712 | Partial+ Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5908doc 0x1714 | Partial+ Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5910doc 0x1716 | Partial+ Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5912doc 0x1718 | Partial- Active Energy - Low | UINT32 | ABCD | Wh | Read | |||
| HR | 5914doc 0x171a | Partial- Active Energy - High | UINT32 | ABCD | MWh | Read | |||
| HR | 5916doc 0x171c | Partial- Reactive Energy - Low | UINT32 | ABCD | varh | Read | |||
| HR | 5918doc 0x171e | Partial- Reactive Energy - High | UINT32 | ABCD | Mvarh | Read | |||
| HR | 5920doc 0x1720 | Signed 3-ph active power | INT32 | ABCD | W | Read | |||
| HR | 5922doc 0x1722 | Signed 3-ph reactive power | INT32 | ABCD | var | Read | |||
| HR | 5924doc 0x1724 | Signed phase1 active power | INT32 | ABCD | W | Read | |||
| HR | 5926doc 0x1726 | Signed phase2 active power | INT32 | ABCD | W | Read | |||
| HR | 5928doc 0x1728 | Signed phase3 active power | INT32 | ABCD | W | Read | |||
| HR | 5930doc 0x172A | Signed phase1 reactive power | INT32 | ABCD | var | Read | |||
| HR | 5932doc 0x172C | Signed phase2 reactive power | INT32 | ABCD | var | Read | |||
| HR | 5934doc 0x172E | Signed phase3 reactive power | INT32 | ABCD | var | Read | |||
| HR | 29952doc 0x7500 | THD I1 | UINT16 | × 0.1 | % | Read | |||
| HR | 29953doc 0x7501 | THD I2 | UINT16 | × 0.1 | % | Read | |||
| HR | 29954doc 0x7502 | THD I3 | UINT16 | × 0.1 | % | Read | |||
| HR | 29955doc 0x7503 | THD V1 (V12) | UINT16 | × 0.1 | % | Read | |||
| HR | 29956doc 0x7504 | THD V2 (V23) | UINT16 | × 0.1 | % | Read | |||
| HR | 29957doc 0x7505 | THD V3 (V31) | UINT16 | × 0.1 | % | Read |
Notes on this map
- Double-word values (UD_WORD/SD_WORD) are sent most significant word first; the protocol notes the meter can be set to big endian, little endian or swapped words, so check that setting if values look wrong.
- Left out: power and energy registers whose unit is footnote (3) or (4); their scale depends on the CT x VT ratio (for example W/100 below a ratio product of 5000). The 0x15xx/0x17xx blocks give the same quantities in fixed units (W, var, Wh plus MWh).
- Left out: setup parameters, device configuration words, the per-slot data areas, and any row whose printed unit does not fit the quantity (for example apparent power printed in W).
- Energy in fixed units is split in two double words: a low part in Wh (varh) and a high part in MWh (Mvarh); total = high x 1,000,000 + low.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the IME Nemo 96HDe multifunction meter (MF96E06)
What Modbus registers does the IME Nemo 96HDe multifunction meter (MF96E06) have?
This map lists 110 registers: 110 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the IME Nemo 96HDe multifunction meter (MF96E06) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are the hex word addresses sent as 'first WORD address' in the function 03 request, so they go on the wire unchanged.
What byte order does the IME Nemo 96HDe multifunction meter (MF96E06) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the IME Nemo 96HDe multifunction meter (MF96E06)?
Start with HR 4096 Phase 1: phase voltage (Phase 1 voltage); HR 4102 Phase 1: current (Phase 1 current); HR 4134 Frequency (Frequency); HR 4132 3-phase: power factor (3-phase power factor); HR 5400 Signed 3-ph Active Power (Signed 3-phase active power); HR 5376 Positive Active Energy - Low (Positive active energy (Wh part)); HR 5378 Positive Active Energy - High (Positive active energy (MWh part)).
How do I enable Modbus control of the IME Nemo 96HDe multifunction meter (MF96E06)?
Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.
Where is the official IME Nemo 96HDe multifunction meter (MF96E06) Modbus documentation?
The source is Communication Modbus protocol PR145 - MF96E06 Nemo 96HDe (PR145), revision 2017-09-07, published free by IME at https://assets.legrand.com/pim/NP-FT-GT/PR145FR.pdf.
More IME Modbus register maps
- Energy meter (DIN-rail, single-phase)
IME Conto D1 single-phase energy meter (CE111)
IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).
Also known as: CE111, Conto D1 - Power meter
IME Nemo 72Le multifunction meter (MF724)
IME Nemo 72Le 72x72 panel meter MF724 with RS-485, per protocol PR141 (software 1.04).
Also known as: MF724, Nemo 72Le - Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Power meter (DIN-rail)
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
IME Nemo D4-Le for Rogowski coils, code KRNEMOD4, per protocol PR140 (software 1.01).
Also known as: KRNEMOD4
Other power & energy meters register maps
- Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Power meter (power analyser)
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
UMG 508 power analyser from firmware release 2.x, per Modbus address list 1.042.008.9.b (08/2022).
Also known as: UMG508, UMG 508, Janitza UMG508 - Power meter (power analyser)
Janitza UMG 605 power quality analyser (Modbus RTU)
UMG 605 (the original, non-PRO model), per Modbus address list 1.038.009.7.a. For the UMG 605-PRO use its own map.
Also known as: UMG605, UMG 605, Janitza UMG605 - Energy meter
KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)
KOSTAL Smart Energy Meter generation 1 and 2, firmware 2.6.0 (interface description dated 13.03.2025); OBIS-coded internal registers only.
Also known as: KSEM, KSEM G1, KSEM G2, KOSTAL Smart Energy Meter - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32
All power & energy meters Modbus register maps →
Source: Communication Modbus protocol PR145 - MF96E06 Nemo 96HDe · PR145 · rev. 2017-09-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.