Power meter · Modbus register map

IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) Modbus register map

Updated 17 November 2026

Short answer

Rogowski-coil version of the Nemo 96HDLe panel meter with an RS-485 Modbus/JBUS port. Voltages and currents are integers in mV/mA; a fixed-unit block gives signed powers and Wh/MWh energy counters.

This page lists 139 Modbus registers for the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from IME’s own free documentation (linked below) and checked against it.

Manufacturer
IME
Model
Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
Equipment type
Power meter
Registers
139 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
KRNEMOHD
Source document
Communication Modbus protocol PR139 - KRNEMOHD Nemo 96HDLe Rogowski coil input · PR139 rev. B · rev. 2016-07-19
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)

Integration in brief

Read holding registers (function 03) from 0x1000 for voltages and currents in mV/mA, and from 0x1500 (or 0x1700) for signed powers and energies in fixed units. Double words are high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4096Phase 1: phase voltageUINT32 ABCDPhase 1 voltageRead
HR 4102Phase 1: currentUINT32 ABCDPhase 1 currentRead
HR 4134FrequencyUINT16FrequencyRead
HR 41323-phase: power factorINT163-phase power factorRead
HR 5400Signed 3-ph Active PowerINT32 ABCDSigned 3-phase active powerRead
HR 5376Positive Active Energy - LowUINT32 ABCDPositive active energy (Wh part)Read
HR 5378Positive Active Energy - HighUINT32 ABCDPositive active energy (MWh part)Read

Enable Modbus control & writes

Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.

Byte order & addressing

Network setup

Watch out for

IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

139 of 139 shown
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4096doc 0x1000Phase 1: phase voltageUINT32ABCD× 0.001VRead
HR4098doc 0x1002Phase 2: phase voltageUINT32ABCD× 0.001VRead
HR4100doc 0x1004Phase 3: phase voltageUINT32ABCD× 0.001VRead
HR4102doc 0x1006Phase 1: currentUINT32ABCD× 0.001ARead
HR4104doc 0x1008Phase 2: currentUINT32ABCD× 0.001ARead
HR4106doc 0x100aPhase 3: currentUINT32ABCD× 0.001ARead
HR4108doc 0x100cNeutral currentUINT32ABCD× 0.001ARead
HR4110doc 0x100eChained voltage: L1-L2UINT32ABCD× 0.001VRead
HR4112doc 0x1010Chained voltage: L2-L3UINT32ABCD× 0.001VRead
HR4114doc 0x1012Chained voltage: L3-L1UINT32ABCD× 0.001VRead
HR4122doc 0x101a3-phase: sign of active powerUINT16Read0 = Positive; 1 = Negative
HR4123doc 0x101b3-phase: sign of reactive powerUINT16Read0 = Positive; 1 = Negative
HR4132doc 0x10243-phase: power factorINT16× 0.01Read
HR4133doc 0x10253-phase: sector of power factor (cap or ind)UINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4134doc 0x1026FrequencyUINT16× 0.1HzRead
HR4139doc 0x102bTime counter for average powerUINT16minRead
HR4146doc 0x1032Phase 1: sign of active powerUINT16Read0 = Positive; 1 = Negative
HR4147doc 0x1033Phase 2: sign of active powerUINT16Read0 = Positive; 1 = Negative
HR4148doc 0x1034Phase 3: sign of active powerUINT16Read0 = Positive; 1 = Negative
HR4155doc 0x103bPhase 1: sign of reactive powerUINT16Read0 = Positive; 1 = Negative
HR4156doc 0x103cPhase 2: sign of reactive powerUINT16Read0 = Positive; 1 = Negative
HR4157doc 0x103dPhase 3: sign of reactive powerUINT16Read0 = Positive; 1 = Negative
HR4164doc 0x1044Phase 1: power factorINT16× 0.01Read
HR4165doc 0x1045Phase 2: power factorINT16× 0.01Read
HR4166doc 0x1046Phase 3: power factorINT16× 0.01Read
HR4167doc 0x1047Phase 1: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4168doc 0x1048Phase 2: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4169doc 0x1049Phase 3: power factor sectorUINT16Read0 = PF = 1; 1 = Inductive; 2 = Capacitive
HR4170doc 0x104aPhase 1: THD V1UINT16× 0.1%Read
HR4171doc 0x104bPhase 2: THD V2UINT16× 0.1%Read
HR4172doc 0x104cPhase 3: THD V3UINT16× 0.1%Read
HR4173doc 0x104dPhase 1: THD I1UINT16× 0.1%Read
HR4174doc 0x104ePhase 2: THD I2UINT16× 0.1%Read
HR4175doc 0x104fPhase 3: THD I3UINT16× 0.1%Read
HR4176doc 0x1050Phase 1: I1 averageUINT32ABCD× 0.001ARead
HR4178doc 0x1052Phase 2: I2 averageUINT32ABCD× 0.001ARead
HR4180doc 0x1054Phase 3: I3 averageUINT32ABCD× 0.001ARead
HR4182doc 0x1056Phase 1: I1 peak maximumUINT32ABCD× 0.001ARead
HR4184doc 0x1058Phase 2: I2 peak maximumUINT32ABCD× 0.001ARead
HR4186doc 0x105aPhase 3: I3 peak maximumUINT32ABCD× 0.001ARead
HR4188doc 0x105c(I1+I2+I3)/3UINT32ABCD× 0.001ARead
HR4190doc 0x105ePhase 1: V1 minUINT32ABCD× 0.001VRead
HR4192doc 0x1060Phase 2: V2 minUINT32ABCD× 0.001VRead
HR4194doc 0x1062Phase 3: V3 minUINT32ABCD× 0.001VRead
HR4196doc 0x1064Phase 1: V1 maxUINT32ABCD× 0.001VRead
HR4198doc 0x1066Phase 2: V2 maxUINT32ABCD× 0.001VRead
HR4200doc 0x1068Phase 3: V3 maxUINT32ABCD× 0.001VRead
HR4206doc 0x106eRun hour meterUINT16hRead
HR4613doc 0x1205Voltages sequence diagnosticUINT16Read1 = OK; 2 = Error
HR5376doc 0x1500Positive Active Energy - LowUINT32ABCDWhRead
HR5378doc 0x1502Positive Active Energy - HighUINT32ABCDMWhRead
HR5380doc 0x1504Positive Reactive Energy - LowUINT32ABCDvarhRead
HR5382doc 0x1506Positive Reactive Energy - HighUINT32ABCDMvarhRead
HR5384doc 0x1508Negative Active Energy - LowUINT32ABCDWhRead
HR5386doc 0x150ANegative Active Energy - HighUINT32ABCDMWhRead
HR5388doc 0x150CNegative Reactive Energy - LowUINT32ABCDvarhRead
HR5390doc 0x150ENegative Reactive Energy - HighUINT32ABCDMvarhRead
HR5392doc 0x1510Partial Active Energy - LowUINT32ABCDWhRead
HR5394doc 0x1512Partial Active Energy - HighUINT32ABCDMWhRead
HR5396doc 0x1514Partial Reactive Energy - LowUINT32ABCDvarhRead
HR5398doc 0x1516Partial Reactive Energy - HighUINT32ABCDMvarhRead
HR5400doc 0x1518Signed 3-ph Active PowerINT32ABCDWRead
HR5402doc 0x151ASigned 3-ph Reactive PowerINT32ABCDvarRead
HR5404doc 0x151CSigned Phase1 Active PowerINT32ABCDWRead
HR5406doc 0x151ESigned Phase2 Active PowerINT32ABCDWRead
HR5408doc 0x1520Signed Phase3 Active PowerINT32ABCDWRead
HR5410doc 0x1522Signed Phase1 Reactive PowerINT32ABCDvarRead
HR5412doc 0x1524Signed Phase2 Reactive PowerINT32ABCDvarRead
HR5414doc 0x1526Signed Phase3 Reactive PowerINT32ABCDvarRead
HR5416doc 0x1528Signed 3-ph Power FactorINT32ABCD× 0.001Read
HR5418doc 0x152ASigned Phase1 Power FactorINT32ABCD× 0.001Read
HR5420doc 0x152CSigned Phase2 Power FactorINT32ABCD× 0.001Read
HR5422doc 0x152ESigned Phase3 Power FactorINT32ABCD× 0.001Read
HR5424doc 0x1530Apparent powerUINT32ABCDVARead
HR5426doc 0x15323-phase: active average powerUINT32ABCDWRead
HR5428doc 0x15343-phase: reactive average powerUINT32ABCDvarRead
HR5430doc 0x15363-phase: apparent average powerUINT32ABCDVARead
HR5432doc 0x15383-phase: active PMD powerUINT32ABCDWRead
HR5434doc 0x153a3-phase: reactive PMD powerUINT32ABCDvarRead
HR5436doc 0x153c3-phase: apparent PMD powerUINT32ABCDVARead
HR5504doc 0x1580Phase1 voltage crest factorUINT16× 0.001Read
HR5505doc 0x1581Phase2 voltage crest factorUINT16× 0.001Read
HR5506doc 0x1582Phase3 voltage crest factorUINT16× 0.001Read
HR5507doc 0x1583Phase1 current crest factorUINT16× 0.001Read
HR5508doc 0x1584Phase2 current crest factorUINT16× 0.001Read
HR5509doc 0x1585Phase3 current crest factorUINT16× 0.001Read
HR5510doc 0x1586Phase12 voltage crest factorUINT16× 0.001Read
HR5511doc 0x1587Phase23 voltage crest factorUINT16× 0.001Read
HR5512doc 0x1588Phase31 voltage crest factorUINT16× 0.001Read
HR5888doc 0x1700Positive Active Energy - LowUINT32ABCDWhRead
HR5890doc 0x1702Positive Active Energy - HighUINT32ABCDMWhRead
HR5892doc 0x1704Positive Reactive Energy - LowUINT32ABCDvarhRead
HR5894doc 0x1706Positive Reactive Energy - HighUINT32ABCDMvarhRead
HR5896doc 0x1708Negative Active Energy - LowUINT32ABCDWhRead
HR5898doc 0x170ANegative Active Energy - HighUINT32ABCDMWhRead
HR5900doc 0x170CNegative Reactive Energy - LowUINT32ABCDvarhRead
HR5902doc 0x170ENegative Reactive Energy - HighUINT32ABCDMvarhRead
HR5904doc 0x1710Partial+ Active Energy - LowUINT32ABCDWhRead
HR5906doc 0x1712Partial+ Active Energy - HighUINT32ABCDMWhRead
HR5908doc 0x1714Partial+ Reactive Energy - LowUINT32ABCDvarhRead
HR5910doc 0x1716Partial+ Reactive Energy - HighUINT32ABCDMvarhRead
HR5912doc 0x1718Partial- Active Energy - LowUINT32ABCDWhRead
HR5914doc 0x171aPartial- Active Energy - HighUINT32ABCDMWhRead
HR5916doc 0x171cPartial- Reactive Energy - LowUINT32ABCDvarhRead
HR5918doc 0x171ePartial- Reactive Energy - HighUINT32ABCDMvarhRead
HR5920doc 0x1720Signed 3-ph active powerINT32ABCDWRead
HR5922doc 0x1722Signed 3-ph reactive powerINT32ABCDvarRead
HR5924doc 0x1724Signed phase1 active powerINT32ABCDWRead
HR5926doc 0x1726Signed phase2 active powerINT32ABCDWRead
HR5928doc 0x1728Signed phase3 active powerINT32ABCDWRead
HR5930doc 0x172ASigned phase1 reactive powerINT32ABCDvarRead
HR5932doc 0x172CSigned phase2 reactive powerINT32ABCDvarRead
HR5934doc 0x172ESigned phase3 reactive powerINT32ABCDvarRead
HR28673doc 0x7001Current phase 1 - 2nd harmonic (percentage)UINT16× 0.1%Read
HR28721doc 0x7031Current phase 1 - 50th harmonic (percentage)UINT16× 0.1%Read
HR28737doc 0x7041Current phase 2 - 2nd harmonic (percentage)UINT16× 0.1%Read
HR28785doc 0x7071Current phase 2 - 50th harmonic (percentage)UINT16× 0.1%Read
HR28801doc 0x7081Current phase 3 - 2nd harmonic (percentage)UINT16× 0.1%Read
HR28849doc 0x70B1Current phase 3 - 50th harmonic (percentage)UINT16× 0.1%Read
HR28913doc 0x70F1Voltage phase 1 (V12) - 50th harmonic (percentage)UINT16× 0.1%Read
HR28929doc 0x7101Voltage phase 2 (V23) - 2nd harmonic (percentage)UINT16× 0.1%Read
HR28977doc 0x7131Voltage phase 2 (V23) - 50th harmonic (percentage)UINT16× 0.1%Read
HR28993doc 0x7141Voltage phase 3 (V31) - 2nd harmonic (percentage)UINT16× 0.1%Read
HR29041doc 0x7171Voltage phase 3 (V31) - 50th harmonic (percentage)UINT16× 0.1%Read
HR29184doc 0x7200Current phase 1 - fundamental (rms)UINT32ABCD× 0.001ARead
HR29282doc 0x7262Current phase 1 - 50th harmonic (rms)UINT32ABCD× 0.001ARead
HR29312doc 0x7280Current phase 2 - fundamental (rms)UINT32ABCD× 0.001ARead
HR29440doc 0x7300Current phase 3 - fundamental (rms)UINT32ABCD× 0.001ARead
HR29568doc 0x7380Voltage phase 1 (V12) - fundamental (rms)UINT32ABCD× 0.001VRead
HR29666doc 0x73E2Voltage phase 1 (V12) - 50th harmonic (rms)UINT32ABCD× 0.001VRead
HR29696doc 0x7400Voltage phase 2 (V23) - fundamental (rms)UINT32ABCD× 0.001VRead
HR29794doc 0x7462Voltage phase 2 (V23) - 50th harmonic (rms)UINT32ABCD× 0.001VRead
HR29824doc 0x7480Voltage phase 3 (V31) - fundamental (rms)UINT32ABCD× 0.001VRead
HR29952doc 0x7500THD I1UINT16× 0.1%Read
HR29953doc 0x7501THD I2UINT16× 0.1%Read
HR29954doc 0x7502THD I3UINT16× 0.1%Read
HR29955doc 0x7503THD V1UINT16× 0.1%Read
HR29956doc 0x7504THD V2UINT16× 0.1%Read
HR29957doc 0x7505THD V3UINT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)

What Modbus registers does the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) have?

This map lists 139 registers: 139 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are the hex word addresses sent as 'first WORD address' in the function 03 request, so they go on the wire unchanged.

What byte order does the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)?

Start with HR 4096 Phase 1: phase voltage (Phase 1 voltage); HR 4102 Phase 1: current (Phase 1 current); HR 4134 Frequency (Frequency); HR 4132 3-phase: power factor (3-phase power factor); HR 5400 Signed 3-ph Active Power (Signed 3-phase active power); HR 5376 Positive Active Energy - Low (Positive active energy (Wh part)); HR 5378 Positive Active Energy - High (Positive active energy (MWh part)).

How do I enable Modbus control of the IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)?

Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.

Where is the official IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD) Modbus documentation?

The source is Communication Modbus protocol PR139 - KRNEMOHD Nemo 96HDLe Rogowski coil input (PR139 rev. B), revision 2016-07-19, published free by IME at https://assets.legrand.com/pim/NP-FT-GT/PR139FR.pdf.

More IME Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Communication Modbus protocol PR139 - KRNEMOHD Nemo 96HDLe Rogowski coil input · PR139 rev. B · rev. 2016-07-19. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.