Easy Modbus
  1. Home
  2. Modbus register maps
  3. Rishabh Instruments
  4. RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)

Power meter (multi-circuit energy meter) · Modbus register map

Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The RISH ML 1400/1410 is a 96 x 96 panel meter that measures up to 12 load circuits from 4 voltage inputs. Every measured value is a 32-bit IEEE float available in both the 3X and 4X tables. This map lists the per-channel instantaneous values (voltage, current, W, VA, VAr, PF, angle), frequency and the core comms settings.

This page lists 82 Modbus registers for the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
Equipment type
Power meter (multi-circuit energy meter)
Registers
82 (3 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor
Source document
Interface Definition RISH MLM Digital Multifunction Instrument · DMAN-00IM-0795 Rev A · rev. 2020-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)

Integration in brief

Read the 12 channel currents and powers with function 04 from wire 12 and 36 as ABCD floats; voltages start at wire 0 and frequency is at wire 1468.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Voltage L1FLOAT32 ABCDVoltage L1Read
IR 12Current channel 1FLOAT32 ABCDCurrent channel 1Read
IR 36W channel 1FLOAT32 ABCDW channel 1Read
IR 108PF channel 1FLOAT32 ABCDPF channel 1Read
IR 1468FrequencyFLOAT32 ABCDFrequencyRead

Enable Modbus control & writes

Set address, baud rate and parity in the meter's communication parameter screen (or the RS485 setup and node address registers).

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

82 of 82 shown
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001 / 40001 (hex 0000, parameter 1)Voltage L1FLOAT32ABCDVRead
IR2doc 30003 / 40003 (hex 0002, parameter 2)Voltage L2FLOAT32ABCDVRead
IR4doc 30005 / 40005 (hex 0004, parameter 3)Voltage L3FLOAT32ABCDVRead
IR6doc 30007 / 40007 (hex 0006, parameter 4)Voltage L12FLOAT32ABCDVRead
IR8doc 30009 / 40009 (hex 0008, parameter 5)Voltage L23FLOAT32ABCDVRead
IR10doc 30011 / 40011 (hex 000A, parameter 6)Voltage L31FLOAT32ABCDVRead
IR12doc 30013 / 40013 (hex 000C, parameter 7)Current channel 1FLOAT32ABCDARead
IR14doc 30015 / 40015 (hex 000E, parameter 8)Current channel 2FLOAT32ABCDARead
IR16doc 30017 / 40017 (hex 0010, parameter 9)Current channel 3FLOAT32ABCDARead
IR18doc 30019 / 40019 (hex 0012, parameter 10)Current channel 4FLOAT32ABCDARead
IR20doc 30021 / 40021 (hex 0014, parameter 11)Current channel 5FLOAT32ABCDARead
IR22doc 30023 / 40023 (hex 0016, parameter 12)Current channel 6FLOAT32ABCDARead
IR24doc 30025 / 40025 (hex 0018, parameter 13)Current channel 7FLOAT32ABCDARead
IR26doc 30027 / 40027 (hex 001A, parameter 14)Current channel 8FLOAT32ABCDARead
IR28doc 30029 / 40029 (hex 001C, parameter 15)Current channel 9FLOAT32ABCDARead
IR30doc 30031 / 40031 (hex 001E, parameter 16)Current channel 10FLOAT32ABCDARead
IR32doc 30033 / 40033 (hex 0020, parameter 17)Current channel 11FLOAT32ABCDARead
IR34doc 30035 / 40035 (hex 0022, parameter 18)Current channel 12FLOAT32ABCDARead
IR36doc 30037 / 40037 (hex 0024, parameter 19)W channel 1Active power of the load on this channel.FLOAT32ABCDWRead
IR38doc 30039 / 40039 (hex 0026, parameter 20)W channel 2Active power of the load on this channel.FLOAT32ABCDWRead
IR40doc 30041 / 40041 (hex 0028, parameter 21)W channel 3Active power of the load on this channel.FLOAT32ABCDWRead
IR42doc 30043 / 40043 (hex 002A, parameter 22)W channel 4Active power of the load on this channel.FLOAT32ABCDWRead
IR44doc 30045 / 40045 (hex 002C, parameter 23)W channel 5Active power of the load on this channel.FLOAT32ABCDWRead
IR46doc 30047 / 40047 (hex 002E, parameter 24)W channel 6Active power of the load on this channel.FLOAT32ABCDWRead
IR48doc 30049 / 40049 (hex 0030, parameter 25)W channel 7Active power of the load on this channel.FLOAT32ABCDWRead
IR50doc 30051 / 40051 (hex 0032, parameter 26)W channel 8Active power of the load on this channel.FLOAT32ABCDWRead
IR52doc 30053 / 40053 (hex 0034, parameter 27)W channel 9Active power of the load on this channel.FLOAT32ABCDWRead
IR54doc 30055 / 40055 (hex 0036, parameter 28)W channel 10Active power of the load on this channel.FLOAT32ABCDWRead
IR56doc 30057 / 40057 (hex 0038, parameter 29)W channel 11Active power of the load on this channel.FLOAT32ABCDWRead
IR58doc 30059 / 40059 (hex 003A, parameter 30)W channel 12Active power of the load on this channel.FLOAT32ABCDWRead
IR60doc 30061 / 40061 (hex 003C, parameter 31)VA channel 1FLOAT32ABCDVARead
IR62doc 30063 / 40063 (hex 003E, parameter 32)VA channel 2FLOAT32ABCDVARead
IR64doc 30065 / 40065 (hex 0040, parameter 33)VA channel 3FLOAT32ABCDVARead
IR66doc 30067 / 40067 (hex 0042, parameter 34)VA channel 4FLOAT32ABCDVARead
IR68doc 30069 / 40069 (hex 0044, parameter 35)VA channel 5FLOAT32ABCDVARead
IR70doc 30071 / 40071 (hex 0046, parameter 36)VA channel 6FLOAT32ABCDVARead
IR72doc 30073 / 40073 (hex 0048, parameter 37)VA channel 7FLOAT32ABCDVARead
IR74doc 30075 / 40075 (hex 004A, parameter 38)VA channel 8FLOAT32ABCDVARead
IR76doc 30077 / 40077 (hex 004C, parameter 39)VA channel 9FLOAT32ABCDVARead
IR78doc 30079 / 40079 (hex 004E, parameter 40)VA channel 10FLOAT32ABCDVARead
IR80doc 30081 / 40081 (hex 0050, parameter 41)VA channel 11FLOAT32ABCDVARead
IR82doc 30083 / 40083 (hex 0052, parameter 42)VA channel 12FLOAT32ABCDVARead
IR84doc 30085 / 40085 (hex 0054, parameter 43)VAr channel 1FLOAT32ABCDVArRead
IR86doc 30087 / 40087 (hex 0056, parameter 44)VAr channel 2FLOAT32ABCDVArRead
IR88doc 30089 / 40089 (hex 0058, parameter 45)VAr channel 3FLOAT32ABCDVArRead
IR90doc 30091 / 40091 (hex 005A, parameter 46)VAr channel 4FLOAT32ABCDVArRead
IR92doc 30093 / 40093 (hex 005C, parameter 47)VAr channel 5FLOAT32ABCDVArRead
IR94doc 30095 / 40095 (hex 005E, parameter 48)VAr channel 6FLOAT32ABCDVArRead
IR96doc 30097 / 40097 (hex 0060, parameter 49)VAr channel 7FLOAT32ABCDVArRead
IR98doc 30099 / 40099 (hex 0062, parameter 50)VAr channel 8FLOAT32ABCDVArRead
IR100doc 30101 / 40101 (hex 0064, parameter 51)VAr channel 9FLOAT32ABCDVArRead
IR102doc 30103 / 40103 (hex 0066, parameter 52)VAr channel 10FLOAT32ABCDVArRead
IR104doc 30105 / 40105 (hex 0068, parameter 53)VAr channel 11FLOAT32ABCDVArRead
IR106doc 30107 / 40107 (hex 006A, parameter 54)VAr channel 12FLOAT32ABCDVArRead
IR108doc 30109 / 40109 (hex 006C, parameter 55)PF channel 1Power factor.FLOAT32ABCDRead
IR110doc 30111 / 40111 (hex 006E, parameter 56)PF channel 2Power factor.FLOAT32ABCDRead
IR112doc 30113 / 40113 (hex 0070, parameter 57)PF channel 3Power factor.FLOAT32ABCDRead
IR114doc 30115 / 40115 (hex 0072, parameter 58)PF channel 4Power factor.FLOAT32ABCDRead
IR116doc 30117 / 40117 (hex 0074, parameter 59)PF channel 5Power factor.FLOAT32ABCDRead
IR118doc 30119 / 40119 (hex 0076, parameter 60)PF channel 6Power factor.FLOAT32ABCDRead
IR120doc 30121 / 40121 (hex 0078, parameter 61)PF channel 7Power factor.FLOAT32ABCDRead
IR122doc 30123 / 40123 (hex 007A, parameter 62)PF channel 8Power factor.FLOAT32ABCDRead
IR124doc 30125 / 40125 (hex 007C, parameter 63)PF channel 9Power factor.FLOAT32ABCDRead
IR126doc 30127 / 40127 (hex 007E, parameter 64)PF channel 10Power factor.FLOAT32ABCDRead
IR128doc 30129 / 40129 (hex 0080, parameter 65)PF channel 11Power factor.FLOAT32ABCDRead
IR130doc 30130 / 40130 (hex 0082, parameter 66)PF channel 12Power factor.FLOAT32ABCDRead
IR132doc 30131 / 40131 (hex 0084, parameter 67)Angle channel 1Phase angle of the channel.FLOAT32ABCDRead
IR134doc 30133 / 40133 (hex 0086, parameter 68)Angle channel 2Phase angle of the channel.FLOAT32ABCDRead
IR136doc 30135 / 40135 (hex 0088, parameter 69)Angle channel 3Phase angle of the channel.FLOAT32ABCDRead
IR138doc 30137 / 40137 (hex 008A, parameter 70)Angle channel 4Phase angle of the channel.FLOAT32ABCDRead
IR140doc 30139 / 40139 (hex 008C, parameter 71)Angle channel 5Phase angle of the channel.FLOAT32ABCDRead
IR142doc 30141 / 40141 (hex 008E, parameter 72)Angle channel 6Phase angle of the channel.FLOAT32ABCDRead
IR144doc 30143 / 40143 (hex 0090, parameter 73)Angle channel 7Phase angle of the channel.FLOAT32ABCDRead
IR146doc 30145 / 40145 (hex 0092, parameter 74)Angle channel 8Phase angle of the channel.FLOAT32ABCDRead
IR148doc 30147 / 40147 (hex 0094, parameter 75)Angle channel 9Phase angle of the channel.FLOAT32ABCDRead
IR150doc 30149 / 40149 (hex 0096, parameter 76)Angle channel 10Phase angle of the channel.FLOAT32ABCDRead
IR152doc 30151 / 40151 (hex 0098, parameter 77)Angle channel 11Phase angle of the channel.FLOAT32ABCDRead
IR154doc 30153 / 40153 (hex 009A, parameter 78)Angle channel 12Phase angle of the channel.FLOAT32ABCDRead
IR1468doc 31469 / 41469 (hex 05BC, parameter 735)FrequencyFLOAT32ABCDHzRead
HR6006doc 46007 (hex 1776)RS485 setup codeBaud/parity/stop-bit code from the manual's table 9.FLOAT32ABCDRead/write
HR6008doc 46009 (hex 1778)Node address1-247.FLOAT32ABCDRead/write
HR6010doc 46011 (hex 177A)Word orderWrite 2141.0 in the order you want floats sent.FLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)

What Modbus registers does the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) have?

This map lists 82 registers: 79 input registers, 3 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 1 prints 30001/40001-style numbers plus a hex start-address column. The manual's example reads Voltage L2 (30003, parameter 2) at start address 00 02 and W channel 2 (40039, parameter 20) at 00 26, so subtract 30001 or 40001. Where the printed decimal and the hex column disagree (parameters 66-84), this map follows the hex column, which matches the rule wire = 2 x (parameter - 1).

What byte order does the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)?

Start with IR 0 Voltage L1 (Voltage L1); IR 12 Current channel 1 (Current channel 1); IR 36 W channel 1 (W channel 1); IR 108 PF channel 1 (PF channel 1); IR 1468 Frequency (Frequency).

How do I enable Modbus control of the Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)?

Set address, baud rate and parity in the meter's communication parameter screen (or the RS485 setup and node address registers).

Where is the official Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU) Modbus documentation?

The source is Interface Definition RISH MLM Digital Multifunction Instrument (DMAN-00IM-0795 Rev A), revision 2020-08, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-ml-1400-ml-1410-multiload-monitor-126/ID-MLM.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Interface Definition RISH MLM Digital Multifunction Instrument · DMAN-00IM-0795 Rev A · rev. 2020-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.