Easy Modbus
  1. Home
  2. Modbus register maps
  3. Rishabh Instruments
  4. RISH Delta Power NX multifunction power meter

Power meter · Modbus register map

Rishabh Instruments RISH Delta Power NX multifunction power meter Modbus register map

Updated 19 November 2026

Short answer

The RISH Delta Power NX is a 96 x 96 mm multifunction meter that measures voltage, current, power, power factor, frequency and demand (no energy counters) on 1-phase and 3-phase networks, with an RS-485 Modbus RTU port. Every value is an IEEE 754 float in two registers: measurements are input registers (FC04) from 30001, mirrored as holding registers at 40001+, and setup parameters sit at 46003-46085. This map covers the measured values, demands, run/on hours and the setup block.

This page lists 89 Modbus registers for the Rishabh Instruments RISH Delta Power NX multifunction power meter — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH Delta Power NX multifunction power meter
Equipment type
Power meter
Registers
89 (22 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH Delta Power NX, Delta Power NX, RISH Delta Power
Source document
Operating Manual RISH Delta Power NX · AMAN-00IM-0117 Rev. E · rev. 2024-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH Delta Power NX multifunction power meter

Integration in brief

Read 30001-30072 (and the demand block 30083-30106) with FC04 and decode each register pair as a big-endian float. Settings are floats at 46003+ written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0V1FLOAT32 ABCDVoltage L1Read
IR 6I1FLOAT32 ABCDCurrent L1Read
IR 52Watt sumFLOAT32 ABCDTotal active powerRead
IR 62PF averageFLOAT32 ABCDAverage power factorRead
IR 70System frequencyFLOAT32 ABCDFrequencyRead

Enable Modbus control & writes

Set the Modbus address (46047, default 1) and Comsetup code (46045, default 8 = 9600 8N1) from the front panel or over Modbus.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH Delta Power NX multifunction power meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

89 of 89 shown
Rishabh Instruments RISH Delta Power NX multifunction power meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001V1L1 voltage (L-N on 4-wire, L-L on 3-wire).FLOAT32ABCDRead
IR2doc 30003V2Not on 1P2W.FLOAT32ABCDRead
IR4doc 30005V33P4W and 3P3W only.FLOAT32ABCDRead
IR6doc 30007I1FLOAT32ABCDRead
IR8doc 30009I2Not on 1P2W.FLOAT32ABCDRead
IR10doc 30011I33P4W and 3P3W only.FLOAT32ABCDRead
IR12doc 30013W1Not on 3P3W.FLOAT32ABCDRead
IR14doc 30015W23P4W and 1P3W only.FLOAT32ABCDRead
IR16doc 30017W33P4W only.FLOAT32ABCDRead
IR18doc 30019VA1Not on 3P3W.FLOAT32ABCDRead
IR20doc 30021VA23P4W and 1P3W only.FLOAT32ABCDRead
IR22doc 30023VA33P4W only.FLOAT32ABCDRead
IR24doc 30025VAR1Not on 3P3W.FLOAT32ABCDRead
IR26doc 30027VAR23P4W and 1P3W only.FLOAT32ABCDRead
IR28doc 30029VAR33P4W only.FLOAT32ABCDRead
IR30doc 30031PF1Not on 3P3W.FLOAT32ABCDRead
IR32doc 30033PF23P4W and 1P3W only.FLOAT32ABCDRead
IR34doc 30035PF33P4W only.FLOAT32ABCDRead
IR36doc 30037Angle1Not on 3P3W.FLOAT32ABCDRead
IR38doc 30039Angle23P4W and 1P3W only.FLOAT32ABCDRead
IR40doc 30041Angle33P4W only.FLOAT32ABCDRead
IR42doc 30043Volt averageNot on 1P2W.FLOAT32ABCDRead
IR44doc 30045Volt sumNot on 1P2W.FLOAT32ABCDRead
IR46doc 30047Current averageNot on 1P2W.FLOAT32ABCDRead
IR48doc 30049Current sumNot on 1P2W.FLOAT32ABCDRead
IR50doc 30051Watt averageNot on 1P2W.FLOAT32ABCDRead
IR52doc 30053Watt sumNot on 1P2W.FLOAT32ABCDRead
IR54doc 30055VA averageNot on 1P2W.FLOAT32ABCDRead
IR56doc 30057VA sumNot on 1P2W.FLOAT32ABCDRead
IR58doc 30059VAR averageNot on 1P2W.FLOAT32ABCDRead
IR60doc 30061VAR sumNot on 1P2W.FLOAT32ABCDRead
IR62doc 30063PF averageNot on 1P2W.FLOAT32ABCDRead
IR64doc 30065PF sum3P4W and 1P3W only.FLOAT32ABCDRead
IR66doc 30067Phase angle averageNot on 1P2W.FLOAT32ABCDRead
IR68doc 30069Phase angle sumNot on 1P2W.FLOAT32ABCDRead
IR70doc 30071System frequencyFLOAT32ABCDRead
IR82doc 30083kW import demandFLOAT32ABCDRead
IR84doc 30085Max kW import demandFLOAT32ABCDRead
IR86doc 30087kW export demandFLOAT32ABCDRead
IR88doc 30089Max kW export demandFLOAT32ABCDRead
IR98doc 30099KVA demandFLOAT32ABCDRead
IR100doc 30101Max KVA demandFLOAT32ABCDRead
IR102doc 30103Current demandFLOAT32ABCDRead
IR104doc 30105Max current demandFLOAT32ABCDRead
IR136doc 30137System voltage maxFLOAT32ABCDRead
IR138doc 30139System voltage minFLOAT32ABCDRead
IR140doc 30141System RPMGenerator speed from 46039 poles.FLOAT32ABCDRead
IR142doc 30143Impulse rateFLOAT32ABCDRead
IR144doc 30145System current maxFLOAT32ABCDRead
IR146doc 30147System current minFLOAT32ABCDRead
IR200doc 30201V123P4W and 1P3W only.FLOAT32ABCDRead
IR202doc 30203V233P4W only.FLOAT32ABCDRead
IR204doc 30205V313P4W only.FLOAT32ABCDRead
IR224doc 30225Neutral current3P4W only.FLOAT32ABCDRead
IR226doc 30227Run hourFLOAT32ABCDRead
IR228doc 30229On hourFLOAT32ABCDRead
IR230doc 30231Number of interruptsFLOAT32ABCDRead
IR262doc 30263Relay 1 statusFLOAT32ABCDRead
IR500doc 30501System kW import demandFLOAT32ABCDRead
IR502doc 30503System kW export demandFLOAT32ABCDRead
IR508doc 30509System KVA demandFLOAT32ABCDRead
IR510doc 30511System current demandFLOAT32ABCDRead
IR512doc 30513System kW import max demandFLOAT32ABCDRead
IR514doc 30515System kW export max demandFLOAT32ABCDRead
IR520doc 30521System KVA max demandFLOAT32ABCDRead
IR522doc 30523System current max demandFLOAT32ABCDRead
HR6002doc 46003System typeDefault 3.FLOAT32ABCDRead/write1 = 1-phase 2-wire; 2 = 3-phase 3-wire; 3 = 3-phase 4-wire; 4 = 1-phase 3-wire
HR6004doc 46005PT primary100 V to 1200 kV L-L; default 415.FLOAT32ABCDRead/write
HR6006doc 46007CT primary1-9999; default 5.FLOAT32ABCDRead/write
HR6008doc 46009PT secondary100-500 V L-L; default 415.FLOAT32ABCDRead/write
HR6010doc 46011CT secondaryFLOAT32ABCDRead/write1 = 1 A; 5 = 5 A
HR6014doc 46015Demand timeDemand period 5-60; default 8.FLOAT32ABCDRead/write
HR6030doc 46031Reset parametersFLOAT32ABCDWrite1 = Lo (min); 2 = Hi (max); 3 = Demand; 4 = Run hour; 5 = On hour; 6 = No. of interrupts; 7 = Reset all
HR6032doc 46033Password0000-9999; reads 0 when locked, 1 when unlocked.FLOAT32ABCDRead/write
HR6034doc 46035Factory resetWrite 5555 to restore factory defaults.FLOAT32ABCDWrite
HR6038doc 46039No. of polesGenerator poles for RPM, 2-40 even.FLOAT32ABCDRead/write
HR6040doc 46041AutoscrollFLOAT32ABCDRead/write0 = Off; 1 = On
HR6042doc 46043Noise cutoffFLOAT32ABCDRead/write0 = 0 mA; 30 = 30 mA
HR6044doc 46045Comsetup (RS485 set-up code)Default 8 (9600 bps, no parity, 1 stop).FLOAT32ABCDRead/write4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop; 16 = 38400 bps, no parity, 1 stop; 17 = 38400 bps, no parity, 2 stop; 18 = 38400 bps, even, 1 stop; 19 = 38400 bps, odd, 1 stop; 20 = 57600 bps, no parity, 1 stop; 21 = 57600 bps, no parity, 2 stop; 22 = 57600 bps, even, 1 stop; 23 = 57600 bps, odd, 1 stop
HR6046doc 46047Modbus address1-247; default 1.FLOAT32ABCDRead/write
HR6048doc 46049Register order / word orderWrite 2141.0 in the wanted order to switch normal/reversed float word order.FLOAT32ABCDRead/write
HR6054doc 46055Relay 1 output selectFLOAT32ABCDRead/write0 = None; 2 = Limit output
HR6056doc 46057Limit 1 parameter selectParameter number per manual Table 2.FLOAT32ABCDRead/write
HR6058doc 46059Limit 1 configurationFLOAT32ABCDRead/write0 = Hi-alarm, energized relay; 1 = Hi-alarm, de-energized relay; 2 = Lo-alarm, energized relay; 3 = Lo-alarm, de-energized relay
HR6060doc 46061Limit 1 trip pointPercent; values per manual Table 2.FLOAT32ABCDRead/write
HR6062doc 46063Limit 1 hysteresis0.5-50 %; default 50.FLOAT32ABCDRead/write
HR6064doc 46065Limit 1 on delay1-10.FLOAT32ABCDRead/write
HR6066doc 46067Limit 1 off delay1-10.FLOAT32ABCDRead/write
HR6084doc 46085Version no.Firmware version.FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH Delta Power NX multifunction power meter

What Modbus registers does the Rishabh Instruments RISH Delta Power NX multifunction power meter have?

This map lists 89 registers: 66 input registers, 23 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH Delta Power NX multifunction power meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 3X/4X register numbers. Wire address = number - 30001 (FC04) or - 40001 (FC03/FC16): the Volts 3 example (30005) starts at 00 04 and the system-type example (46003) starts at 17 72 (6002).

What byte order does the Rishabh Instruments RISH Delta Power NX multifunction power meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH Delta Power NX multifunction power meter?

Start with IR 0 V1 (Voltage L1); IR 6 I1 (Current L1); IR 52 Watt sum (Total active power); IR 62 PF average (Average power factor); IR 70 System frequency (Frequency).

How do I enable Modbus control of the Rishabh Instruments RISH Delta Power NX multifunction power meter?

Set the Modbus address (46047, default 1) and Comsetup code (46045, default 8 = 9600 8N1) from the front panel or over Modbus.

Where is the official Rishabh Instruments RISH Delta Power NX multifunction power meter Modbus documentation?

The source is Operating Manual RISH Delta Power NX (AMAN-00IM-0117 Rev. E), revision 2024-02, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-delta-power-nx-72/RISH_Delta_POWER_NX__Manual_REV_E.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Operating Manual RISH Delta Power NX · AMAN-00IM-0117 Rev. E · rev. 2024-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.