- Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Energy meter (pulse and status concentrator) · Modbus register map
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator Modbus register map
Updated 19 November 2026
The Acti 9 Smartlink gathers status, commands and pulse counts from up to 11 Ti24 channels (iOF+SD24 auxiliaries, iACT24/iATL24, Reflex iC60, RCA iC60, pulse meters such as iEM2000T) and serves them on one Modbus RTU address. Summary blocks give all channels in one read; each channel also has a 40-register detail block. 32-bit counters are big-endian.
This page lists 80 Modbus registers for the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
- Equipment type
- Energy meter (pulse and status concentrator)
- Registers
- 80 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink
Integration notes: Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Read 120-121 for all input states, 14050-14093 for every channel's energy/pulse totals and 14000-14043 for rates; write bits in 130/131 to open or close Acti 9 devices.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 112 | Smartlink status and diagnostics | BITMAP16 | Module health | Read |
| HR 120 | Input 1 state, all channels | BITMAP16 | Input 1 state of all channels | Read |
| HR 121 | Input 2 state, all channels | BITMAP16 | Input 2 state of all channels | Read |
| HR 130 | Open order, Acti 9 products | BITMAP16 | Open orders | Read/write |
| HR 131 | Close order, Acti 9 products | BITMAP16 | Close orders | Read/write |
| HR 14050 | Ch 1 I1 consumption meter | UINT32 ABCD | Channel 1 meter total | Read |
Enable Modbus control & writes
Set the Modbus address (01-99) on the two thumbwheels. Speed, parity and stop bits are picked up from the master automatically at power-up.
Byte order & addressing
- Addresses are protocol (0-based) addresses.
- Order bits are cleared by the Smartlink once executed.
- In a channel order register (14201 / 14202), setting bit 0 and bit 1 together has no effect.
Network setup
- Thumbwheels: left = tens, right = units (01-99).
- Default 19200 baud, even parity, 1 stop bit; 4800 and 9600 also supported.
- Factory reset: power off, set address 00, power on.
Watch out for
- Auto-adaptation only happens at power-up.
- Pulse weights default to 10; set 14230/14231 per channel to match the meter.
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 112 | Smartlink status and diagnostics | Bits 0-3 are mutually exclusive modes. | BITMAP16 | Read | bit 0 = Start-up phase; bit 1 = Operating phase; bit 2 = Downgraded mode (24 V low or I/O overcurrent); bit 3 = Failure mode; bit 6 = Invalid data; bit 7 = Invalid 24 V I/O; bit 13 = EEPROM error; bit 14 = RAM error; bit 15 = FLASH error | |||
| HR | 120 | Input 1 state, all channels | Bit n-1 = channel n input I1; 1 = current flowing. | BITMAP16 | Read | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 121 | Input 2 state, all channels | Bit n-1 = channel n input I2; 1 = current flowing. | BITMAP16 | Read | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 130 | Open order, Acti 9 products | Set bit n-1 to open channel n; the Smartlink clears it when done. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 131 | Close order, Acti 9 products | Set bit n-1 to close channel n; cleared when taken into account. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 132 | Deactivation order, non-Acti 9 products | Bit n-1 = channel n. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 133 | Activation order, non-Acti 9 products | Bit n-1 = channel n. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11 | |||
| HR | 14000 | Ch 1 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14002 | Ch 2 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14004 | Ch 3 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14006 | Ch 4 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14008 | Ch 5 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14010 | Ch 6 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14012 | Ch 7 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14014 | Ch 8 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14016 | Ch 9 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14018 | Ch 10 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14020 | Ch 11 I1 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14022 | Ch 1 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14024 | Ch 2 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14026 | Ch 3 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14028 | Ch 4 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14030 | Ch 5 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14032 | Ch 6 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14034 | Ch 7 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14036 | Ch 8 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14038 | Ch 9 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14040 | Ch 10 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14042 | Ch 11 I2 power or flow indicator | Rate from the last two pulses, per hour; unit set by the connected meter. | FLOAT32 | ABCD | Read | |||
| HR | 14050 | Ch 1 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14052 | Ch 2 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14054 | Ch 3 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14056 | Ch 4 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14058 | Ch 5 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14060 | Ch 6 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14062 | Ch 7 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14064 | Ch 8 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14066 | Ch 9 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14068 | Ch 10 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14070 | Ch 11 I1 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14072 | Ch 1 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14074 | Ch 2 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14076 | Ch 3 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14078 | Ch 4 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14080 | Ch 5 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14082 | Ch 6 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14084 | Ch 7 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14086 | Ch 8 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14088 | Ch 9 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14090 | Ch 10 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14092 | Ch 11 I2 consumption meter | Pulse total times pulse weight. | UINT32 | ABCD | Read | |||
| HR | 14100 | Ch 1 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14102 | Ch 2 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14104 | Ch 3 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14106 | Ch 4 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14108 | Ch 5 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14110 | Ch 6 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14112 | Ch 7 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14114 | Ch 8 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14116 | Ch 9 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14118 | Ch 10 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14120 | Ch 11 I1 operation counter | Counts input changes from 1 to 0; writable to preset. | UINT32 | ABCD | Read/write | |||
| HR | 14144 | Ch 1 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14146 | Ch 2 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14148 | Ch 3 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14150 | Ch 4 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14152 | Ch 5 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14154 | Ch 6 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14156 | Ch 7 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14158 | Ch 8 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14160 | Ch 9 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14162 | Ch 10 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14164 | Ch 11 I1 running hours | Hours with input I1 active; writable to preset. | UINT32 | ABCD | h | Read/write | ||
| HR | 14200 | Ch 1 input status | Add 40 x (n-1) for channel n. | BITMAP16 | Read | bit 0 = Input I1 level (1 = current); bit 1 = Input I2 level (1 = current) | |||
| HR | 14201 | Ch 1 order, Acti 9 product | Add 40 x (n-1) for channel n. | BITMAP16 | Read/write | bit 0 = Close order; bit 1 = Open order | |||
| HR | 14202 | Ch 1 order, non-Acti 9 product | Add 40 x (n-1) for channel n. | BITMAP16 | Read/write | bit 0 = Deactivation order; bit 1 = Activation order | |||
| HR | 14214 | Ch 1 I2 operation counter | Add 40 x (n-1) for channel n. | UINT32 | ABCD | Read/write | |||
| HR | 14230 | Ch 1 I1 pulse weight | Default 10; add 40 x (n-1) for channel n. | UINT16 | Read/write | ||||
| HR | 14231 | Ch 1 I2 pulse weight | Default 10; add 40 x (n-1) for channel n. | UINT16 | Read/write | ||||
| HR | 20035 | Ch 1 I1 product type | Configured device on channel 1 input 1. | UINT16 | Read | 0 = None; 1 = Standard IO; 2 = Standard pulse counter; 3 = OF+SD24; 4 = iOF+SD24; 5 = Reflex iC60; 6 = RCA iC60; 7 = iACT24; 8 = iATL24; 10 = PM3210; 12 = PM3255; 13 = iEM3110; 15 = iEM3155; 16 = iEM3210; 18 = iEM3255; 19 = iEM2000T; 25 = Breaker IO; 27 = iEM3355 |
Notes on this map
- The manual states 32-bit values are big-endian: most significant word first.
- Channel n detail registers = channel 1 register + 40 x (n-1) (14200, 14240 ... 14600). Only channel 1's detail block is listed here; the summary blocks 14000-14165 cover all channels.
- Power/flow and consumption units depend on the meter on that input (Wh, m3, L ...), set by its pulse weight. The flow value drops to 0 when pulses stop.
- Left out: identification strings (100, 109), date/time (115) and counter setting dates (DATE type), and the embedded configuration blocks beyond the channel 1 product type.
- The Smartlink adapts to the master's baud and parity after up to 25 frames at power-up; with no parity it needs 2 stop bits.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
What Modbus registers does the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator have?
This map lists 80 registers: 80 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modbus protocol addresses, which start at 0, and says a master that uses data-model numbering must add 1. Its frame example reads address 14050 as 0x36E2.
What byte order does the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator?
Start with HR 112 Smartlink status and diagnostics (Module health); HR 120 Input 1 state, all channels (Input 1 state of all channels); HR 121 Input 2 state, all channels (Input 2 state of all channels); HR 130 Open order, Acti 9 products (Open orders); HR 131 Close order, Acti 9 products (Close orders); HR 14050 Ch 1 I1 consumption meter (Channel 1 meter total).
How do I enable Modbus control of the Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator?
Set the Modbus address (01-99) on the two thumbwheels. Speed, parity and stop bits are picked up from the master automatically at power-up.
Where is the official Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator Modbus documentation?
The source is Acti 9 Smartlink Modbus Communication System - User Manual (DOCA0004EN-06), revision 2016-04, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0004EN.
More Schneider Electric Modbus register maps
- Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Other power & energy meters register maps
- Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Power meter
Accuenergy Acuvim II Series
Accuenergy Acuvim II series multifunction power meters (manual 1040E1303, V3.2.16 revised September 2026).
Also known as: Acuvim IIR, Acuvim IIW - Energy meter (DC)
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
DCM1 300 A / 600 A, 1000 V DC meters (MID, Eichrecht and LNE variants) with RS485 and Ethernet, protocol version 1.11.
Also known as: DCM1A60V10L20S1PFA, DCM1A60V10L20S1PFB, DCM1A60V10L20S2DEB, DCM1A60V10L20S3DEB, DCM1A60V10L20S2DEBF, DCM1A60V10L20S3DEBF, DCM1A30V10L20S1PFA, DCM1A30V10L20S1PFB, DCM1A30V10L20S2DEB, DCM1A30V10L20S3DEB, DCM1A30V10L20S2DEBF, DCM1A30V10L20S3DEBF, DCM1A60V10L20S1ULB, DCM1A30V10L20S1ULB - Energy meter
Carlo Gavazzi EM270 / EM280 dual three-phase energy meters with TCD current sensors
EM270 X (firmware r.b0+), EM270 W (r.C0+) and EM280 (r.E0+) on RS485 Modbus RTU, per communication protocol version 5 revision 1 (2018-01-29).
Also known as: EM270, EM280, EM270 X, EM270 W, EM27072DMV53X2SX, EM28072DMV53X2SX
All power & energy meters Modbus register maps →
Source: Acti 9 Smartlink Modbus Communication System - User Manual · DOCA0004EN-06 · rev. 2016-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.