Solar inverter · Modbus register map

Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus register map

Updated 17 November 2026

Short answer

The Conext Core XC is a grid-tied three-phase PV inverter with an RS-485 Modbus RTU port. All values are 16-bit integers with a fixed multiplier, read with function 03 and written with function 16. This map covers the read-only monitoring block (0x1700-0x1828), ratings and grid-code settings, the main power-limit and remote enable/disable controls, Modbus port settings and the log-reading registers.

This page lists 125 Modbus registers for the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Equipment type
Solar inverter
Registers
125 (24 writable)
Transport
Modbus RTU
Default unit ID
247
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
Firmware
v1.07 and later (individual registers list a minimum firmware, e.g. v3.01, v5.00)
Also known as
0G-XC-BB, XC-AIC15P
Source document
Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note · AP-XC-095 Revision A · rev. 2017-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)

Integration in brief

Poll 0x1700-0x1828 with function 03 for state, grid voltages and currents, active/reactive power and PV values (all 16-bit, divide by the listed factor). To control power, set Parameter Control Station (0xE0E0) to 2 = Modbus, then write the active power limit at 0xFA19 with function 16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 5888Operational Mode StateUINT16Operating mode and stateRead
HR 6142Active PowerINT16Active power, kW x10Read
HR 6145PV PowerINT16PV powerRead
HR 6136Grid Voltage V12INT16Grid voltage V12Read
HR 6146Grid FrequencyINT16Grid frequencyRead
HR 6184Alarm CodeUINT16Active alarm codeRead
HR 57568Parameter Control StationUINT16Hand settings control to ModbusRead/write
HR 64025User Active Power LimitINT16User active power limitRead/write

Enable Modbus control & writes

On the front panel go to 2 Language, Time, Interface > Comm. Interface > Parameter Control Station and select panel control to set the Modbus address and baud rate, then power-cycle with QF2. For writes, set register 0xE0E0 to 2 (Modbus).

Byte order & addressing

Network setup

Watch out for

Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

125 of 125 shown
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR5888doc 0x1700Operational Mode StateHigh byte = enable mode, low byte = state.UINT16Read0 = PV mode offline; 1 = PV mode reconnecting; 2 = PV mode online; 256 = CP mode offline; 257 = CP mode reconnecting; 258 = CP mode online; 512 = PVCQ mode offline; 513 = PVCQ mode reconnecting; 514 = PVCQ mode online
HR5889doc 0x1701Temperature Power BoardINT16× 0.1°CRead
HR5890doc 0x1702Temperature Heatsink1INT16× 0.1°CRead
HR5891doc 0x1703Temperature Heatsink2INT16× 0.1°CRead
HR5892doc 0x1704Temperature Heatsink3INT16× 0.1°CRead
HR5893doc 0x1705Grid CurrentINT16× 0.1ArmsRead
HR6129doc 0x17F1Apparent PowerUINT16× 0.1kVARead
HR6132doc 0x17F4Reactive PowerINT16× 0.1kVArRead
HR6136doc 0x17F8Grid Voltage V12INT16× 0.1VrmsRead
HR6137doc 0x17F9Grid Voltage V23INT16× 0.1VrmsRead
HR6138doc 0x17FAGrid Voltage V31INT16× 0.1VrmsRead
HR6139doc 0x17FBGrid Current Line1INT16× 0.1ArmsRead
HR6140doc 0x17FCGrid Current Line2INT16× 0.1ArmsRead
HR6141doc 0x17FDGrid Current Line3INT16× 0.1ArmsRead
HR6142doc 0x17FEActive PowerINT16× 0.1kWRead
HR6143doc 0x17FFPV VoltageINT16× 0.1VDCRead
HR6144doc 0x1800PV CurrentINT16× 0.1ADCRead
HR6145doc 0x1801PV PowerINT16× 0.1kWRead
HR6146doc 0x1802Grid FrequencyINT16× 0.1HzRead
HR6147doc 0x1803Grid Frequency (Hi Res)INT16× 0.01HzRead
HR6157doc 0x180DDC VoltageINT16× 0.1VDCRead
HR6158doc 0x180EThermal LoadingUINT16× 0.1%Read
HR6168doc 0x1818Phase A FrequencyUINT16× 0.1HzRead
HR6169doc 0x1819Phase B FrequencyUINT16× 0.1HzRead
HR6170doc 0x181APhase C FrequencyUINT16× 0.1HzRead
HR6171doc 0x181BPhase A Real PowerINT16× 0.1kWRead
HR6172doc 0x181CPhase B Real PowerINT16× 0.1kWRead
HR6173doc 0x181DPhase C Real PowerINT16× 0.1kWRead
HR6174doc 0x181EPhase A Reactive PowerINT16× 0.1kVArRead
HR6175doc 0x181FPhase B Reactive PowerINT16× 0.1kVArRead
HR6176doc 0x1820Phase C Reactive PowerINT16× 0.1kVArRead
HR6177doc 0x1821Phase A Apparent PowerUINT16× 0.1kVARead
HR6178doc 0x1822Phase B Apparent PowerUINT16× 0.1kVARead
HR6179doc 0x1823Phase C Apparent PowerUINT16× 0.1kVARead
HR6182doc 0x1826Event CodeUINT16Read
HR6183doc 0x1827System StateUINT16Read0 = Initializing; 1 = Disable; 2 = Enable; 3 = Service
HR6184doc 0x1828Alarm CodeUINT16Read
HR16393doc 0x4009Day Log RateUINT16minRead
HR16394doc 0x400AFirst Daytime HourUINT16hRead
HR16395doc 0x400BNight Log RateUINT16minRead
HR16396doc 0x400CFirst Nighttime HourUINT16hRead
HR16476doc 0x405CGrid Voltage12 Gain CalibrationUINT16× 0.001Read
HR16477doc 0x405DGrid Voltage23 Gain CalibrationUINT16× 0.001Read
HR16478doc 0x405EGrid Voltage31 Gain CalibrationUINT16× 0.001Read
HR16479doc 0x405FGrid Voltage12 Offset CalibrationINT16× 0.1VRead
HR16480doc 0x4060Grid Voltage23 Offset CalibrationINT16× 0.1VRead
HR16481doc 0x4061Grid Voltage31 Offset CalibrationINT16× 0.1VRead
HR16482doc 0x4062Gain kVAr InductiveUINT16× 0.1(V2/kVAr*Hz)Read
HR16483doc 0x4063Gain kVAr CapacitiveUINT16× 0.1(V2/kVAr*Hz)Read
HR16526doc 0x408EDisconnect ProfileUINT16Read
HR16527doc 0x408FP-analog Filter TimeUINT16× 0.01sRead
HR16528doc 0x4090Q-analog Filter TimeUINT16× 0.01sRead
HR16529doc 0x4091I1 Gain CalUINT16× 0.001sRead
HR16530doc 0x4092I2 Gain CalUINT16× 0.001sRead
HR16531doc 0x4093I3 Gain CalUINT16× 0.001sRead
HR16532doc 0x4094I1 Offset CalUINT16× 0.1sRead
HR16533doc 0x4095I2 Offset CalUINT16× 0.1sRead
HR16534doc 0x4096I3 Offset CalUINT16× 0.1sRead
HR16535doc 0x4097Analog Error SuppressedUINT16Read/write0 = Off; 1 = Suppress P error; 2 = Suppress Q error; 3 = Suppress P and Q error
HR16536doc 0x4098Modbus User P ReadoutUINT16× 0.1kWRead
HR16537doc 0x4099Modbus User Q ReadoutUINT16× 0.1kVArRead
HR16538doc 0x409AAnalog P Signal ReadoutUINT16× 0.1mARead
HR16539doc 0x409BAnalog Q Signal ReadoutUINT16× 0.1mARead
HR16563doc 0x40B3AI Disconn LF ThresholdUINT16× 0.01HzRead
HR16564doc 0x40B4AI Disconn LF DelayUINT16× 0.01sRead
HR16565doc 0x40B5AI LF Disconn FunctionUINT16Read
HR18176doc 0x4700Number of Data Log RecordsUp to 1861 records.UINT16Read
HR18177doc 0x4701Number of Event Log RecordsUp to 8192 records.UINT16Read
HR18178doc 0x4702Number of Fault Log RecordsUp to 910 records.UINT16Read
HR18179doc 0x4703Log Request IndexRecord to fetch; 1 = most recent.UINT16Read/write
HR18180doc 0x4704Log Response IndexEquals the request index when the buffer is ready.UINT16Read
HR18181doc 0x4705Logger Mode0 log, 1 data, 2 event, 3 service, 4 oscillography, 5 config.UINT16Read/write0 = Log mode; 1 = Read data log; 2 = Read event log; 3 = Read service log; 4 = Read oscillography; 5 = Config mode
HR18182doc 0x4706Logger StateLogger status flags.BITMAP16Readbit 0 = Board not ready; bit 1 = Log mode active; bit 2 = Read mode active; bit 3 = Config mode active; bit 8 = RTC battery low; bit 9 = NVRAM record CRC error; bit 10 = Other RTC error
HR32771doc 0x8003Modbus Unit IDModbus unit ID; takes effect after a system reset.UINT16Read/write
HR32784doc 0x8010Baud RateUINT16Read/write24 = 4800 baud; 28 = 9600 baud; 32 = 19200 baud; 36 = 38400 baud; 40 = 57600 baud
HR57568doc 0xE0E0Parameter Control StationUINT16Read/write1 = PANELCONTROL; 2 = MODBUS
HR57569doc 0xE0E1Commit Modbus SettingsUINT16Write1 = COMMIT
HR61438doc 0xEFFERemote Disable/EnableUINT16Write0 = Remote start; 1 = Remote shutdown
HR63489doc 0xF801Rated Input (PV) CurrentUINT16ARead
HR63490doc 0xF802Maximum Input (PV) VoltageUINT16VDCRead
HR63491doc 0xF803Max Tracking VoltUINT16VRead/write
HR63492doc 0xF804Min Tracking VoltUINT16VRead/write
HR63493doc 0xF805Max PV OC VoltageUINT16VDCRead
HR63494doc 0xF806Max STC PV-SC CurrentUINT16ADCRead
HR63495doc 0xF807Rated Apparent PowerUINT16× 0.1kVARead
HR63496doc 0xF808Rated Powerat Unity PFINT16× 0.1kWRead
HR63497doc 0xF809Min Input (PV) VoltageUINT16VDCRead
HR63498doc 0xF80ANominal L-to-L VoltageUINT16VrmsRead
HR63499doc 0xF80BNominal Line CurrentUINT16ArmsRead
HR63500doc 0xF80CRated Reactive PowerINT16× 0.1kVArRead
HR63990doc 0xF9F6P(f) Control FunctionUINT16Read/write0 = Off; 1 = P(f) type 1; 2 = P(f) type 2
HR64009doc 0xFA09Grid Reconnection DelayUINT16sRead/write
HR64011doc 0xFA0BDisconn HV ThresholdUINT16%Read
HR64012doc 0xFA0CDisconn LV ThresholdUINT16%Read
HR64015doc 0xFA0FDisconn HF ThresholdUINT16× 0.01HzRead
HR64016doc 0xFA10Disconn LF ThresholdUINT16× 0.01HzRead
HR64025doc 0xFA19User Active Power LimitCan be written while the inverter is enabled.INT16× 0.1kWRead/write
HR64026doc 0xFA1AActive Anti-Islanding FunctionUINT16Read0 = OFF; 1 = ON
HR64027doc 0xFA1BUser Reactive Power ReferenceCan be written while the inverter is enabled.INT16× 0.1kVArRead/write
HR64029doc 0xFA1DUser Apparent Power LimitCan be written while the inverter is enabled.UINT16× 0.1kVARead/write
HR64030doc 0xFA1EUser Phase Current LimitCan be written while the inverter is enabled.UINT16%Read/write
HR64031doc 0xFA1FUtility RegionUINT16Read
HR64032doc 0xFA20LanguageUINT16Read/write0 = English; 1 = German; 2 = Spanish; 3 = French; 4 = Italian; 6 = Custom 1; 7 = Custom 2
HR64036doc 0xFA24Voltage Support FunctionUINT16Read/write0 = OFF; 1 = ON
HR64053doc 0xFA35Power Ref. Ramp TimeUINT16msRead/write
HR64054doc 0xFA36System L-to-L VoltageUINT16VrmsRead
HR64055doc 0xFA37Disconnvery HV ThresholdUINT16%Read
HR64058doc 0xFA3ADisconnvery LV ThresholdUINT16%Read
HR64061doc 0xFA3DDisconnvery LF ThresholdUINT16× 0.01HzRead
HR64064doc 0xFA40Disconnvery HF ThresholdUINT16× 0.01HzRead
HR64070doc 0xFA46Reconn Power Ramp TimeUINT16sRead/write
HR64072doc 0xFA48Power Reference SelectionUINT16Read/write0 = MODBUS; 1 = ANALOGINPUT
HR64264doc 0xFB08DC Cap Surge AccumUINT16minRead
HR64272doc 0xFB10Voltage Envelope ThresholdUINT16%Read
HR64273doc 0xFB11Voltage Envelope DelayUINT16SamplesRead
HR64305doc 0xFB31DC Switch Open CountUINT16Read
HR64306doc 0xFB32AC Switch Open CountUINT16Read
HR64344doc 0xFB58Vac-RegulationUINT16Read/write0 = Off; 1 = Q(V); 2 = Phi(P)
HR64354doc 0xFB62Power Ramp RateUINT16× 0.1%/minRead/write
HR64355doc 0xFB63Min. Power Ramp StepUINT16× 0.1kWRead
HR64413doc 0xFB9DCQ ModeUINT16Read/write0 = OFF; 1 = ON
HR64415doc 0xFB9FDevice Active StatusBITMAP16Readbit 0 = AC breaker closed; bit 1 = DC switch closed; bit 2 = Fan in test mode
HR64419doc 0xFBA3CountdownUINT16Read
HR64466doc 0xFBD2Max Daily Online CyclingUINT16Read
HR64474doc 0xFBDAFan SpeedUINT16× 0.1VRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)

What Modbus registers does the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) have?

This map lists 125 registers: 125 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The application note says register addresses are zero based, printed in hex, and go straight into the request's address field. A master that wants register numbers must convert to decimal and add 1.

What are the minimum Modbus registers to integrate the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)?

Start with HR 5888 Operational Mode State (Operating mode and state); HR 6142 Active Power (Active power, kW x10); HR 6145 PV Power (PV power); HR 6136 Grid Voltage V12 (Grid voltage V12); HR 6146 Grid Frequency (Grid frequency); HR 6184 Alarm Code (Active alarm code); HR 57568 Parameter Control Station (Hand settings control to Modbus); HR 64025 User Active Power Limit (User active power limit).

How do I enable Modbus control of the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)?

On the front panel go to 2 Language, Time, Interface > Comm. Interface > Parameter Control Station and select panel control to set the Modbus address and baud rate, then power-cycle with QF2. For writes, set register 0xE0E0 to 2 (Modbus).

Where is the official Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus documentation?

The source is Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note (AP-XC-095 Revision A), revision 2017-01, published free by Schneider Electric at https://solar.se.com/eu/wp-content/uploads/sites/4/2021/12/TP20170101_Conext-Core-XC-Using-Modbus-App-NoteAP-XC-095.pdf.

More Schneider Electric Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note · AP-XC-095 Revision A · rev. 2017-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.