Solar inverter · Modbus register map
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus register map
Updated 17 November 2026
The Conext Core XC is a grid-tied three-phase PV inverter with an RS-485 Modbus RTU port. All values are 16-bit integers with a fixed multiplier, read with function 03 and written with function 16. This map covers the read-only monitoring block (0x1700-0x1828), ratings and grid-code settings, the main power-limit and remote enable/disable controls, Modbus port settings and the log-reading registers.
This page lists 125 Modbus registers for the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
- Equipment type
- Solar inverter
- Registers
- 125 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- 247
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Firmware
- v1.07 and later (individual registers list a minimum firmware, e.g. v3.01, v5.00)
- Also known as
- 0G-XC-BB, XC-AIC15P
Integration notes: Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Poll 0x1700-0x1828 with function 03 for state, grid voltages and currents, active/reactive power and PV values (all 16-bit, divide by the listed factor). To control power, set Parameter Control Station (0xE0E0) to 2 = Modbus, then write the active power limit at 0xFA19 with function 16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 5888 | Operational Mode State | UINT16 | Operating mode and state | Read |
| HR 6142 | Active Power | INT16 | Active power, kW x10 | Read |
| HR 6145 | PV Power | INT16 | PV power | Read |
| HR 6136 | Grid Voltage V12 | INT16 | Grid voltage V12 | Read |
| HR 6146 | Grid Frequency | INT16 | Grid frequency | Read |
| HR 6184 | Alarm Code | UINT16 | Active alarm code | Read |
| HR 57568 | Parameter Control Station | UINT16 | Hand settings control to Modbus | Read/write |
| HR 64025 | User Active Power Limit | INT16 | User active power limit | Read/write |
Enable Modbus control & writes
On the front panel go to 2 Language, Time, Interface > Comm. Interface > Parameter Control Station and select panel control to set the Modbus address and baud rate, then power-cycle with QF2. For writes, set register 0xE0E0 to 2 (Modbus).
Byte order & addressing
- Addresses are hex and zero based; a master that counts from 1 must add one.
- Only function codes 03, 16, 08 (sub-function 00) and 43 are supported; there is no FC06 single-register write.
- Changing the Modbus unit ID (0xE0E1 commit, 0x8003) needs a system reset before it takes effect.
Network setup
- Default RS-485 settings: 19200 baud, 8 data bits, even parity, 1 stop bit; all inverters on one bus must use the same settings.
- Do not use 57600 baud if the Vigilohm IM400 is installed (it only supports 38400).
Watch out for
- Reading an unmapped address returns 0xFFFF with no exception, so a wrong address can look like a valid value.
- Leaving Logger Mode (0x4705) in any read mode stops data logging; set it back to 0.
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 5888doc 0x1700 | Operational Mode State | High byte = enable mode, low byte = state. | UINT16 | Read | 0 = PV mode offline; 1 = PV mode reconnecting; 2 = PV mode online; 256 = CP mode offline; 257 = CP mode reconnecting; 258 = CP mode online; 512 = PVCQ mode offline; 513 = PVCQ mode reconnecting; 514 = PVCQ mode online | |||
| HR | 5889doc 0x1701 | Temperature Power Board | INT16 | × 0.1 | °C | Read | |||
| HR | 5890doc 0x1702 | Temperature Heatsink1 | INT16 | × 0.1 | °C | Read | |||
| HR | 5891doc 0x1703 | Temperature Heatsink2 | INT16 | × 0.1 | °C | Read | |||
| HR | 5892doc 0x1704 | Temperature Heatsink3 | INT16 | × 0.1 | °C | Read | |||
| HR | 5893doc 0x1705 | Grid Current | INT16 | × 0.1 | Arms | Read | |||
| HR | 6129doc 0x17F1 | Apparent Power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 6132doc 0x17F4 | Reactive Power | INT16 | × 0.1 | kVAr | Read | |||
| HR | 6136doc 0x17F8 | Grid Voltage V12 | INT16 | × 0.1 | Vrms | Read | |||
| HR | 6137doc 0x17F9 | Grid Voltage V23 | INT16 | × 0.1 | Vrms | Read | |||
| HR | 6138doc 0x17FA | Grid Voltage V31 | INT16 | × 0.1 | Vrms | Read | |||
| HR | 6139doc 0x17FB | Grid Current Line1 | INT16 | × 0.1 | Arms | Read | |||
| HR | 6140doc 0x17FC | Grid Current Line2 | INT16 | × 0.1 | Arms | Read | |||
| HR | 6141doc 0x17FD | Grid Current Line3 | INT16 | × 0.1 | Arms | Read | |||
| HR | 6142doc 0x17FE | Active Power | INT16 | × 0.1 | kW | Read | |||
| HR | 6143doc 0x17FF | PV Voltage | INT16 | × 0.1 | VDC | Read | |||
| HR | 6144doc 0x1800 | PV Current | INT16 | × 0.1 | ADC | Read | |||
| HR | 6145doc 0x1801 | PV Power | INT16 | × 0.1 | kW | Read | |||
| HR | 6146doc 0x1802 | Grid Frequency | INT16 | × 0.1 | Hz | Read | |||
| HR | 6147doc 0x1803 | Grid Frequency (Hi Res) | INT16 | × 0.01 | Hz | Read | |||
| HR | 6157doc 0x180D | DC Voltage | INT16 | × 0.1 | VDC | Read | |||
| HR | 6158doc 0x180E | Thermal Loading | UINT16 | × 0.1 | % | Read | |||
| HR | 6168doc 0x1818 | Phase A Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 6169doc 0x1819 | Phase B Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 6170doc 0x181A | Phase C Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 6171doc 0x181B | Phase A Real Power | INT16 | × 0.1 | kW | Read | |||
| HR | 6172doc 0x181C | Phase B Real Power | INT16 | × 0.1 | kW | Read | |||
| HR | 6173doc 0x181D | Phase C Real Power | INT16 | × 0.1 | kW | Read | |||
| HR | 6174doc 0x181E | Phase A Reactive Power | INT16 | × 0.1 | kVAr | Read | |||
| HR | 6175doc 0x181F | Phase B Reactive Power | INT16 | × 0.1 | kVAr | Read | |||
| HR | 6176doc 0x1820 | Phase C Reactive Power | INT16 | × 0.1 | kVAr | Read | |||
| HR | 6177doc 0x1821 | Phase A Apparent Power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 6178doc 0x1822 | Phase B Apparent Power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 6179doc 0x1823 | Phase C Apparent Power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 6182doc 0x1826 | Event Code | UINT16 | Read | |||||
| HR | 6183doc 0x1827 | System State | UINT16 | Read | 0 = Initializing; 1 = Disable; 2 = Enable; 3 = Service | ||||
| HR | 6184doc 0x1828 | Alarm Code | UINT16 | Read | |||||
| HR | 16393doc 0x4009 | Day Log Rate | UINT16 | min | Read | ||||
| HR | 16394doc 0x400A | First Daytime Hour | UINT16 | h | Read | ||||
| HR | 16395doc 0x400B | Night Log Rate | UINT16 | min | Read | ||||
| HR | 16396doc 0x400C | First Nighttime Hour | UINT16 | h | Read | ||||
| HR | 16476doc 0x405C | Grid Voltage12 Gain Calibration | UINT16 | × 0.001 | Read | ||||
| HR | 16477doc 0x405D | Grid Voltage23 Gain Calibration | UINT16 | × 0.001 | Read | ||||
| HR | 16478doc 0x405E | Grid Voltage31 Gain Calibration | UINT16 | × 0.001 | Read | ||||
| HR | 16479doc 0x405F | Grid Voltage12 Offset Calibration | INT16 | × 0.1 | V | Read | |||
| HR | 16480doc 0x4060 | Grid Voltage23 Offset Calibration | INT16 | × 0.1 | V | Read | |||
| HR | 16481doc 0x4061 | Grid Voltage31 Offset Calibration | INT16 | × 0.1 | V | Read | |||
| HR | 16482doc 0x4062 | Gain kVAr Inductive | UINT16 | × 0.1 | (V2/kVAr*Hz) | Read | |||
| HR | 16483doc 0x4063 | Gain kVAr Capacitive | UINT16 | × 0.1 | (V2/kVAr*Hz) | Read | |||
| HR | 16526doc 0x408E | Disconnect Profile | UINT16 | Read | |||||
| HR | 16527doc 0x408F | P-analog Filter Time | UINT16 | × 0.01 | s | Read | |||
| HR | 16528doc 0x4090 | Q-analog Filter Time | UINT16 | × 0.01 | s | Read | |||
| HR | 16529doc 0x4091 | I1 Gain Cal | UINT16 | × 0.001 | s | Read | |||
| HR | 16530doc 0x4092 | I2 Gain Cal | UINT16 | × 0.001 | s | Read | |||
| HR | 16531doc 0x4093 | I3 Gain Cal | UINT16 | × 0.001 | s | Read | |||
| HR | 16532doc 0x4094 | I1 Offset Cal | UINT16 | × 0.1 | s | Read | |||
| HR | 16533doc 0x4095 | I2 Offset Cal | UINT16 | × 0.1 | s | Read | |||
| HR | 16534doc 0x4096 | I3 Offset Cal | UINT16 | × 0.1 | s | Read | |||
| HR | 16535doc 0x4097 | Analog Error Suppressed | UINT16 | Read/write | 0 = Off; 1 = Suppress P error; 2 = Suppress Q error; 3 = Suppress P and Q error | ||||
| HR | 16536doc 0x4098 | Modbus User P Readout | UINT16 | × 0.1 | kW | Read | |||
| HR | 16537doc 0x4099 | Modbus User Q Readout | UINT16 | × 0.1 | kVAr | Read | |||
| HR | 16538doc 0x409A | Analog P Signal Readout | UINT16 | × 0.1 | mA | Read | |||
| HR | 16539doc 0x409B | Analog Q Signal Readout | UINT16 | × 0.1 | mA | Read | |||
| HR | 16563doc 0x40B3 | AI Disconn LF Threshold | UINT16 | × 0.01 | Hz | Read | |||
| HR | 16564doc 0x40B4 | AI Disconn LF Delay | UINT16 | × 0.01 | s | Read | |||
| HR | 16565doc 0x40B5 | AI LF Disconn Function | UINT16 | Read | |||||
| HR | 18176doc 0x4700 | Number of Data Log Records | Up to 1861 records. | UINT16 | Read | ||||
| HR | 18177doc 0x4701 | Number of Event Log Records | Up to 8192 records. | UINT16 | Read | ||||
| HR | 18178doc 0x4702 | Number of Fault Log Records | Up to 910 records. | UINT16 | Read | ||||
| HR | 18179doc 0x4703 | Log Request Index | Record to fetch; 1 = most recent. | UINT16 | Read/write | ||||
| HR | 18180doc 0x4704 | Log Response Index | Equals the request index when the buffer is ready. | UINT16 | Read | ||||
| HR | 18181doc 0x4705 | Logger Mode | 0 log, 1 data, 2 event, 3 service, 4 oscillography, 5 config. | UINT16 | Read/write | 0 = Log mode; 1 = Read data log; 2 = Read event log; 3 = Read service log; 4 = Read oscillography; 5 = Config mode | |||
| HR | 18182doc 0x4706 | Logger State | Logger status flags. | BITMAP16 | Read | bit 0 = Board not ready; bit 1 = Log mode active; bit 2 = Read mode active; bit 3 = Config mode active; bit 8 = RTC battery low; bit 9 = NVRAM record CRC error; bit 10 = Other RTC error | |||
| HR | 32771doc 0x8003 | Modbus Unit ID | Modbus unit ID; takes effect after a system reset. | UINT16 | Read/write | ||||
| HR | 32784doc 0x8010 | Baud Rate | UINT16 | Read/write | 24 = 4800 baud; 28 = 9600 baud; 32 = 19200 baud; 36 = 38400 baud; 40 = 57600 baud | ||||
| HR | 57568doc 0xE0E0 | Parameter Control Station | UINT16 | Read/write | 1 = PANELCONTROL; 2 = MODBUS | ||||
| HR | 57569doc 0xE0E1 | Commit Modbus Settings | UINT16 | Write | 1 = COMMIT | ||||
| HR | 61438doc 0xEFFE | Remote Disable/Enable | UINT16 | Write | 0 = Remote start; 1 = Remote shutdown | ||||
| HR | 63489doc 0xF801 | Rated Input (PV) Current | UINT16 | A | Read | ||||
| HR | 63490doc 0xF802 | Maximum Input (PV) Voltage | UINT16 | VDC | Read | ||||
| HR | 63491doc 0xF803 | Max Tracking Volt | UINT16 | V | Read/write | ||||
| HR | 63492doc 0xF804 | Min Tracking Volt | UINT16 | V | Read/write | ||||
| HR | 63493doc 0xF805 | Max PV OC Voltage | UINT16 | VDC | Read | ||||
| HR | 63494doc 0xF806 | Max STC PV-SC Current | UINT16 | ADC | Read | ||||
| HR | 63495doc 0xF807 | Rated Apparent Power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 63496doc 0xF808 | Rated Powerat Unity PF | INT16 | × 0.1 | kW | Read | |||
| HR | 63497doc 0xF809 | Min Input (PV) Voltage | UINT16 | VDC | Read | ||||
| HR | 63498doc 0xF80A | Nominal L-to-L Voltage | UINT16 | Vrms | Read | ||||
| HR | 63499doc 0xF80B | Nominal Line Current | UINT16 | Arms | Read | ||||
| HR | 63500doc 0xF80C | Rated Reactive Power | INT16 | × 0.1 | kVAr | Read | |||
| HR | 63990doc 0xF9F6 | P(f) Control Function | UINT16 | Read/write | 0 = Off; 1 = P(f) type 1; 2 = P(f) type 2 | ||||
| HR | 64009doc 0xFA09 | Grid Reconnection Delay | UINT16 | s | Read/write | ||||
| HR | 64011doc 0xFA0B | Disconn HV Threshold | UINT16 | % | Read | ||||
| HR | 64012doc 0xFA0C | Disconn LV Threshold | UINT16 | % | Read | ||||
| HR | 64015doc 0xFA0F | Disconn HF Threshold | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64016doc 0xFA10 | Disconn LF Threshold | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64025doc 0xFA19 | User Active Power Limit | Can be written while the inverter is enabled. | INT16 | × 0.1 | kW | Read/write | ||
| HR | 64026doc 0xFA1A | Active Anti-Islanding Function | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 64027doc 0xFA1B | User Reactive Power Reference | Can be written while the inverter is enabled. | INT16 | × 0.1 | kVAr | Read/write | ||
| HR | 64029doc 0xFA1D | User Apparent Power Limit | Can be written while the inverter is enabled. | UINT16 | × 0.1 | kVA | Read/write | ||
| HR | 64030doc 0xFA1E | User Phase Current Limit | Can be written while the inverter is enabled. | UINT16 | % | Read/write | |||
| HR | 64031doc 0xFA1F | Utility Region | UINT16 | Read | |||||
| HR | 64032doc 0xFA20 | Language | UINT16 | Read/write | 0 = English; 1 = German; 2 = Spanish; 3 = French; 4 = Italian; 6 = Custom 1; 7 = Custom 2 | ||||
| HR | 64036doc 0xFA24 | Voltage Support Function | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 64053doc 0xFA35 | Power Ref. Ramp Time | UINT16 | ms | Read/write | ||||
| HR | 64054doc 0xFA36 | System L-to-L Voltage | UINT16 | Vrms | Read | ||||
| HR | 64055doc 0xFA37 | Disconnvery HV Threshold | UINT16 | % | Read | ||||
| HR | 64058doc 0xFA3A | Disconnvery LV Threshold | UINT16 | % | Read | ||||
| HR | 64061doc 0xFA3D | Disconnvery LF Threshold | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64064doc 0xFA40 | Disconnvery HF Threshold | UINT16 | × 0.01 | Hz | Read | |||
| HR | 64070doc 0xFA46 | Reconn Power Ramp Time | UINT16 | s | Read/write | ||||
| HR | 64072doc 0xFA48 | Power Reference Selection | UINT16 | Read/write | 0 = MODBUS; 1 = ANALOGINPUT | ||||
| HR | 64264doc 0xFB08 | DC Cap Surge Accum | UINT16 | min | Read | ||||
| HR | 64272doc 0xFB10 | Voltage Envelope Threshold | UINT16 | % | Read | ||||
| HR | 64273doc 0xFB11 | Voltage Envelope Delay | UINT16 | Samples | Read | ||||
| HR | 64305doc 0xFB31 | DC Switch Open Count | UINT16 | Read | |||||
| HR | 64306doc 0xFB32 | AC Switch Open Count | UINT16 | Read | |||||
| HR | 64344doc 0xFB58 | Vac-Regulation | UINT16 | Read/write | 0 = Off; 1 = Q(V); 2 = Phi(P) | ||||
| HR | 64354doc 0xFB62 | Power Ramp Rate | UINT16 | × 0.1 | %/min | Read/write | |||
| HR | 64355doc 0xFB63 | Min. Power Ramp Step | UINT16 | × 0.1 | kW | Read | |||
| HR | 64413doc 0xFB9D | CQ Mode | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 64415doc 0xFB9F | Device Active Status | BITMAP16 | Read | bit 0 = AC breaker closed; bit 1 = DC switch closed; bit 2 = Fan in test mode | ||||
| HR | 64419doc 0xFBA3 | Countdown | UINT16 | Read | |||||
| HR | 64466doc 0xFBD2 | Max Daily Online Cycling | UINT16 | Read | |||||
| HR | 64474doc 0xFBDA | Fan Speed | UINT16 | × 0.1 | V | Read |
Notes on this map
- Scale: the document gives units as 'unit/xN', meaning divide the raw value by N; this is converted to scale = 1/N.
- Left out: the 32-bit items (kWh Energy Produced 0x0802-0x0803, Energy Today 0x0804-0x0805, Operating Hours 0x081E-0x081F and Time 0xFA21-0xFA22) because the note does not state their word order; the text product designation, assembly and serial number blocks (0x1-0x1D, typed uchar8); and the log buffer registers.
- Only a selection of the writable registers in Table 18 is included (enable/disable, power and phase-current limits, power reference source, MPPT voltage window, port settings and a few grid-support switches). The many grid-code thresholds and delays are left out.
- Registers flagged ** in the note can be written while the inverter is enabled; the rest need the inverter disabled.
- Unmapped addresses inside a block read 0xFFFF without an error; writing one returns an illegal address exception.
- The note's Table 20/21 for the optional Vigilohm IM400 insulation monitor is a separate device and is not part of this map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
What Modbus registers does the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) have?
This map lists 125 registers: 125 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The application note says register addresses are zero based, printed in hex, and go straight into the request's address field. A master that wants register numbers must convert to decimal and add 1.
What are the minimum Modbus registers to integrate the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)?
Start with HR 5888 Operational Mode State (Operating mode and state); HR 6142 Active Power (Active power, kW x10); HR 6145 PV Power (PV power); HR 6136 Grid Voltage V12 (Grid voltage V12); HR 6146 Grid Frequency (Grid frequency); HR 6184 Alarm Code (Active alarm code); HR 57568 Parameter Control Station (Hand settings control to Modbus); HR 64025 User Active Power Limit (User active power limit).
How do I enable Modbus control of the Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)?
On the front panel go to 2 Language, Time, Interface > Comm. Interface > Parameter Control Station and select panel control to set the Modbus address and baud rate, then power-cycle with QF2. For writes, set register 0xE0E0 to 2 (Modbus).
Where is the official Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB) Modbus documentation?
The source is Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note (AP-XC-095 Revision A), revision 2017-01, published free by Schneider Electric at https://solar.se.com/eu/wp-content/uploads/sites/4/2021/12/TP20170101_Conext-Core-XC-Using-Modbus-App-NoteAP-XC-095.pdf.
More Schneider Electric Modbus register maps
- Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Other solar & battery inverters register maps
- Solar inverter (MPPT solar charge controller)
Studer Innotec VarioTrack MPPT solar charge controller (via Xcom-485i)
Studer VarioTrack VT-40/65/80/HV MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VT-40, VT-65, VT-80, VT-HV, VarioTrack VT-65, Xcom-485i - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0 - Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Battery inverter
SMA Sunny Tripower Storage X / Sunny Island X (SMA Modbus, ennexOS)
Sunny Tripower Storage X 30/50 (incl. US variants) and Sunny Island X 30/50 (incl. US variants), queried through the System Manager over Modbus TCP.
Also known as: STPS30-20, STPS50-20, STPS27-US-20, STPS60-US-20, SI30-20, SI50-20, SI27-US208-20, SI40-US480-20, SI60-US480-20, Sunny Tripower Storage X 50, Sunny Island X 50 - Battery inverter system (lithium battery BMS interface)
Studer Innotec Xcom-CAN in BMS mode (lithium battery link, via Xcom-485i)
Studer Xcom-CAN set to BMS mode (CAN link to a lithium battery BMS), read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: Xcom-CAN, Xcom-CAN BMS, Xcom-485i - Solar inverter
Fronius Tauro 50-3 (SunSpec int+SF)
Fronius Tauro 50-3-P / 50-3-D commercial inverters (rest-of-world map, 3 MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro, Tauro 50-3-P, Tauro 50-3-D
All solar & battery inverters Modbus register maps →
Source: Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note · AP-XC-095 Revision A · rev. 2017-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.