Solar inverter · Modbus register map
Fronius Tauro 50-3 (SunSpec int+SF) Modbus register map
Updated 17 November 2026
These inverters run the same Modbus TCP/RTU server as the Fronius GEN24 and present a SunSpec map: common block, inverter model 103, nameplate 120, settings 121, status 122, immediate controls 123, multiple-MPPT model 160 (three PV inputs, MPPT 1-3). This map covers the 16-bit measurements, ratings, state and control registers, each scaled through its SunSpec scale factor.
This page lists 133 Modbus registers for the Fronius Tauro 50-3 (SunSpec int+SF) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fronius’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fronius
- Model
- Tauro 50-3 (SunSpec int+SF)
- Equipment type
- Solar inverter
- Registers
- 133 (18 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- Register map archive 1.2.7-2 (bundled with inverter firmware 1.36.x); manual 42,0410,2649 rev. 034-28092026.
- Also known as
- Fronius Tauro, Tauro 50-3-P, Tauro 50-3-D
Integration notes: Fronius Tauro 50-3 (SunSpec int+SF)
In the inverter web UI (Communication > Modbus) enable the TCP server, select int+SF and tick Allow Control if you need writes; then poll unit ID 1. Read registers 40070-40109 (wire addresses 40069-40108) for live data and model 123 for power limits.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40069 | Inverter ID | UINT16 | Inverter model ID (103) - confirms int+SF layout | Read |
| HR 40083 | W | INT16 | AC power | Read |
| HR 40084 | W_SF | INT16 | AC power scale factor (auto-scaled) | Read |
| HR 40107 | St | UINT16 | Operating state | Read |
| HR 40232 | WMaxLimPct | UINT16 | Active power limit % | Read/write |
| HR 40236 | WMaxLim_Ena | UINT16 | Enable/disable the power limit | Read/write |
| HR 40250 | WMaxLimPct_SF | INT16 | Power limit scale factor | Read |
| HR 40274 | module/1/DCW | UINT16 | DC power of input 1 | Read |
Enable Modbus control & writes
Inverter web interface > Communication > Modbus: choose TCP Server and/or RTU Server, set SunSpec Model Type (int+SF for this map), and activate 'Allow Control' for on/off, power reduction, power factor and reactive power commands. 'Restrict Control' limits control to fixed IP addresses. Writes to the control models raise an exception when control is not allowed.
Communication loss & watchdog
Model 123 controls have *_RvrtTms fallback timers (0-28800 s) that restart with every Modbus message; on expiry the control ends and the next-priority mode takes over. 0 (default) keeps the setting until disabled.
Byte order & addressing
- Off-by-one: SunSpec registers are numbered from 40001; request number minus one (40001 -> 40000).
- Switching float/int+SF changes the address of every model after the inverter model.
- Writes to read-only or unsupported registers are silently ignored; out-of-range values return exception 3.
Network setup
- TCP: inverter unit ID is always 1 (identify devices by IP address); port 502 or 1502 selectable in the web UI.
- RTU: set Inverter address (1-247, factory 1), interface, baud and parity in the web UI; each inverter on the bus needs a unique address.
- RTU wiring: 120-ohm termination at both line ends, shielded twisted pair, strict daisy chain.
Watch out for
- Query sequentially (at most 2 requests in parallel) with a response timeout of at least 1 s; read blocks rather than single registers.
- After changing a value of an active mode (e.g. a new WMaxLimPct), re-write the matching _Ena register with 1.
Fronius Tauro 50-3 (SunSpec int+SF) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40002doc 40003 | Common ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40003doc 40004 | Common L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40004doc 40005 | Mn | Manufacturer name, reads Fronius. | STRING[32] | Read | ||||
| HR | 40020doc 40021 | Md | Inverter model name, e.g. Tauro 50-3-P. | STRING[32] | Read | ||||
| HR | 40044doc 40045 | Vr | Inverter software version. | STRING[16] | Read | ||||
| HR | 40052doc 40053 | SN | Serial number (may fall back to a controller ID). | STRING[32] | Read | ||||
| HR | 40068doc 40069 | DA | Modbus device address (unit ID). | UINT16 | Read | ||||
| HR | 40069doc 40070 | Inverter ID | Model ID of this block. | UINT16 | Read | 103 = Three phase | |||
| HR | 40070doc 40071 | Inverter L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40071doc 40072 | A | Total AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40072doc 40073 | AphA | Phase A AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40073doc 40074 | AphB | Phase B AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40074doc 40075 | AphC | Phase C AC current. | UINT16 | × 10^SF (HR 40075) | A | Read | ||
| HR | 40075doc 40076 | A_SF | Scale factor (power of ten) for A. | INT16 | Read | ||||
| HR | 40076doc 40077 | PPVphAB | Line voltage A-B. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40077doc 40078 | PPVphBC | Line voltage B-C. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40078doc 40079 | PPVphCA | Line voltage C-A. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40079doc 40080 | PhVphA | Phase A to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40080doc 40081 | PhVphB | Phase B to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40081doc 40082 | PhVphC | Phase C to neutral voltage. | UINT16 | × 10^SF (HR 40082) | V | Read | ||
| HR | 40082doc 40083 | V_SF | Scale factor (power of ten) for V. | INT16 | Read | ||||
| HR | 40083doc 40084 | W | AC active power. | INT16 | × 10^SF (HR 40084) | W | Read | ||
| HR | 40084doc 40085 | W_SF | Scale factor (power of ten) for W. | INT16 | Read | ||||
| HR | 40085doc 40086 | Hz | Grid frequency. | UINT16 | × 10^SF (HR 40086) | Hz | Read | ||
| HR | 40086doc 40087 | Hz_SF | Scale factor (power of ten) for Hz. | INT16 | Read | ||||
| HR | 40087doc 40088 | VA | AC apparent power. | INT16 | × 10^SF (HR 40088) | VA | Read | ||
| HR | 40088doc 40089 | VA_SF | Scale factor (power of ten) for VA. | INT16 | Read | ||||
| HR | 40089doc 40090 | VAr | AC reactive power. | INT16 | × 10^SF (HR 40090) | var | Read | ||
| HR | 40090doc 40091 | VAr_SF | Scale factor (power of ten) for VAr. | INT16 | Read | ||||
| HR | 40091doc 40092 | PF | Power factor. | INT16 | × 10^SF (HR 40092) | Pct | Read | ||
| HR | 40092doc 40093 | PF_SF | Scale factor (power of ten) for PF. | INT16 | Read | ||||
| HR | 40095doc 40096 | WH_SF | Scale factor (power of ten) for WH. | INT16 | Read | ||||
| HR | 40100doc 40101 | DCW | Total DC input power. | INT16 | × 10^SF (HR 40101) | W | Read | ||
| HR | 40101doc 40102 | DCW_SF | Scale factor (power of ten) for DCW. | INT16 | Read | ||||
| HR | 40102doc 40103 | TmpCab | Cabinet temperature. | INT16 | × 10^SF (HR 40106) | C | Read | ||
| HR | 40106doc 40107 | Tmp_SF | Scale factor (power of ten) for Tmp. | INT16 | Read | ||||
| HR | 40107doc 40108 | St | SunSpec operating state. | UINT16 | Read | 1 = Off; 2 = Sleeping (auto shutdown); 3 = Starting; 4 = Producing normally (MPPT); 5 = Throttled (power reduction); 6 = Shutting down; 7 = Fault; 8 = Standby | |||
| HR | 40108doc 40109 | StVnd | Vendor operating state; the map says it mirrors St. | UINT16 | Read | 1 = Off; 2 = Sleeping (auto shutdown); 3 = Starting; 4 = Producing normally (MPPT); 5 = Throttled (power reduction); 6 = Shutting down; 7 = Fault; 8 = Standby | |||
| HR | 40121doc 40122 | Nameplate ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40122doc 40123 | Nameplate L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40123doc 40124 | DERTyp | Device type; this map lists 4 (PV). | UINT16 | Read | ||||
| HR | 40124doc 40125 | WRtg | Rated continuous active power. | UINT16 | × 10^SF (HR 40125) | W | Read | ||
| HR | 40125doc 40126 | WRtg_SF | Scale factor (power of ten) for WRtg. | INT16 | Read | ||||
| HR | 40126doc 40127 | VARtg | Rated apparent power. | UINT16 | × 10^SF (HR 40127) | VA | Read | ||
| HR | 40127doc 40128 | VARtg_SF | Scale factor (power of ten) for VARtg. | INT16 | Read | ||||
| HR | 40128doc 40129 | VArRtgQ1 | Rated reactive power, quadrant 1. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40129doc 40130 | VArRtgQ2 | Rated reactive power, quadrant 2. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40130doc 40131 | VArRtgQ3 | Rated reactive power, quadrant 3. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40131doc 40132 | VArRtgQ4 | Rated reactive power, quadrant 4. | INT16 | × 10^SF (HR 40132) | var | Read | ||
| HR | 40132doc 40133 | VArRtg_SF | Scale factor (power of ten) for VArRtg. | INT16 | Read | ||||
| HR | 40133doc 40134 | ARtg | Rated AC current. | UINT16 | × 10^SF (HR 40134) | A | Read | ||
| HR | 40134doc 40135 | ARtg_SF | Scale factor (power of ten) for ARtg. | INT16 | Read | ||||
| HR | 40135doc 40136 | PFRtgQ1 | Minimum power factor capability, quadrant 1. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40136doc 40137 | PFRtgQ2 | Minimum power factor capability, quadrant 2. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40137doc 40138 | PFRtgQ3 | Minimum power factor capability, quadrant 3. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40138doc 40139 | PFRtgQ4 | Minimum power factor capability, quadrant 4. | INT16 | × 10^SF (HR 40139) | cos() | Read | ||
| HR | 40139doc 40140 | PFRtg_SF | Scale factor (power of ten) for PFRtg. | INT16 | Read | ||||
| HR | 40149doc 40150 | Settings ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40150doc 40151 | Settings L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40151doc 40152 | WMax | Maximum active power setting. | UINT16 | × 10^SF (HR 40171) | W | Read | ||
| HR | 40152doc 40153 | VRef | Reference voltage at the grid connection point. | UINT16 | × 10^SF (HR 40172) | V | Read | ||
| HR | 40153doc 40154 | VRefOfs | Voltage offset between grid connection point and inverter. | INT16 | × 10^SF (HR 40173) | V | Read | ||
| HR | 40156doc 40157 | VAMax | Maximum apparent power setting. | UINT16 | × 10^SF (HR 40175) | VA | Read | ||
| HR | 40157doc 40158 | VArMaxQ1 | Reactive power limit, quadrant 1. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40158doc 40159 | VArMaxQ2 | Reactive power limit, quadrant 2. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40159doc 40160 | VArMaxQ3 | Reactive power limit, quadrant 3. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40160doc 40161 | VArMaxQ4 | Reactive power limit, quadrant 4. | INT16 | × 10^SF (HR 40176) | var | Read | ||
| HR | 40162doc 40163 | PFMinQ1 | Minimum power factor setting, quadrant 1. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40163doc 40164 | PFMinQ2 | Minimum power factor setting, quadrant 2. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40164doc 40165 | PFMinQ3 | Minimum power factor setting, quadrant 3. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40165doc 40166 | PFMinQ4 | Minimum power factor setting, quadrant 4. | INT16 | × 10^SF (HR 40178) | cos() | Read | ||
| HR | 40171doc 40172 | WMax_SF | Scale factor (power of ten) for WMax. | INT16 | Read | ||||
| HR | 40172doc 40173 | VRef_SF | Scale factor (power of ten) for VRef. | INT16 | Read | ||||
| HR | 40173doc 40174 | VRefOfs_SF | Scale factor (power of ten) for VRefOfs. | INT16 | Read | ||||
| HR | 40175doc 40176 | VAMax_SF | Scale factor (power of ten) for VAMax. | INT16 | Read | ||||
| HR | 40176doc 40177 | VArMax_SF | Scale factor (power of ten) for VArMax. | INT16 | Read | ||||
| HR | 40178doc 40179 | PFMin_SF | Scale factor (power of ten) for PFMin. | INT16 | Read | ||||
| HR | 40181doc 40182 | Status ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40182doc 40183 | Status L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40183doc 40184 | PVConn | PV inverter connection status bits. | BITMAP16 | Read | bit 0 = Connected; bit 1 = Available; bit 2 = Operating | |||
| HR | 40184doc 40185 | StorConn | Storage connection status bits. | BITMAP16 | Read | bit 0 = Connected; bit 1 = Available; bit 2 = Operating | |||
| HR | 40185doc 40186 | ECPConn | Grid feed-in status. | BITMAP16 | Read | bit 0 = Connected to grid (feeding) | |||
| HR | 40218doc 40219 | TmSrc | STRING[8] | Read | |||||
| HR | 40225doc 40226 | Ris | Insulation resistance. | UINT16 | × 10^SF (HR 40226) | ohms | Read | ||
| HR | 40226doc 40227 | Ris_SF | Scale factor (power of ten) for Ris. | INT16 | Read | ||||
| HR | 40227doc 40228 | Controls ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40228doc 40229 | Controls L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40229doc 40230 | Conn_WinTms | Random start window for connect/disconnect commands. | UINT16 | Secs | Read/write | |||
| HR | 40230doc 40231 | Conn_RvrtTms | Fallback timer for the connect/disconnect command; 0 = no fallback. | UINT16 | Secs | Read/write | |||
| HR | 40231doc 40232 | Conn | Write 0 for standby (no feed-in), 1 to resume feed-in. | UINT16 | Read/write | 0 = Disconnected (standby); 1 = Connected (feeding grid) | |||
| HR | 40232doc 40233 | WMaxLimPct | Active power limit as percent of WMax. | UINT16 | × 10^SF (HR 40250) | % WMax | Read/write | ||
| HR | 40233doc 40234 | WMaxLimPct_WinTms | Random start window for the power limit. | UINT16 | Secs | Read/write | |||
| HR | 40234doc 40235 | WMaxLimPct_RvrtTms | Fallback timer for the power limit; restarts on every Modbus message, 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40235doc 40236 | WMaxLimPct_RmpTms | Ramp time to the new power limit. | UINT16 | Secs | Read/write | |||
| HR | 40236doc 40237 | WMaxLim_Ena | Starts (1) or ends (0) the power limit. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40237doc 40238 | OutPFSet | Fixed power factor setpoint (signed, see sign convention). | INT16 | × 10^SF (HR 40251) | cos() | Read/write | ||
| HR | 40238doc 40239 | OutPFSet_WinTms | Random start window for the power factor setpoint. | UINT16 | Secs | Read/write | |||
| HR | 40239doc 40240 | OutPFSet_RvrtTms | Fallback timer for the power factor setpoint; 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40240doc 40241 | OutPFSet_RmpTms | Ramp time to the new power factor. | UINT16 | Secs | Read/write | |||
| HR | 40241doc 40242 | OutPFSet_Ena | Starts (1) or ends (0) the fixed power factor mode. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40243doc 40244 | VArMaxPct | Fixed reactive power as percent of VArMax. | INT16 | × 10^SF (HR 40252) | % VArMax | Read/write | ||
| HR | 40245doc 40246 | VArPct_WinTms | Random start window for the reactive power setpoint. | UINT16 | Secs | Read/write | |||
| HR | 40246doc 40247 | VArPct_RvrtTms | Fallback timer for the reactive power setpoint; 0 = none. | UINT16 | Secs | Read/write | |||
| HR | 40247doc 40248 | VArPct_RmpTms | Ramp time to the new reactive power value. | UINT16 | Secs | Read/write | |||
| HR | 40248doc 40249 | VArPct_Mod | Reactive power limit mode (read-only). | UINT16 | Read | 2 = VAr limit as % of VArMax | |||
| HR | 40249doc 40250 | VArPct_Ena | Starts (1) or ends (0) the fixed reactive power mode. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 40250doc 40251 | WMaxLimPct_SF | Scale factor (power of ten) for WMaxLimPct. | INT16 | Read | ||||
| HR | 40251doc 40252 | OutPFSet_SF | Scale factor (power of ten) for OutPFSet. | INT16 | Read | ||||
| HR | 40252doc 40253 | VArPct_SF | Scale factor (power of ten) for VArPct. | INT16 | Read | ||||
| HR | 40253doc 40254 | MPPT ID | Model ID of this block. | UINT16 | Read | ||||
| HR | 40254doc 40255 | MPPT L | Length of this block in registers. | UINT16 | Registers | Read | |||
| HR | 40255doc 40256 | MPPT DCA_SF | Scale factor (power of ten) for DCA. | INT16 | Read | ||||
| HR | 40256doc 40257 | MPPT DCV_SF | Scale factor (power of ten) for DCV. | INT16 | Read | ||||
| HR | 40257doc 40258 | MPPT DCW_SF | Scale factor (power of ten) for DCW. | INT16 | Read | ||||
| HR | 40258doc 40259 | MPPT DCWH_SF | Scale factor (power of ten) for DCWH. | INT16 | Read | ||||
| HR | 40261doc 40262 | N | Number of DC inputs reported in this model (3 here). | UINT16 | Read | ||||
| HR | 40263doc 40264 | module/1/ID | Input number 1. | UINT16 | Read | ||||
| HR | 40264doc 40265 | module/1/IDStr | Label of DC input 1, reads MPPT 1. | STRING[16] | Read | ||||
| HR | 40272doc 40273 | module/1/DCA | DC current of input 1. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40273doc 40274 | module/1/DCV | DC voltage of input 1. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40274doc 40275 | module/1/DCW | DC power of input 1. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40283doc 40284 | module/2/ID | Input number 2. | UINT16 | Read | ||||
| HR | 40284doc 40285 | module/2/IDStr | Label of DC input 2, reads MPPT 2. | STRING[16] | Read | ||||
| HR | 40292doc 40293 | module/2/DCA | DC current of input 2. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40293doc 40294 | module/2/DCV | DC voltage of input 2. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40294doc 40295 | module/2/DCW | DC power of input 2. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40303doc 40304 | module/3/ID | Input number 3. | UINT16 | Read | ||||
| HR | 40304doc 40305 | module/3/IDStr | Label of DC input 3, reads MPPT 3. | STRING[16] | Read | ||||
| HR | 40312doc 40313 | module/3/DCA | DC current of input 3. | UINT16 | × 10^SF (HR 40255) | A | Read | ||
| HR | 40313doc 40314 | module/3/DCV | DC voltage of input 3. | UINT16 | × 10^SF (HR 40256) | V | Read | ||
| HR | 40314doc 40315 | module/3/DCW | DC power of input 3. | UINT16 | × 10^SF (HR 40257) | W | Read | ||
| HR | 40323doc 40324 | End ID | End-of-map marker, reads 0xFFFF. | UINT16 | Read | ||||
| HR | 40324doc 40325 | End L | End block length, reads 0. | UINT16 | Read |
Notes on this map
- Register table from Fronius' official XLSX 'Tauro_Inverter_Register_Map_Int&SF_ROW.xlsx' in gen24-modbus-api-external-docs.zip (archive 1.2.7-2); behaviour, addressing and settings from the Fronius GEN24 Modbus TCP & RTU manual 42,0410,2649. Fronius' Modbus TCP download page lists this manual as 'Fronius GEN24, Tauro Modbus TCP & RTU Manual' (https://www.fronius.com/en-gb/uk/solar-energy/installers-partners/technical-data/all-products/system-monitoring/open-interfaces/modbus-tcp) and the ZIP as 'Fronius GEN24 & Tauro Modbus Register'.
- Addresses assume SunSpec Model Type = int+SF. With float the inverter model is 113 and every later model moves by +10 registers. Fronius advises walking the model chain from 40001 rather than hard-coding addresses.
- Word order: neither the manual nor the XLSX states the order of 32/64-bit values, so they are left out: SID 40001-40002, WH 40094-40095, Evt1/Evt2/EvtVnd1-2 40110-40117, ActWh 40187-40190, StActCtl 40217-40218, Tms 40223-40224, and DCWH/Tms of every MPPT input.
- DCA/DCV in the inverter model (40097-40100) are left out: their scale factors are marked not supported and per-input DC values are in model 160.
- Registers marked 'not supported' in the XLSX are left out (Opt, extra temperatures, VMax/VMin, ramp settings, model 160 Tmp/DCSt/DCEvt and similar), plus the storage ratings in model 120 (WHRtg, AhrRtg, MaxChaRte, MaxDisChaRte).
- Many scale factors are auto-scaled (A, W, VA, VAr, DCW, Ris, model 160): read a value and its SF in the same request.
- Unsupported values read as: int16 0x8000, uint16/enum16/bitfield16 0xFFFF, sunssf 0x8000.
- The MPPT model (160) here reports 3 repeating input blocks: three PV inputs, MPPT 1-3; the end block is at 40324.
- The Smart Meter is a separate Modbus device (default unit ID 200) with its own SunSpec map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fronius Tauro 50-3 (SunSpec int+SF)
What Modbus registers does the Fronius Tauro 50-3 (SunSpec int+SF) have?
This map lists 133 registers: 133 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fronius Tauro 50-3 (SunSpec int+SF) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Fronius numbers SunSpec registers from 40001 and says to send the register number minus one: register 40001 is read at address 40000 (0x9C40). The manual's RTU example reads register 40005 (Mn) with address bytes 9C 44 (40004).
What are the minimum Modbus registers to integrate the Fronius Tauro 50-3 (SunSpec int+SF)?
Start with HR 40069 Inverter ID (Inverter model ID (103) - confirms int+SF layout); HR 40083 W (AC power); HR 40084 W_SF (AC power scale factor (auto-scaled)); HR 40107 St (Operating state); HR 40232 WMaxLimPct (Active power limit %); HR 40236 WMaxLim_Ena (Enable/disable the power limit); HR 40250 WMaxLimPct_SF (Power limit scale factor); HR 40274 module/1/DCW (DC power of input 1).
How do I enable Modbus control of the Fronius Tauro 50-3 (SunSpec int+SF)?
Inverter web interface > Communication > Modbus: choose TCP Server and/or RTU Server, set SunSpec Model Type (int+SF for this map), and activate 'Allow Control' for on/off, power reduction, power factor and reactive power commands. 'Restrict Control' limits control to fixed IP addresses. Writes to the control models raise an exception when control is not allowed.
What happens when the Fronius Tauro 50-3 (SunSpec int+SF) loses Modbus communication?
Model 123 controls have *_RvrtTms fallback timers (0-28800 s) that restart with every Modbus message; on expiry the control ends and the next-priority mode takes over. 0 (default) keeps the setting until disabled.
Where is the official Fronius Tauro 50-3 (SunSpec int+SF) Modbus documentation?
The source is Fronius GEN24 Modbus TCP & RTU (operating instructions) + Tauro_Inverter_Register_Map_Int&SF_ROW.xlsx (42,0410,2649 (034-28092026)), revision 2026-09, published free by Fronius at https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2649.pdf.
More Fronius Modbus register maps
- Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Energy meter
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
An energy meter wired to a Fronius Datamanager (or Hybridmanager) over Modbus RTU and republished by it, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus - Solar inverter
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Fronius Primo/Symo GEN24 (Plus) US variants with a battery configured, SunSpec Model Type int+SF; the US map appends IEEE 1547 models 701-713 after storage model 124.
Also known as: Primo GEN24 Plus US, Symo GEN24 Plus US, Primo GEN24 10.0 208-240, Primo GEN24 3.8 208-240, Primo GEN24 6.0 208-240 - Solar inverter
Fronius Symo / Primo / Galvo / Symo Hybrid via Datamanager (SunSpec int+SF)
Fronius inverters read through a Fronius Datamanager (1.0/2.0 card or Hybridmanager) with SunSpec Model Type set to int+SF; model 124 present on Symo Hybrid.
Also known as: Fronius Symo, Fronius Primo, Fronius Galvo, Fronius Symo Hybrid, Fronius IG Plus, Datamanager 2.0 - Solar inverter
Fronius Tauro ECO 50-100 (SunSpec int+SF)
Fronius Tauro ECO 50-100 kW commercial inverters (rest-of-world map, single MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro ECO, Tauro ECO 50-3-P, Tauro ECO 99-3-D, Tauro ECO 100-3-P, Tauro ECO 100-3-D
Other solar & battery inverters register maps
- Solar charge controller (PWM, dual battery)
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver Duo through the MSC MeterBus-to-RS-232 adapter; Modbus specification V04 (19 March 2019). 16-bit registers only.
Also known as: SunSaver Duo, SSDuo - Solar inverter gateway (PV plant data logger)
SMA Sunny WebBox Modbus gateway (plant and gateway unit IDs 1-2)
Sunny WebBox firmware 1.52 or later with Modbus enabled, SMA Modbus profile as documented in WEBBOX_MODBUS-TB-US-EN-19 v1.9 (legacy product).
Also known as: Sunny WebBox, WebBox, SWEBBOX, Sunny WebBox with Bluetooth - Battery inverter (off-grid inverter-charger)
Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)
Studer Xtender XTH, XTM and XTS inverter-chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: XTH, XTM, XTS, Xtender XTH, Xtender XTM, Xtender XTS, Xcom-485i - Solar charge controller (MPPT, battery charger)
Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver MPPT through the MSC MeterBus-to-RS-232 adapter; Modbus specification v11.
Also known as: SunSaver MPPT, SS-MPPT - Solar inverter (via Sunny WebBox gateway)
SMA Sunny WebBox Modbus profile - common addresses of SMA devices (unit IDs 3-247)
SMA devices reached through a Sunny WebBox (fw 1.52+) on unit IDs 3-247 whose family uses the common address set; SB n000US and SB nn000TL-US-12 families use their own tables instead.
Also known as: Sunny WebBox device profile, SMA Modbus profile WebBox, Sunny Central via WebBox, Sunny Tripower STP nn000TL-10 via WebBox, Sunny Mini Central via WebBox - Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417
All solar & battery inverters Modbus register maps →
Source: Fronius GEN24 Modbus TCP & RTU (operating instructions) + Tauro_Inverter_Register_Map_Int&SF_ROW.xlsx · 42,0410,2649 (034-28092026) · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.