Energy meter (DC) · Modbus register map
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
The DCM1 is a two-part DC meter (DCM-D display/meter plus DCM-T transducer) for DC fast chargers, with RS485 Modbus RTU and Modbus TCP. Readings are 32-bit integers sent low word first with fixed weights. This map covers voltage, current, power, energy and Ah counters, run hours, shunt temperatures, serial and Ethernet settings, resets, the device state word and the main OCMF charging-session registers.
This page lists 71 Modbus registers for the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Carlo Gavazzi
- Model
- DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
- Equipment type
- Energy meter (DC)
- Registers
- 71 (32 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- OCMF display/string registers need firmware 1.5.3 onward
- Also known as
- DCM1A60V10L20S1PFA, DCM1A60V10L20S1PFB, DCM1A60V10L20S2DEB, DCM1A60V10L20S3DEB, DCM1A60V10L20S2DEBF, DCM1A60V10L20S3DEBF, DCM1A30V10L20S1PFA, DCM1A30V10L20S1PFB, DCM1A30V10L20S2DEB, DCM1A30V10L20S3DEB, DCM1A30V10L20S2DEBF, DCM1A30V10L20S3DEBF, DCM1A60V10L20S1ULB, DCM1A30V10L20S1ULB
Integration notes: Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
Poll input registers 0000h-0005h (function 04 or 03) for V, A and W and 0010h-0027h for energy; values are INT32 low word first with fixed weights. For signed charging sessions follow the OCMF procedure around 7040h and 7100h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | INT32 CDAB | DC voltage | Read |
| IR 2 | Current | INT32 CDAB | DC current | Read |
| IR 4 | Power | INT32 CDAB | DC power | Read |
| IR 16 | kWh (+) TOT | INT32 CDAB | Imported energy total | Read |
| IR 32 | kWh (-) TOT | INT32 CDAB | Exported energy total | Read |
| HR 20498 | Device state | BITMAP16 | Device state / transducer health | Read |
| HR 28741 | Charging status | UINT16 | Charging session status | Read |
Enable Modbus control & writes
RS485 and Ethernet are both active. Serial settings at 2000h-2004h take effect after writing 1 to 2010h; Ethernet settings at 2100h-210Dh after writing 1 to 210Eh or a power cycle.
Byte order & addressing
- 32-bit and 64-bit unsigned values are low word first.
- Totals are 0.1 kWh resolution; run hours are in 1/100 h.
- Certified versions block the total-energy reset.
Network setup
- Serial defaults: address 1, 9600 baud, no parity, 1 stop bit.
- Ethernet defaults: 192.168.1.10 / 255.255.255.0, gateway 192.168.1.1, port 502, DHCP off.
- With DHCP on, read the assigned address at 2120h-2123h.
Watch out for
- Max RS485 answer time is 500 ms; use a long enough timeout.
- After reading an OCMF file, write 0 to 7100h or no new session can start.
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 300001 / 0000h | Voltage | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 2doc 300003 / 0002h | Current | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 4doc 300005 / 0004h | Power | Signed DC power. | INT32 | CDAB | × 0.1 | W | Read | |
| IR | 11doc 300012 / 000Bh | Carlo Gavazzi identification code | Model code, e.g. 1824 = DCM1A60V10L20S1PFA; see the part-number table. | UINT16 | Read | ||||
| IR | 16doc 300017 / 0010h | kWh (+) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 18doc 300019 / 0012h | Ah (+) TOT | INT32 | CDAB | × 0.1 | Ah | Read | ||
| IR | 20doc 300021 / 0014h | kWh (+) PAR | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 22doc 300023 / 0016h | Ah (+) PAR | INT32 | CDAB | × 0.1 | Ah | Read | ||
| IR | 32doc 300033 / 0020h | kWh (-) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 34doc 300035 / 0022h | Ah (-) TOT | INT32 | CDAB | × 0.1 | Ah | Read | ||
| IR | 36doc 300037 / 0024h | kWh (-) PAR | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 38doc 300039 / 0026h | Ah (-) PAR | INT32 | CDAB | × 0.1 | Ah | Read | ||
| IR | 44doc 300045 / 002Ch | Run hour meter | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 46doc 300047 / 002Eh | Run hour meter kWh- | Hours counted while energy flows in the negative direction. | INT32 | CDAB | × 0.01 | h | Read | |
| IR | 48doc 300049 / 0030h | Run hour meter ON time | Hours the meter has been powered. | INT32 | CDAB | × 0.01 | h | Read | |
| IR | 50doc 300051 / 0032h | Run hour meter PAR | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 52doc 300053 / 0034h | Run hour meter kWh- PAR | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 54doc 300055 / 0036h | Run hour meter ON time PAR | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 80doc 300081 / 0050h | T1 (shunt terminal 1 temperature) | INT32 | CDAB | × 0.1 | °C | Read | ||
| IR | 82doc 300083 / 0052h | T2 (shunt terminal 2 temperature) | INT32 | CDAB | × 0.1 | °C | Read | ||
| IR | 770doc 300771 / 0302h | Firmware version DCM-D (meter) | High byte: bits 0-3 minor, bits 4-7 major; low byte: revision. | UINT16 | Read | ||||
| IR | 771doc 300772 / 0303h | Firmware version DCM-D (cryptography) | High byte: bits 0-3 minor, bits 4-7 major; low byte: revision. | UINT16 | Read | ||||
| IR | 772doc 300773 / 0304h | Firmware version DCM-T (transducer) | High byte: bits 0-3 minor, bits 4-7 major; low byte: revision. | UINT16 | Read | ||||
| HR | 4096doc 304097 / 1000h | Password | 0 = no password (default), up to 9999. | UINT16 | Read/write | ||||
| HR | 4355doc 304356 / 1103h | Easy connection | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 4361doc 304362 / 1109h | Quick set up at next power on | UINT16 | Read/write | 0 = Menu disabled; 1 = Menu enabled (default) | ||||
| HR | 4363doc 304364 / 110Bh | Start-up current of run hour counter | Default 480 (0.48 A); A30 models 160-300000, A60 models up to 600000. | UINT32 | CDAB | × 0.001 | A | Read/write | |
| HR | 8192doc 308193 / 2000h | RS485 instrument address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 8193doc 308194 / 2001h | RS485 baud rate | UINT16 | Read/write | 1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps | ||||
| HR | 8194doc 308195 / 2002h | RS485 parity | UINT16 | Read/write | 1 = No parity (default); 2 = Even parity | ||||
| HR | 8195doc 308196 / 2003h | Stop bit | UINT16 | Read/write | 1 = 1 (default); 2 = 2 | ||||
| HR | 8196doc 308197 / 2004h | RS485 delay on reply | 0-1000, default 0. | UINT16 | ms | Read/write | |||
| HR | 8208doc 308209 / 2010h | Update serial communication settings | Write 1 to apply new serial settings. | UINT16 | Read/write | ||||
| HR | 8448doc 308449 / 2100h | Stored IP address octet A | Default 192.168.1.10; used when DHCP is off. | UINT16 | Read/write | ||||
| HR | 8449doc 308450 / 2101h | Stored IP address octet B | UINT16 | Read/write | |||||
| HR | 8450doc 308451 / 2102h | Stored IP address octet C | UINT16 | Read/write | |||||
| HR | 8451doc 308452 / 2103h | Stored IP address octet D | UINT16 | Read/write | |||||
| HR | 8452doc 308453 / 2104h | Stored subnet mask octet A | Default 255.255.255.0. | UINT16 | Read/write | ||||
| HR | 8453doc 308454 / 2105h | Stored subnet mask octet B | UINT16 | Read/write | |||||
| HR | 8454doc 308455 / 2106h | Stored subnet mask octet C | UINT16 | Read/write | |||||
| HR | 8455doc 308456 / 2107h | Stored subnet mask octet D | UINT16 | Read/write | |||||
| HR | 8456doc 308457 / 2108h | Stored default gateway octet A | Default 192.168.1.1. | UINT16 | Read/write | ||||
| HR | 8457doc 308458 / 2109h | Stored default gateway octet B | UINT16 | Read/write | |||||
| HR | 8458doc 308459 / 210Ah | Stored default gateway octet C | UINT16 | Read/write | |||||
| HR | 8459doc 308460 / 210Bh | Stored default gateway octet D | UINT16 | Read/write | |||||
| HR | 8460doc 308461 / 210Ch | Modbus TCP/IP port | 1-9999, default 502. | UINT16 | Read/write | ||||
| HR | 8461doc 308462 / 210Dh | DHCP enabled | UINT16 | Read/write | 0 = DHCP off (default); 1 = DHCP on | ||||
| HR | 8462doc 210Eh | Update TCP/IP communication settings | Write 1 to apply new Ethernet settings (or power-cycle). | UINT16 | Read/write | ||||
| HR | 8480doc 308481 / 2120h | Actual IP address octet A | Reads 0xFFFF while DHCP has not assigned an address. | UINT16 | Read | ||||
| HR | 8481doc 308482 / 2121h | Actual IP address octet B | UINT16 | Read | |||||
| HR | 8482doc 308483 / 2122h | Actual IP address octet C | UINT16 | Read | |||||
| HR | 8483doc 308484 / 2123h | Actual IP address octet D | UINT16 | Read | |||||
| HR | 9471doc 309472 / 24FFh | Signature type | UINT16 | Read | 0 = 256-bit signature; 1 = 384-bit signature; 2 = No signature | ||||
| HR | 16387doc 316388 / 4003h | Reset total counters | Write 1. Non-certified: totals, Ah, run hours. Certified: Ah and run hours only. | UINT16 | Read/write | ||||
| HR | 16388doc 316389 / 4004h | Reset partial counters | Write 1 to clear partial energy, Ah and run-hour counters. | UINT16 | Read/write | ||||
| HR | 20498doc 320499 / 5012h | Device state | Bits 11-12: 00 DCM-T OK, 01 warning (over range), 11 failure. | BITMAP16 | Read | bit 0 = Voltage over range (beyond ±1150.1 V); bit 1 = Current over range (beyond ±600.1 A); bit 2 = Terminal 1 temperature below -25.1 °C; bit 3 = Terminal 1 temperature above 120.1 °C; bit 4 = Terminal 2 temperature below -25.1 °C; bit 5 = Terminal 2 temperature above 120.1 °C; bit 11 = DCM-T status, low bit; bit 12 = DCM-T status, high bit; bit 13 = Transducer disconnected; bit 14 = Invalid transducer connected; bit 15 = Internal device fault | |||
| HR | 20499doc 320500 / 5013h | Shunt temperature position 1 | UINT16 | × 0.1 | °C | Read | |||
| HR | 20500doc 320501 / 5014h | Shunt temperature position 2 | UINT16 | × 0.1 | °C | Read | |||
| HR | 20736doc 320737 / 5100h | Cable loss value | Cable resistance used to correct energy; max 500. | INT32 | CDAB | mOhm | Read | ||
| HR | 28721doc 328722 / 7031h | Local time delta | Offset from UTC, -1440 to 1440. | INT16 | min | Read/write | |||
| HR | 28726doc 328727 / 7036h | Display charging direction | UINT16 | Read/write | 0 = Charging vehicle; 1 = Vehicle to grid; 2 = Bidirectional | ||||
| HR | 28736doc 328737 / 7040h | OCMF command | Write ASCII 'B' to begin, 'E' to end, 'A' to abort a transaction. | UINT16 | Read/write | ||||
| HR | 28741doc 328742 / 7045h | Charging status | UINT16 | Read | 0 = No charging; 1 = Charging; 2 = End of last transaction; 3 = End of last transaction with error | ||||
| HR | 28752doc 328753 / 7050h | Charging session end page duration | 60-300, default 300. | UINT16 | s | Read/write | |||
| HR | 28768doc 328769 / 7060h | Time synchronization status | UINT16 | Read | 0 = Time not synchronized; 1 = Time synchronized | ||||
| HR | 28928doc 328929 / 7100h | OCMF state | Write 0 after reading the OCMF file to allow a new session. | UINT16 | Read/write | 0 = Ready for new transaction; 1 = Running; 2 = Session completed, OCMF file ready; 3 = Session completed with internal error, OCMF file corrupted | |||
| HR | 28929doc 328930 / 7101h | OCMF file length | UINT16 | words | Read | ||||
| HR | 28930doc 328931 / 7102h | OCMF last transaction id | UINT32 | CDAB | Read | ||||
| HR | 31232doc 331233 / 7A00h | Session delta kWh+ | Energy delivered in the current/last charging session. | UINT64 | CDAB | Wh | Read | ||
| HR | 31236doc 331237 / 7A04h | Session delta kWh- | UINT64 | CDAB | Wh | Read | |||
| HR | 31240doc 331241 / 7A08h | Session duration | UINT64 | CDAB | s | Read |
Notes on this map
- Word order: the protocol says INT32, UINT32 and UINT64 are sent least significant word first with bytes MSB first, so those values are CDAB here.
- Left out: the FLOAT block at 0200h (no word order stated for IEEE 754), INT64 energy blocks at 0500h/0600h and the INT64 UTC timestamp at 7032h (word order stated only for unsigned 64-bit), the mirror block at 0100h, the signed OBIS maps at 0700h/0800h, public keys, signatures, display page filters, MAC address, OCMF identification fields, custom display strings, the OCMF file buffer, maintenance mode and the cable-loss datalogger.
- When the DCM-T transducer is unplugged, its values read 0x7FFF or 0x7FFFFFFF and the device state flags it.
- The part-number table gives code 1832 for both ULB variants, with hex 0x0728 and 0x0729; check the code on the unit.
- The charging-session procedure (sync clock at 7031h/7032h, write 'B' to 7040h, read 7A00h-7A08h, write 'E', read and acknowledge the OCMF file at 7100h-7110h) is described in the source.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
What Modbus registers does the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) have?
This map lists 71 registers: 23 input registers, 48 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx for function 04, 4xxxxx for function 03) and the hex physical address that goes in the frame. 300001 / 0000h is wire address 0. Functions 03 and 04 return the same data.
What byte order does the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)?
Start with IR 0 Voltage (DC voltage); IR 2 Current (DC current); IR 4 Power (DC power); IR 16 kWh (+) TOT (Imported energy total); IR 32 kWh (-) TOT (Exported energy total); HR 20498 Device state (Device state / transducer health); HR 28741 Charging status (Charging session status).
How do I enable Modbus control of the Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)?
RS485 and Ethernet are both active. Serial settings at 2000h-2004h take effect after writing 1 to 2010h; Ethernet settings at 2100h-210Dh after writing 1 to 210Eh or a power cycle.
Where is the official Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP) Modbus documentation?
The source is DCM1 Modbus Communication Protocol - Public version (Version 1.11), revision 2025-07-30, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/DCM1_CPP.pdf.
More Carlo Gavazzi Modbus register maps
- Energy meter (DC)
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)
DCT1 300 A and 600 A / 1000 V DC meters, with and without signed data (S1/S2/S3), protocol version 1.1.
Also known as: DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Energy meter
Carlo Gavazzi EM270 / EM280 dual three-phase energy meters with TCD current sensors
EM270 X (firmware r.b0+), EM270 W (r.C0+) and EM280 (r.E0+) on RS485 Modbus RTU, per communication protocol version 5 revision 1 (2018-01-29).
Also known as: EM270, EM280, EM270 X, EM270 W, EM27072DMV53X2SX, EM28072DMV53X2SX - Energy meter
Carlo Gavazzi EM271 dual three-phase energy meter with TCD current sensors
EM271 (firmware r.d0+, PF values from r.d2) on RS485 Modbus RTU, per communication protocol version 1 revision 2 (2018-01-29).
Also known as: EM271, EM27172DMV53X2SX, EM27172DMV63X2SX - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter (power analyzer)
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
WM14 Advanced (revision 5 onward) and CPT-DIN Advanced (revision 6 onward) with RS485 (or RS232 on CPT-DIN), protocol version 2 revision 2 (2008-01-09).
Also known as: WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A - Power meter (power analyzer)
Carlo Gavazzi WM15 power analyzer
WM15-96 three-phase panel power analyzers with RS485 Modbus RTU (OS / OSPF / HOS versions), protocol version 1.2.
Also known as: WM15, WM15-96, WM1596AV53XOSX, WM1596AV53XOSPFB, WM1596AV53HOSX - Power meter (power analyzer)
Carlo Gavazzi WM20 / WM30 / WM40 power analyzers
WM20, WM30 and WM40 modular power analyzers with an RS485 (or Ethernet) Modbus module, protocol internal version rev. 4.0 (2018-03-28); WM30 = firmware letter X, WM40 = Y, WM20 = Z.
Also known as: WM20, WM30, WM40, WM20-96, WM30-96, WM40-96 - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5
Other power & energy meters register maps
- Power meter
Circutor CVM-E3-MINI
Circutor CVM-E3-MINI DIN-rail power analyzer, RS-485 Modbus RTU (Map 2 / CVM-C10-compatible addresses), manual M170B01-03-25B.
Also known as: CVM-E3-MINI-ITF-RS485, CVM-E3-MINI-MC, CVM-E3-MINI-FLEX, CVM-E3-MINI-mV, CVM-E3-MINI-ITF-WiEth - Energy meter
Eastron SDM120-Modbus
Eastron SDM120Modbus single-phase DIN-rail meter (direct connected), protocol implementation V2.4.
Also known as: SDM120M, SDM120Modbus, SDM120-M - Energy meter
Eastron SDM630MCT
Eastron SDM630MCT three-phase CT-connected DIN-rail meter with RS485 Modbus RTU, protocol implementation V1.7.
Also known as: SDM630 MCT - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Energy meter (DIN-rail, single-phase)
IME Conto D1 single-phase energy meter (CE111)
IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).
Also known as: CE111, Conto D1 - Power meter (DIN-rail)
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
IME Nemo D4-Le for Rogowski coils, code KRNEMOD4, per protocol PR140 (software 1.01).
Also known as: KRNEMOD4
All power & energy meters Modbus register maps →
Source: DCM1 Modbus Communication Protocol - Public version · Version 1.11 · rev. 2025-07-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.