Energy meter (DC) · Modbus register map

Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The DCT1 is a DC energy meter with an internal shunt, built for EV charging and DC distribution, with an RS485 Modbus RTU port. Readings are 32-bit integers sent low word first with fixed weights. This map covers voltage, current, power, imported and exported energy and Ah, run-hour counters, shunt temperatures, cable-loss value, serial settings, resets and the device state word.

This page lists 37 Modbus registers for the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.

Manufacturer
Carlo Gavazzi
Model
DCT1 DC energy meter (Modbus RTU)
Equipment type
Energy meter (DC)
Registers
37 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC
Source document
DCT1 Modbus Communication Protocol - Public version · Version 1.1 · rev. 2024-02-13
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)

Integration in brief

Read input registers 0000h-0005h (function 04 or 03) for volts, amps and watts, and 0010h-0027h for energy and Ah; decode INT32 low word first and apply the fixed weights (V and W x10, A x1000, kWh and Ah x10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageINT32 CDABDC voltageRead
IR 2CurrentINT32 CDABDC currentRead
IR 4PowerINT32 CDABDC powerRead
IR 16kWh (+) TOTINT32 CDABImported energy totalRead
IR 32kWh (-) TOTINT32 CDABExported energy totalRead
HR 20498Device stateBITMAP16Device state / over-range flagsRead

Enable Modbus control & writes

Modbus RTU is always on. Set address, baud, parity and stop bits at 2000h-2003h, then write 1 to 2010h to apply them.

Byte order & addressing

Network setup

Watch out for

Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

37 of 37 shown
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 300001 / 0000hVoltageINT32CDAB× 0.1VRead
IR2doc 300003 / 0002hCurrentINT32CDAB× 0.001ARead
IR4doc 300005 / 0004hPowerSigned DC power.INT32CDAB× 0.1WRead
IR11doc 300012 / 000BhCarlo Gavazzi identification codeRead one word at a time.UINT16Read1808 = DCT1A60V10LS1X; 1809 = DCT1A60V10LS2EC; 1810 = DCT1A60V10LS3EC; 1812 = DCT1A30V10LS1X; 1813 = DCT1A30V10LS2EC; 1814 = DCT1A30V10LS3EC
IR16doc 300017 / 0010hkWh (+) TOTINT32CDAB× 0.1kWhRead
IR18doc 300019 / 0012hAh (+) TOTINT32CDAB× 0.1AhRead
IR20doc 300021 / 0014hkWh (+) PARINT32CDAB× 0.1kWhRead
IR22doc 300023 / 0016hAh (+) PARINT32CDAB× 0.1AhRead
IR32doc 300033 / 0020hkWh (-) TOTINT32CDAB× 0.1kWhRead
IR34doc 300035 / 0022hAh (-) TOTINT32CDAB× 0.1AhRead
IR36doc 300037 / 0024hkWh (-) PARINT32CDAB× 0.1kWhRead
IR38doc 300039 / 0026hAh (-) PARINT32CDAB× 0.1AhRead
IR44doc 300045 / 002ChRun hour meterINT32CDAB× 0.01hRead
IR46doc 300047 / 002EhRun hour meter kWh-Hours counted while energy flows in the negative direction.INT32CDAB× 0.01hRead
IR48doc 300049 / 0030hRun hour meter ON timeHours the meter has been powered.INT32CDAB× 0.01hRead
IR50doc 300051 / 0032hRun hour meter PARINT32CDAB× 0.01hRead
IR52doc 300053 / 0034hRun hour meter kWh- PARINT32CDAB× 0.01hRead
IR54doc 300055 / 0036hRun hour meter ON time PARINT32CDAB× 0.01hRead
IR80doc 300081 / 0050hT1 (shunt terminal 1 temperature)INT32CDAB× 0.1°CRead
IR82doc 300083 / 0052hT2 (shunt terminal 2 temperature)INT32CDAB× 0.1°CRead
IR770doc 300771 / 0302hFirmware version and revisionHigh byte: bits 0-3 minor, bits 4-7 major; low byte: revision.UINT16Read
HR4355doc 304356 / 1103hEasy connectionUINT16Read/write0 = Disabled (default); 1 = Enabled
HR4363doc 304360 / 110BhStartup current of run hour counterRange 480-600000 (0.48-600 A), default 480. Write with function 10h only.UINT32CDAB× 0.001ARead/write
HR8192doc 308193 / 2000hRS485 instrument address1-247, default 1.UINT16Read/write
HR8193doc 308194 / 2001hRS485 baud rateUINT16Read/write1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps
HR8194doc 308195 / 2002hRS485 parityUINT16Read/write1 = No parity (default); 2 = Even parity
HR8195doc 308196 / 2003hStop bitUINT16Read/write1 = 1 (default); 2 = 2
HR8196doc 308197 / 2004hRS485 delay on reply0-1000, default 20.UINT16msRead/write
HR8208doc 308209 / 2010hUpdate serial communication settingsWrite 1 to apply new serial settings; other values do nothing.UINT16Read/write
HR9471doc 309472 / 24FFhSignature typeUINT16Read0 = 256-bit signature; 1 = 384-bit signature; 2 = No signature
HR16387doc 316388 / 4003hReset total countersWrite 1. Non-certified: totals, Ah, run hours. Certified: Ah and run hours only.UINT16Read/write
HR16388doc 316389 / 4004hReset partial countersWrite 1 to clear partial energy, Ah and run-hour counters.UINT16Read/write
HR20487doc 320488 / 5007hProduction yearFour digits.UINT16Read
HR20498doc 320499 / 5012hDevice stateBITMAP16Readbit 0 = Voltage over range (beyond ±1150.1 V); bit 1 = Current over range (±600.1 A on A60 models, ±300.1 A on A30 models); bit 2 = Terminal 1 temperature below -25.1 °C; bit 3 = Terminal 1 temperature above 120.1 °C; bit 4 = Terminal 2 temperature below -25.1 °C; bit 5 = Terminal 2 temperature above 120.1 °C; bit 15 = Internal device fault
HR20499doc 320500 / 5013hShunt temperature position 1UINT16× 0.1°CRead
HR20500doc 320501 / 5014hShunt temperature position 2UINT16× 0.1°CRead
HR20736doc 320737 / 5100hCable loss valueCable resistance used to correct energy.INT32CDABmOhmRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)

What Modbus registers does the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) have?

This map lists 37 registers: 21 input registers, 16 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a 6-digit Modicon number (3xxxxx) and the hex physical address; the hex value goes in the frame. 300001 / 0000h is read at wire address 0. Functions 03 and 04 both read the measurement tables.

What byte order does the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)?

Start with IR 0 Voltage (DC voltage); IR 2 Current (DC current); IR 4 Power (DC power); IR 16 kWh (+) TOT (Imported energy total); IR 32 kWh (-) TOT (Exported energy total); HR 20498 Device state (Device state / over-range flags).

How do I enable Modbus control of the Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)?

Modbus RTU is always on. Set address, baud, parity and stop bits at 2000h-2003h, then write 1 to 2010h to apply them.

Where is the official Carlo Gavazzi DCT1 DC energy meter (Modbus RTU) Modbus documentation?

The source is DCT1 Modbus Communication Protocol - Public version (Version 1.1), revision 2024-02-13, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/DCT1_CPP_%20V1.1_05042024.pdf.

More Carlo Gavazzi Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: DCT1 Modbus Communication Protocol - Public version · Version 1.1 · rev. 2024-02-13. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.