Sensor (electromagnetic flowmeter) · Modbus register map
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) Modbus register map
Updated 19 November 2026
Promag 300 is an Endress+Hauser electromagnetic flowmeter with a compact transmitter. With the Modbus RS485 option it is a Modbus RTU slave. This map covers flow, conductivity, temperature and density process values, totalizers, unit codes, diagnostics, serial settings and identification.
This page lists 32 Modbus registers for the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.
- Manufacturer
- Endress+Hauser
- Model
- Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
- Equipment type
- Sensor (electromagnetic flowmeter)
- Registers
- 32 (11 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 247
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Valid as of device firmware 01.06.zz
- Also known as
- Promag 300, Promag P 300, Promag H 300, Promag W 300
Integration notes: Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
Read the process value floats (CDAB at the factory byte order) with function 03 or 04 and check Actual diagnostics (2732). Read the unit registers once so you know the engineering unit of each value.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3873 | Volume flow | FLOAT32 CDAB | Volume flow | Read |
| HR 2010 | Corrected volume flow | FLOAT32 CDAB | Corrected volume flow | Read |
| HR 3875 | Mass flow | FLOAT32 CDAB | Mass flow | Read |
| HR 2018 | Flow velocity | FLOAT32 CDAB | Flow velocity | Read |
| HR 2731 | Actual diagnostics | UINT16 | Actual diagnostics | Read |
Enable Modbus control & writes
The Modbus RS485 option must be ordered. Bus address, baud rate, parity and byte order are under Expert > Communication > Modbus configuration (registers 4910-4917).
Byte order & addressing
- Factory byte order 1-0-3-2 gives CDAB floats; adjust the device Byte order (4915) rather than the PLC if needed.
- Function 03 and 04 both read the same registers; write with 06 or 16.
Network setup
- Check the factory bus address, baud rate and parity on the device before connecting; change them in the Modbus configuration menu.
Watch out for
- Avoid cyclic writes to non-volatile parameters; the EEPROM write count is limited.
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2010doc 2011 to 2012 | Corrected volume flow | Unit per the corresponding unit parameter. | FLOAT32 | CDAB | Read | |||
| HR | 2012doc 2013 to 2014 | Conductivity | Unit set by register 2121. | FLOAT32 | CDAB | Read | |||
| HR | 2014doc 2015 to 2016 | Temperature | Unit set by register 2109. | FLOAT32 | CDAB | Read | |||
| HR | 2018doc 2019 to 2020 | Flow velocity | FLOAT32 | CDAB | Read | ||||
| HR | 2057doc 2058 to 2067 | Order code | STRING[20] | Read | |||||
| HR | 2082doc 2083 to 2084 | Density | Unit set by register 2107. | FLOAT32 | CDAB | Read | |||
| HR | 2100doc 2101 | Mass flow unit | Unit code; see the picklist in the manual. | UINT16 | Read/write | ||||
| HR | 2102doc 2103 | Volume flow unit | Unit code; see the picklist in the manual. | UINT16 | Read/write | ||||
| HR | 2106doc 2107 | Density unit | Unit code; see the picklist in the manual. | UINT16 | Read/write | ||||
| HR | 2108doc 2109 | Temperature unit | Unit code; see the picklist in the manual. | UINT16 | Read/write | ||||
| HR | 2120doc 2121 | Conductivity unit | Unit code; see the picklist in the manual. | UINT16 | Read/write | ||||
| HR | 2609doc 2610 to 2611 | Totalizer 1 value | Totalizer unit per its own setting. | FLOAT32 | CDAB | Read | |||
| HR | 2611doc 2612 to 2613 | Totalizer 1 overflow | Number of overflows of totalizer value. | FLOAT32 | CDAB | Read | |||
| HR | 2731doc 2732 | Actual diagnostics | Current diagnostic message (behaviour symbol, code and short text). | UINT16 | Read | ||||
| HR | 2733doc 2734 | Previous diagnostics | UINT16 | Read | |||||
| HR | 2809doc 2810 to 2811 | Totalizer 2 value | Totalizer unit per its own setting. | FLOAT32 | CDAB | Read | |||
| HR | 2811doc 2812 to 2813 | Totalizer 2 overflow | Number of overflows of totalizer value. | FLOAT32 | CDAB | Read | |||
| HR | 3009doc 3010 to 3011 | Totalizer 3 value | Totalizer unit per its own setting. | FLOAT32 | CDAB | Read | |||
| HR | 3011doc 3012 to 3013 | Totalizer 3 overflow | Number of overflows of totalizer value. | FLOAT32 | CDAB | Read | |||
| HR | 3873doc 3874 to 3875 | Volume flow | Unit set by register 2103. | FLOAT32 | CDAB | Read | |||
| HR | 3875doc 3876 to 3877 | Mass flow | Unit set by register 2101. | FLOAT32 | CDAB | Read | |||
| HR | 3976doc 3977 to 3978 | Corrected conductivity | Unit set by register 2121. | FLOAT32 | CDAB | Read | |||
| HR | 4909doc 4910 | Bus address | 1-247. | UINT16 | Read/write | ||||
| HR | 4911doc 4912 | Baudrate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200 | ||||
| HR | 4912doc 4913 | Data transfer mode | Factory setting RTU. | UINT16 | Read/write | 0 = RTU; 1 = ASCII | |||
| HR | 4913doc 4914 | Parity | Even, odd or none; see note on the conflicting picklist codes. | UINT16 | Read/write | ||||
| HR | 4914doc 4915 | Byte order | Float byte sequence; factory 1-0-3-2. | UINT16 | Read/write | 0 = 0-1-2-3; 1 = 3-2-1-0; 2 = 2-3-0-1; 3 = 1-0-3-2 (factory) | |||
| HR | 4915doc 4916 to 4917 | Telegram delay | FLOAT32 | CDAB | ms | Read/write | |||
| HR | 6636doc 6637 to 6638 | Reference density | Unit per the corresponding unit parameter. | FLOAT32 | CDAB | Read | |||
| HR | 7002doc 7003 to 7008 | Serial number | STRING[12] | Read | |||||
| HR | 7237doc 7238 to 7245 | Device name | STRING[16] | Read | |||||
| HR | 7276doc 7277 to 7280 | Firmware version | STRING[8] | Read |
Notes on this map
- Integrator subset of a parameter manual that gives a register for every menu item; display, I/O-module, sensor adjustment, web server and service parameters are left out.
- Float word order follows the Byte order parameter (register 4915). The factory setting 1-0-3-2 sends byte 1, byte 0, byte 3, byte 2, where byte 3 holds sign and exponent, so floats are CDAB. Changing Byte order changes every float.
- Integer parameters are 2 bytes and listed as UINT16; at 1-0-3-2 integers go out MSB first.
- Unit picklists (volume, mass, temperature and so on) are long code lists; read the unit register and look the code up in the manual.
- Totalizer control registers are left out because the extracted option list does not line up cleanly in the source table.
- Parity codes conflict inside the manual: the parameter description lists 2 = None/1 stop bit and 3 = None/2 stop bits, while the register table lists them the other way round. The enum is left out; set parity on the device display or check by reading back.
- The device also supports Modbus ASCII (Data transfer mode, register 4913); the factory setting is RTU.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
What Modbus registers does the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) have?
This map lists 32 registers: 32 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed in the Modbus Application Protocol form, which the manual equates with Modicon 3XXXX/4XXXX numbers (its example: mass flow 2007 = 32007), and the scan list calls register addresses 1-based. Subtract 1 on the wire.
What byte order does the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)?
Start with HR 3873 Volume flow (Volume flow); HR 2010 Corrected volume flow (Corrected volume flow); HR 3875 Mass flow (Mass flow); HR 2018 Flow velocity (Flow velocity); HR 2731 Actual diagnostics (Actual diagnostics).
How do I enable Modbus control of the Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)?
The Modbus RS485 option must be ordered. Bus address, baud rate, parity and byte order are under Expert > Communication > Modbus configuration (registers 4910-4917).
Where is the official Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485) Modbus documentation?
The source is Description of Device Parameters Proline Promag 300 electromagnetic flowmeter (GP01053D/06/EN/04.22-00), revision 2022-08-01, published free by Endress+Hauser at https://bdih-download.endress.com/file/005056A5E3831EED839B635D1828E740/GP01053DEN_0422-00.pdf.
More Endress+Hauser Modbus register maps
- Sensor (water analysis transmitter)
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Liquiline CM44x with the Modbus RS485 or Modbus TCP option, software 1.11.00 and later (SD01189C/07/EN/07.22). The CSFxx sampler and CA80xx analyzer blocks of the same guide are not included.
Also known as: CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448 - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Sensor (clamp-on ultrasonic flowmeter)
Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)
Proline Prosonic Flow W 400 clamp-on flowmeter with the Modbus RS485 output, as described in GP01207D/06/EN/01.24.
Also known as: Prosonic Flow W 400
Other power & energy meters register maps
- Energy meter
Fronius Fronius Smart Meter via Datamanager (SunSpec meter model int+SF)
An energy meter wired to a Fronius Datamanager (or Hybridmanager) over Modbus RTU and republished by it, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Energy meter
inepro Metering PRO2 single-phase energy meter (2026 PRO line)
PRO2-Mod (art. 1201) and PRO2-Mod-Ba (art. 1202, with RTC tariffs) from the 2026 PRO2 user manual version 1.3; the PRO2-S has no Modbus.
Also known as: PRO2-Mod, PRO2-Mod-Ba, PRO2 1U AC 100A Mod T MID, PRO2 1U AC 100A Mod T Ba MID, 1201, 1202 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Sensor (electromagnetic flowmeter)
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
IFC 100 signal converter with the Modbus option, supplementary instructions 4001410101 R01 (08/2014).
Also known as: IFC100, IFC 100 Modbus, KROHNE IFC 100
All power & energy meters Modbus register maps →
Source: Description of Device Parameters Proline Promag 300 electromagnetic flowmeter · GP01053D/06/EN/04.22-00 · rev. 2022-08-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.