Sensor (dew point transmitter) · Modbus register map
Vaisala DMT153 dew point transmitter (Modbus RTU) Modbus register map
Updated 19 November 2026
The DMT153 is a Vaisala DRYCAP transmitter for very dry gases (calibrated range -80 to -20 °C dew point) and the successor to the DMT152. In digital mode it is a Modbus RTU slave on RS-485. This map covers dew/frost point, ppbv and ppmw readings, status and error codes, pressure and molar-mass compensation, purge, analog outputs, limit alarms, test and user adjustment registers.
This page lists 57 Modbus registers for the Vaisala DMT153 dew point transmitter (Modbus RTU) — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- DMT153 dew point transmitter (Modbus RTU)
- Equipment type
- Sensor (dew point transmitter)
- Registers
- 57 (40 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- DMT153, DRYCAP DMT153
- Source document
- DMT153 User Guide · M213149EN-B · rev. 2026-06
Integration notes: Vaisala DMT153 dew point transmitter (Modbus RTU)
Read holding registers 1-8 for all four measurement values (CDAB floats). Write the process pressure to 769 (or 771 for a fixed power-up value) because ppbv and ppmw are calculated from dew point and that pressure.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Dew/frost point temperature | FLOAT32 CDAB | Dew/frost point | Read |
| HR 2 | Water concentration (wet basis) | FLOAT32 CDAB | Water ppbv | Read |
| HR 515 | Error code | INT32 CDAB | Error code | Read |
| HR 522 | Device status | BITMAP16 | Device status | Read |
| HR 625 | Unreliable | UINT16 | Reading not ready | Read |
| HR 768 | Volatile pressure compensation | FLOAT32 CDAB | Live pressure compensation | Read/write |
Enable Modbus control & writes
The transmitter reads pin 5 of the M12 connector at power-up: pin 5 left unconnected gives digital (Modbus RTU over RS-485) mode, pin 5 tied to GND gives analog mode. Change the wiring and power-cycle to switch; both modes cannot run at once.
Byte order & addressing
- Floats are low word first (CDAB); pick "word-swapped" float in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
Network setup
- Defaults: address 240, 19200 baud, None parity, 8 data bits, 2 stop bits.
Watch out for
- Use the test registers (7937 on) to confirm float format and addressing before trusting readings.
- If the unit is reset while pin 5 is floating it comes up in digital mode, not analog.
Vaisala DMT153 dew point transmitter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Dew/frost point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 2doc 3 | Water concentration (wet basis) | FLOAT32 | CDAB | ppbv | Read | |||
| HR | 4doc 5 | Water mass fraction | FLOAT32 | CDAB | ppmw | Read | |||
| HR | 6doc 7 | Dew point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 515doc 516 | Error code | Sum of active error bits. | INT32 | CDAB | Read | bit 0 = Device settings corrupted; bit 1 = Sensor purge in progress; bit 2 = Ambient temperature out of range; bit 3 = Supply voltage too low; bit 4 = Supply voltage too high; bit 5 = Temperature sensor failure (short circuit); bit 6 = Temperature sensor failure (open circuit); bit 7 = Humidity sensor failure (open circuit); bit 8 = Humidity sensor failure (short circuit); bit 9 = Calibration has expired; bit 10 = Calibration is about to expire | ||
| HR | 521doc 522 | Td/f measurement status | 0 = OK. | BITMAP16 | Read | bit 0 = Not available; bit 1 = Not reliable; bit 2 = Under range; bit 3 = Over range; bit 5 = Value locked; bit 7 = Sensor failure; bit 8 = Measurement not ready | |||
| HR | 522doc 523 | Device status | 0 = OK. | BITMAP16 | Read | bit 0 = Critical error, maintenance needed; bit 1 = Error, may recover automatically; bit 2 = Warning; bit 3 = Notification; bit 4 = Calibration mode active | |||
| HR | 624doc 625 | Value locked | UINT16 | Read | 0 = No; 1 = Value locked | ||||
| HR | 625doc 626 | Unreliable | UINT16 | Read | 0 = No; 1 = Measurement not ready | ||||
| HR | 640doc 641 | Time until next sensor purge | INT32 | CDAB | s | Read | |||
| HR | 768doc 769 | Volatile pressure compensation | 1-50000 hPa; cleared at reset. | FLOAT32 | CDAB | hPa | Read/write | ||
| HR | 770doc 771 | Power-up pressure compensation | Default 1013.25 hPa. | FLOAT32 | CDAB | hPa | Read/write | ||
| HR | 794doc 795 | Filtering factor | 0-1; used when 1282 is on. | FLOAT32 | CDAB | Read/write | |||
| HR | 800doc 801 | Molar mass of gas | Default 28.02; used for ppmw. | FLOAT32 | CDAB | g/mol | Read/write | ||
| HR | 816doc 817 | Purge prevention duration | 1-168 h. | FLOAT32 | CDAB | h | Read/write | ||
| HR | 1281doc 1282 | Filtering on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1284doc 1285 | Start sensor purge | Write 1 to start; reads 1-100 progress, 0 done. | INT16 | Read/write | ||||
| HR | 1285doc 1286 | Interval purge on/off | 0 disables until restart. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 1296doc 1297 | Control pin function in analog mode | UINT16 | Read/write | 0 = None; 1 = Start sensor purge; 2 = Prevent sensor purge | ||||
| HR | 1536doc 1537 | Modbus address | 1-247, default 240. | INT16 | Read/write | ||||
| HR | 1537doc 1538 | Bit rate | UINT16 | Read/write | 0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600; 9 = 115200 | ||||
| HR | 1538doc 1539 | Parity, data, stop bits | Default 1 (None, 8, 2). | UINT16 | Read/write | 0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2 | |||
| HR | 1539doc 1540 | Response delay | 0-1000 ms. | INT16 | ms | Read/write | |||
| HR | 1541doc 1542 | Restart device | Write 1 to restart. | INT16 | Write | ||||
| HR | 1792doc 1793 | AOUT1 output mode | UINT16 | Read/write | 0 = Off; 1 = 4-20 mA; 2 = 0-20 mA | ||||
| HR | 1793doc 1794 | AOUT1 output parameter | Register address of the output value. | UINT16 | Read/write | ||||
| HR | 1794doc 1795 | AOUT1 scale low end | FLOAT32 | CDAB | Read/write | ||||
| HR | 1796doc 1797 | AOUT1 scale high end | FLOAT32 | CDAB | Read/write | ||||
| HR | 1798doc 1799 | AOUT1 error output level | 0-25 mA. | FLOAT32 | CDAB | mA | Read/write | ||
| HR | 1808doc 1809 | AOUT1 output level | FLOAT32 | CDAB | mA | Read | |||
| HR | 2048doc 2049 | AOUT2 output mode | UINT16 | Read/write | 0 = Off; 1 = 0-10 V; 2 = 0-5 V | ||||
| HR | 2049doc 2050 | AOUT2 output parameter | Register address of the output value. | UINT16 | Read/write | ||||
| HR | 2050doc 2051 | AOUT2 scale low end | FLOAT32 | CDAB | Read/write | ||||
| HR | 2052doc 2053 | AOUT2 scale high end | FLOAT32 | CDAB | Read/write | ||||
| HR | 2054doc 2055 | AOUT2 error output level | 0-11 V. | FLOAT32 | CDAB | V | Read/write | ||
| HR | 2064doc 2065 | AOUT2 output level | FLOAT32 | CDAB | V | Read | |||
| HR | 3585doc 3586 | Limit alarm 1 parameter | Register address: 0x0000, 0x0002, 0x0004 or 0x0006. | UINT16 | Read/write | ||||
| HR | 3586doc 3587 | Limit alarm 1 activate below | FLOAT32 | CDAB | Read/write | ||||
| HR | 3588doc 3589 | Limit alarm 1 activate above | FLOAT32 | CDAB | Read/write | ||||
| HR | 3590doc 3591 | Limit alarm 1 hysteresis | FLOAT32 | CDAB | Read/write | ||||
| HR | 3593doc 3594 | Limit alarm 1 output state | UINT16 | Read | 0 = Off; 1 = Active | ||||
| HR | 3841doc 3842 | Limit alarm 2 parameter | Register address: 0x0000, 0x0002, 0x0004 or 0x0006. | UINT16 | Read/write | ||||
| HR | 3842doc 3843 | Limit alarm 2 activate below | FLOAT32 | CDAB | Read/write | ||||
| HR | 3844doc 3845 | Limit alarm 2 activate above | FLOAT32 | CDAB | Read/write | ||||
| HR | 3846doc 3847 | Limit alarm 2 hysteresis | FLOAT32 | CDAB | Read/write | ||||
| HR | 3849doc 3850 | Limit alarm 2 output state | UINT16 | Read | 0 = Off; 1 = Active | ||||
| HR | 7680doc 7681 | Restore factory settings | Write 1. | INT16 | Write | ||||
| HR | 7936doc 7937 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 7938 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read | |||
| HR | 7939doc 7940 | Text string test | Reads the text "-123.45". | STRING[8] | Read | ||||
| HR | 8192doc 8193 | Calibration passcode | 1300 enables calibration mode. | INT16 | Read/write | ||||
| HR | 8448doc 8449 | User adjustment reference point 1 | -80...-30 °C. | FLOAT32 | CDAB | °C | Read/write | ||
| HR | 8450doc 8451 | User adjustment measured point 1 | FLOAT32 | CDAB | °C | Read/write | |||
| HR | 8452doc 8453 | User adjustment reference point 2 | -80...-30 °C. | FLOAT32 | CDAB | °C | Read/write | ||
| HR | 8454doc 8455 | User adjustment measured point 2 | FLOAT32 | CDAB | °C | Read/write | |||
| HR | 8480doc 8481 | Activate adjustment | Write 1. | INT16 | Write | ||||
| HR | 8481doc 8482 | Restore factory adjustment | Write 1. | INT16 | Write |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16.
- 32-bit floats and 32-bit integers put the least significant word at the listed register (CDAB). The guide states this and its worked read example confirms it.
- Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.
- The 16-bit boolean output states 3594/3850 and the lock/unreliable flags 625/626 read 1 when active.
- Left out: device tag text (2561) and the calibration date/text block (8194-8228), which need multi-register text writes.
- Analog output clipping and error limits (1801-1807, 2057-2063) are left out.
- Calibration mode is turned on by writing 1300 to register 8193; the guide's adjustment procedures run in calibration mode.
- The four limit-alarm and analog-output parameter registers take the register address (hex) of the value to follow, as listed in the guide.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala DMT153 dew point transmitter (Modbus RTU)
What Modbus registers does the Vaisala DMT153 dew point transmitter (Modbus RTU) have?
This map lists 57 registers: 57 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala DMT153 dew point transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.
What byte order does the Vaisala DMT153 dew point transmitter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala DMT153 dew point transmitter (Modbus RTU)?
Start with HR 0 Dew/frost point temperature (Dew/frost point); HR 2 Water concentration (wet basis) (Water ppbv); HR 515 Error code (Error code); HR 522 Device status (Device status); HR 625 Unreliable (Reading not ready); HR 768 Volatile pressure compensation (Live pressure compensation).
How do I enable Modbus control of the Vaisala DMT153 dew point transmitter (Modbus RTU)?
The transmitter reads pin 5 of the M12 connector at power-up: pin 5 left unconnected gives digital (Modbus RTU over RS-485) mode, pin 5 tied to GND gives analog mode. Change the wiring and power-cycle to switch; both modes cannot run at once.
Where is the official Vaisala DMT153 dew point transmitter (Modbus RTU) Modbus documentation?
The source is DMT153 User Guide (M213149EN-B), revision 2026-06, published free by Vaisala at https://docs.vaisala.com/r/M213149EN-B/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor - Sensor (duct averaging temperature)
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
ACI Averaging Series copper and flexible duct averaging temperature sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000932).
Also known as: Copper Averaging, Flexible Averaging, Averaging Series BACnet Modbus - Actuator / valve (damper and valve actuator)
Belimo Air/water actuators with Modbus RTU (..24A-MOD)
Belimo ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD air/water actuators, per Modbus interface description edition 2026-05 / V3.08.
Also known as: LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD - Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge
All valves, actuators & sensors Modbus register maps →
Source: DMT153 User Guide · M213149EN-B · rev. 2026-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.