Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The GMW87 is the Modbus RTU member of the Vaisala GMW80 family of CO2 wall transmitters for building automation. Address, bit rate and parity are set with DIP switches. This map covers CO2 and internal temperature in float and integer form, status registers and the integer and float test registers.

This page lists 9 Modbus registers for the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
GMW87 CO2 and temperature wall transmitter (Modbus RTU)
Equipment type
Sensor (CO2 wall transmitter)
Registers
9 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
GMW87, GMW80 series Modbus
Source document
GMW80 Series User Guide · M211748EN-H · rev. 2021-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)

Integration in brief

Read holding registers 1-2 for CO2 as a CDAB float, or 257 as an integer. Status 513 is 0 when the device is OK.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Measured CO2FLOAT32 CDABCO2 ppmRead
HR 256Measured CO2 (integer)INT16CO2 ppm (integer)Read
HR 512Device statusUINT16Device statusRead
HR 519CO2 measurement statusBITMAP16CO2 measurement statusRead

Enable Modbus control & writes

Set the Modbus address, bit rate and parity with the DIP switches on the transmitter board before power-up.

Byte order & addressing

Network setup

Watch out for

Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

9 of 9 shown
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Measured CO2FLOAT32CDABppmRead
HR4doc 5Measured temperatureInternal device temperature; accuracy not specified.FLOAT32CDAB°CRead
HR256doc 257Measured CO2 (integer)INT16ppmRead
HR258doc 259Measured temperature (integer)Internal device temperature.INT16× 0.1°CRead
HR512doc 513Device status0 = OK; other values are listed in the troubleshooting section.UINT16Read
HR518doc 519Temperature measurement status0 = OK.BITMAP16Readbit 2 = Under range; bit 3 = Over range; bit 7 = Sensor failure; bit 8 = Measurement not ready (CO2 only)
HR519doc 520CO2 measurement statusBITMAP16Readbit 2 = Under range; bit 3 = Over range; bit 7 = Sensor failure; bit 8 = Measurement not ready (CO2 only)
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)

What Modbus registers does the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) have?

This map lists 9 registers: 9 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)?

Start with HR 0 Measured CO2 (CO2 ppm); HR 256 Measured CO2 (integer) (CO2 ppm (integer)); HR 512 Device status (Device status); HR 519 CO2 measurement status (CO2 measurement status).

How do I enable Modbus control of the Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)?

Set the Modbus address, bit rate and parity with the DIP switches on the transmitter board before power-up.

Where is the official Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU) Modbus documentation?

The source is GMW80 Series User Guide (M211748EN-H), revision 2021-10, published free by Vaisala at https://docs.vaisala.com/r/M211748EN-H/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: GMW80 Series User Guide · M211748EN-H · rev. 2021-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.