Sensor (chart recorder) · Modbus register map

Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus register map

Updated 17 November 2026

Short answer

The HR-700 is a hybrid chart recorder with a Modbus map for up to six channels. From firmware 4.00 it offers Modbus RTU on RS-485/RS-232C alongside Shinko's original protocol. Input registers carry the clock, recording status, per-channel alarm flags, measured values as scaled integers and as IEEE floats, and unit text; holding registers carry recording commands and channel, alarm and communication settings.

This page lists 240 Modbus registers for the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) — 196 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Equipment type
Sensor (chart recorder)
Registers
240 (196 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
Body version 4.00 or later (map version 01)
Also known as
HR-700
Source document
HR-700 Hybrid Recorder Communication Command Manual · No. HR7CE4 · rev. 2018-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)

Integration in brief

Set Communication protocol to Modbus RTU with 8-bit data, then read input registers 30107-30130 for the six channels (integer plus decimal point, or IEEE float) and 30101-30106 for alarm flags; start and stop recording by writing AA01H/AA00H to 40101.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 118CH1 measurement (float)FLOAT32 ABCDCH1 measured value (float)Read
IR 106CH1 measurement (integer)INT16CH1 measured value (integer)Read
IR 112CH1 decimal point positionUINT16CH1 decimal pointRead
IR 100CH1 channel statusBITMAP16CH1 alarm flagsRead
IR 56Recording statusUINT16Recording statusRead
HR 100Recording start/stopUINT16Recording start/stop commandWrite
HR 103Save the settingsUINT16Save settings commandWrite

Enable Modbus control & writes

Needs body firmware 4.00 or later. Set Communication protocol to Modbus RTU and data length to 8 bit in the recorder's communication settings (also exposed at 40973 and 40976).

Byte order & addressing

Network setup

Watch out for

Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

240 of 240 shown
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Model typeASCII, 8 registers: MULTI (multipoint) or PEN.STRING[16]Read
IR8doc 30009Software versionASCII, 16 registers.STRING[32]Read
IR24doc 30025Modbus map versionUINT16Read
IR50doc 30051Clock yearTwo-digit year (0-99).UINT16Read
IR51doc 30052Clock monthUINT16Read
IR52doc 30053Clock dayUINT16Read
IR53doc 30054Clock hourUINT16Read
IR54doc 30055Clock minuteUINT16Read
IR55doc 30056Clock secondUINT16Read
IR56doc 30057Recording statusUINT16Read0 = Recording not in progress; 1 = Recording in progress
IR57doc 30058Chart sensor statusUINT16Read0 = With chart; 1 = Without chart
IR58doc 30059Manual print statusUINT16Read0 = Print stops; 1 = During printing
IR59doc 30060List print statusUINT16Read0 = Print stops; 1 = During printing
IR60doc 30061Engineering list print statusUINT16Read0 = Print stops; 1 = During printing
IR100doc 30101CH1 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR101doc 30102CH2 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR102doc 30103CH3 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR103doc 30104CH4 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR104doc 30105CH5 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR105doc 30106CH6 channel statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON
IR106doc 30107CH1 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR107doc 30108CH2 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR108doc 30109CH3 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR109doc 30110CH4 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR110doc 30111CH5 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR111doc 30112CH6 measurement (integer)-32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range.INT16Read
IR112doc 30113CH1 decimal point position0-4 digits after the decimal point.UINT16Read
IR113doc 30114CH2 decimal point position0-4 digits after the decimal point.UINT16Read
IR114doc 30115CH3 decimal point position0-4 digits after the decimal point.UINT16Read
IR115doc 30116CH4 decimal point position0-4 digits after the decimal point.UINT16Read
IR116doc 30117CH5 decimal point position0-4 digits after the decimal point.UINT16Read
IR117doc 30118CH6 decimal point position0-4 digits after the decimal point.UINT16Read
IR118doc 30119CH1 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR120doc 30121CH2 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR122doc 30123CH3 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR124doc 30125CH4 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR126doc 30127CH5 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR128doc 30129CH6 measurement (float)IEEE float, high-order word first.FLOAT32ABCDRead
IR130doc 30131CH1 unitCurrent unit text, 4 registers.STRING[8]Read
IR134doc 30135CH2 unitCurrent unit text, 4 registers.STRING[8]Read
IR138doc 30139CH3 unitCurrent unit text, 4 registers.STRING[8]Read
IR142doc 30143CH4 unitCurrent unit text, 4 registers.STRING[8]Read
IR146doc 30147CH5 unitCurrent unit text, 4 registers.STRING[8]Read
IR150doc 30151CH6 unitCurrent unit text, 4 registers.STRING[8]Read
HR100doc 40101Recording start/stopWrite AA01H to start, AA00H to stop; ignored if DI controls it.UINT16Write43520 = Stop (AA00H); 43521 = Start (AA01H)
HR103doc 40104Save the settingsWrite AA01H to store parameter writes.UINT16Write43521 = Save (AA01H)
HR104doc 40105Manual printUINT16Write43520 = Stop (AA00H); 43521 = Start (AA01H)
HR105doc 40106LIST printUINT16Write43520 = Stop (AA00H); 43521 = Start (AA01H)
HR106doc 40107ELIST printUINT16Write43520 = Stop (AA00H); 43521 = Start (AA01H)
HR107doc 40108Comments 1 printUINT16Write43521 = Sync (AA01H); 43522 = Async (AA02H)
HR108doc 40109Comments 2 printUINT16Write43521 = Sync (AA01H); 43522 = Async (AA02H)
HR109doc 40110Comments 3 printUINT16Write43521 = Sync (AA01H); 43522 = Async (AA02H)
HR110doc 40111Clock setAA01H then year..second in one 7-register write (function 10H).UINT16Write43521 = Run (AA01H)
HR111doc 40112Clock set year0-99; part of the 7-register clock write.UINT16Write
HR112doc 40113Clock set month1-12; part of the 7-register clock write.UINT16Write
HR113doc 40114Clock set day1-31; part of the 7-register clock write.UINT16Write
HR114doc 40115Clock set hour0-23; part of the 7-register clock write.UINT16Write
HR115doc 40116Clock set minute0-59; part of the 7-register clock write.UINT16Write
HR116doc 40117Clock set second0-59; part of the 7-register clock write.UINT16Write
HR200doc 40201CH1 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR201doc 40202CH1 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR202doc 40203CH1 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR203doc 40204CH1 measurement range lowRange-dependent integer.INT16Read/write
HR204doc 40205CH1 measurement range highRange-dependent integer.INT16Read/write
HR205doc 40206CH1 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR206doc 40207CH1 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR207doc 40208CH1 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR216doc 40217CH1 digital printUINT16Read/write0 = OFF; 1 = ON
HR222doc 40223CH1 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR223doc 40224CH1 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR224doc 40225CH1 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR225doc 40226CH1 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR226doc 40227CH1 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR227doc 40228CH1 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR228doc 40229CH1 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR229doc 40230CH1 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR230doc 40231CH1 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR231doc 40232CH1 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR232doc 40233CH1 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR233doc 40234CH1 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR234doc 40235CH1 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR235doc 40236CH1 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR236doc 40237CH1 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR237doc 40238CH1 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR238doc 40239CH1 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR239doc 40240CH1 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR240doc 40241CH1 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR241doc 40242CH1 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR300doc 40301CH2 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR301doc 40302CH2 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR302doc 40303CH2 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR303doc 40304CH2 measurement range lowRange-dependent integer.INT16Read/write
HR304doc 40305CH2 measurement range highRange-dependent integer.INT16Read/write
HR305doc 40306CH2 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR306doc 40307CH2 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR307doc 40308CH2 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR316doc 40317CH2 digital printUINT16Read/write0 = OFF; 1 = ON
HR322doc 40323CH2 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR323doc 40324CH2 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR324doc 40325CH2 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR325doc 40326CH2 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR326doc 40327CH2 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR327doc 40328CH2 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR328doc 40329CH2 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR329doc 40330CH2 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR330doc 40331CH2 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR331doc 40332CH2 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR332doc 40333CH2 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR333doc 40334CH2 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR334doc 40335CH2 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR335doc 40336CH2 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR336doc 40337CH2 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR337doc 40338CH2 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR338doc 40339CH2 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR339doc 40340CH2 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR340doc 40341CH2 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR341doc 40342CH2 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR400doc 40401CH3 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR401doc 40402CH3 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR402doc 40403CH3 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR403doc 40404CH3 measurement range lowRange-dependent integer.INT16Read/write
HR404doc 40405CH3 measurement range highRange-dependent integer.INT16Read/write
HR405doc 40406CH3 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR406doc 40407CH3 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR407doc 40408CH3 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR416doc 40417CH3 digital printUINT16Read/write0 = OFF; 1 = ON
HR422doc 40423CH3 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR423doc 40424CH3 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR424doc 40425CH3 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR425doc 40426CH3 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR426doc 40427CH3 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR427doc 40428CH3 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR428doc 40429CH3 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR429doc 40430CH3 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR430doc 40431CH3 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR431doc 40432CH3 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR432doc 40433CH3 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR433doc 40434CH3 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR434doc 40435CH3 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR435doc 40436CH3 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR436doc 40437CH3 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR437doc 40438CH3 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR438doc 40439CH3 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR439doc 40440CH3 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR440doc 40441CH3 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR441doc 40442CH3 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR500doc 40501CH4 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR501doc 40502CH4 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR502doc 40503CH4 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR503doc 40504CH4 measurement range lowRange-dependent integer.INT16Read/write
HR504doc 40505CH4 measurement range highRange-dependent integer.INT16Read/write
HR505doc 40506CH4 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR506doc 40507CH4 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR507doc 40508CH4 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR516doc 40517CH4 digital printUINT16Read/write0 = OFF; 1 = ON
HR522doc 40523CH4 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR523doc 40524CH4 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR524doc 40525CH4 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR525doc 40526CH4 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR526doc 40527CH4 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR527doc 40528CH4 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR528doc 40529CH4 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR529doc 40530CH4 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR530doc 40531CH4 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR531doc 40532CH4 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR532doc 40533CH4 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR533doc 40534CH4 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR534doc 40535CH4 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR535doc 40536CH4 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR536doc 40537CH4 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR537doc 40538CH4 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR538doc 40539CH4 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR539doc 40540CH4 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR540doc 40541CH4 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR541doc 40542CH4 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR600doc 40601CH5 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR601doc 40602CH5 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR602doc 40603CH5 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR603doc 40604CH5 measurement range lowRange-dependent integer.INT16Read/write
HR604doc 40605CH5 measurement range highRange-dependent integer.INT16Read/write
HR605doc 40606CH5 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR606doc 40607CH5 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR607doc 40608CH5 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR616doc 40617CH5 digital printUINT16Read/write0 = OFF; 1 = ON
HR622doc 40623CH5 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR623doc 40624CH5 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR624doc 40625CH5 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR625doc 40626CH5 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR626doc 40627CH5 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR627doc 40628CH5 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR628doc 40629CH5 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR629doc 40630CH5 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR630doc 40631CH5 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR631doc 40632CH5 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR632doc 40633CH5 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR633doc 40634CH5 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR634doc 40635CH5 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR635doc 40636CH5 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR636doc 40637CH5 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR637doc 40638CH5 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR638doc 40639CH5 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR639doc 40640CH5 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR640doc 40641CH5 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR641doc 40642CH5 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR700doc 40701CH6 modeUINT16Read/write0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip
HR701doc 40702CH6 input type (range code)0-34; range code table in manual section 6.5.5.UINT16Read/write
HR702doc 40703CH6 reference channelChannel used by DELT/SIGM/MEAN; not settable on CH1.UINT16Read/write
HR703doc 40704CH6 measurement range lowRange-dependent integer.INT16Read/write
HR704doc 40705CH6 measurement range highRange-dependent integer.INT16Read/write
HR705doc 40706CH6 scaling range low-32000..32000; uses the decimal point register.INT16Read/write
HR706doc 40707CH6 scaling range high-32000..32000; uses the decimal point register.INT16Read/write
HR707doc 40708CH6 decimal point position0-4; applies when scaling is ON.UINT16Read/write
HR716doc 40717CH6 digital printUINT16Read/write0 = OFF; 1 = ON
HR722doc 40723CH6 alarm 1 actionUINT16Read/write0 = OFF; 1 = ON
HR723doc 40724CH6 alarm 1 typeUINT16Read/write0 = H (high); 1 = L (low)
HR724doc 40725CH6 alarm 1 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR725doc 40726CH6 alarm 1 relay outputUINT16Read/write0 = OFF; 1 = ON
HR726doc 40727CH6 alarm 1 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR727doc 40728CH6 alarm 2 actionUINT16Read/write0 = OFF; 1 = ON
HR728doc 40729CH6 alarm 2 typeUINT16Read/write0 = H (high); 1 = L (low)
HR729doc 40730CH6 alarm 2 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR730doc 40731CH6 alarm 2 relay outputUINT16Read/write0 = OFF; 1 = ON
HR731doc 40732CH6 alarm 2 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR732doc 40733CH6 alarm 3 actionUINT16Read/write0 = OFF; 1 = ON
HR733doc 40734CH6 alarm 3 typeUINT16Read/write0 = H (high); 1 = L (low)
HR734doc 40735CH6 alarm 3 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR735doc 40736CH6 alarm 3 relay outputUINT16Read/write0 = OFF; 1 = ON
HR736doc 40737CH6 alarm 3 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR737doc 40738CH6 alarm 4 actionUINT16Read/write0 = OFF; 1 = ON
HR738doc 40739CH6 alarm 4 typeUINT16Read/write0 = H (high); 1 = L (low)
HR739doc 40740CH6 alarm 4 set value-32000..32000, scaling-dependent decimal point.INT16Read/write
HR740doc 40741CH6 alarm 4 relay outputUINT16Read/write0 = OFF; 1 = ON
HR741doc 40742CH6 alarm 4 DO numberMultipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3).UINT16Read/write
HR802doc 40803Recording periodMultipoint type only.UINT16Read/write0 = 10 s; 1 = 20 s; 2 = 30 s; 3 = 60 s
HR970doc 40971Host addressSlave address 1-32.UINT16Read/write
HR971doc 40972Communication speedUINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps
HR972doc 40973Data lengthModbus RTU needs 8 bit.UINT16Read/write0 = 7 bit; 1 = 8 bit
HR973doc 40974ParityUINT16Read/write0 = Even; 1 = Odd; 2 = OFF
HR974doc 40975Stop bitUINT16Read/write0 = 1 bit; 1 = 2 bit
HR975doc 40976Communication protocolUINT16Read/write0 = Original; 1 = Modbus RTU

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)

What Modbus registers does the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) have?

This map lists 240 registers: 44 input registers, 196 holding registers. 196 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints Modicon numbers (30001, 40101) next to a hex relative address; 30001 and 40001 are relative address 0, so subtract 30001 or 40001 to get the wire address. The manual's function 04 example reads relative address 0032H, which is 30051 (clock year).

What byte order does the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)?

Start with IR 118 CH1 measurement (float) (CH1 measured value (float)); IR 106 CH1 measurement (integer) (CH1 measured value (integer)); IR 112 CH1 decimal point position (CH1 decimal point); IR 100 CH1 channel status (CH1 alarm flags); IR 56 Recording status (Recording status); HR 100 Recording start/stop (Recording start/stop command); HR 103 Save the settings (Save settings command).

How do I enable Modbus control of the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)?

Needs body firmware 4.00 or later. Set Communication protocol to Modbus RTU and data length to 8 bit in the recorder's communication settings (also exposed at 40973 and 40976).

Where is the official Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus documentation?

The source is HR-700 Hybrid Recorder Communication Command Manual (No. HR7CE4), revision 2018-05, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/HR7CE4.pdf.