- HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Sensor (chart recorder) · Modbus register map
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus register map
Updated 17 November 2026
The HR-700 is a hybrid chart recorder with a Modbus map for up to six channels. From firmware 4.00 it offers Modbus RTU on RS-485/RS-232C alongside Shinko's original protocol. Input registers carry the clock, recording status, per-channel alarm flags, measured values as scaled integers and as IEEE floats, and unit text; holding registers carry recording commands and channel, alarm and communication settings.
This page lists 240 Modbus registers for the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) — 196 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
- Equipment type
- Sensor (chart recorder)
- Registers
- 240 (196 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Body version 4.00 or later (map version 01)
- Also known as
- HR-700
Integration notes: Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Set Communication protocol to Modbus RTU with 8-bit data, then read input registers 30107-30130 for the six channels (integer plus decimal point, or IEEE float) and 30101-30106 for alarm flags; start and stop recording by writing AA01H/AA00H to 40101.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 118 | CH1 measurement (float) | FLOAT32 ABCD | CH1 measured value (float) | Read |
| IR 106 | CH1 measurement (integer) | INT16 | CH1 measured value (integer) | Read |
| IR 112 | CH1 decimal point position | UINT16 | CH1 decimal point | Read |
| IR 100 | CH1 channel status | BITMAP16 | CH1 alarm flags | Read |
| IR 56 | Recording status | UINT16 | Recording status | Read |
| HR 100 | Recording start/stop | UINT16 | Recording start/stop command | Write |
| HR 103 | Save the settings | UINT16 | Save settings command | Write |
Enable Modbus control & writes
Needs body firmware 4.00 or later. Set Communication protocol to Modbus RTU and data length to 8 bit in the recorder's communication settings (also exposed at 40973 and 40976).
Byte order & addressing
- 7-bit data length does not work with Modbus RTU.
- Out-of-range integer readings return 8181H (minus side) or 7E7EH (plus side).
- Clock set must be one 7-register write starting at 40111.
Network setup
- Slave address 1-247 per the overview table (host address setting 40971 allows 1-32); speeds 1200-38400 bps; parity none/even/odd; 1 or 2 stop bits.
Watch out for
- Function 06 writes one register and 10H up to 123; reads are limited to 123 registers.
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Model type | ASCII, 8 registers: MULTI (multipoint) or PEN. | STRING[16] | Read | ||||
| IR | 8doc 30009 | Software version | ASCII, 16 registers. | STRING[32] | Read | ||||
| IR | 24doc 30025 | Modbus map version | UINT16 | Read | |||||
| IR | 50doc 30051 | Clock year | Two-digit year (0-99). | UINT16 | Read | ||||
| IR | 51doc 30052 | Clock month | UINT16 | Read | |||||
| IR | 52doc 30053 | Clock day | UINT16 | Read | |||||
| IR | 53doc 30054 | Clock hour | UINT16 | Read | |||||
| IR | 54doc 30055 | Clock minute | UINT16 | Read | |||||
| IR | 55doc 30056 | Clock second | UINT16 | Read | |||||
| IR | 56doc 30057 | Recording status | UINT16 | Read | 0 = Recording not in progress; 1 = Recording in progress | ||||
| IR | 57doc 30058 | Chart sensor status | UINT16 | Read | 0 = With chart; 1 = Without chart | ||||
| IR | 58doc 30059 | Manual print status | UINT16 | Read | 0 = Print stops; 1 = During printing | ||||
| IR | 59doc 30060 | List print status | UINT16 | Read | 0 = Print stops; 1 = During printing | ||||
| IR | 60doc 30061 | Engineering list print status | UINT16 | Read | 0 = Print stops; 1 = During printing | ||||
| IR | 100doc 30101 | CH1 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 101doc 30102 | CH2 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 102doc 30103 | CH3 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 103doc 30104 | CH4 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 104doc 30105 | CH5 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 105doc 30106 | CH6 channel status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 3 = Alarm 4 ON | ||||
| IR | 106doc 30107 | CH1 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 107doc 30108 | CH2 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 108doc 30109 | CH3 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 109doc 30110 | CH4 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 110doc 30111 | CH5 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 111doc 30112 | CH6 measurement (integer) | -32000..32000; apply CH decimal point. 8181H/7E7EH = under/over range. | INT16 | Read | ||||
| IR | 112doc 30113 | CH1 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 113doc 30114 | CH2 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 114doc 30115 | CH3 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 115doc 30116 | CH4 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 116doc 30117 | CH5 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 117doc 30118 | CH6 decimal point position | 0-4 digits after the decimal point. | UINT16 | Read | ||||
| IR | 118doc 30119 | CH1 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | CH2 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | CH3 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | CH4 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | CH5 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | CH6 measurement (float) | IEEE float, high-order word first. | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | CH1 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| IR | 134doc 30135 | CH2 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| IR | 138doc 30139 | CH3 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| IR | 142doc 30143 | CH4 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| IR | 146doc 30147 | CH5 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| IR | 150doc 30151 | CH6 unit | Current unit text, 4 registers. | STRING[8] | Read | ||||
| HR | 100doc 40101 | Recording start/stop | Write AA01H to start, AA00H to stop; ignored if DI controls it. | UINT16 | Write | 43520 = Stop (AA00H); 43521 = Start (AA01H) | |||
| HR | 103doc 40104 | Save the settings | Write AA01H to store parameter writes. | UINT16 | Write | 43521 = Save (AA01H) | |||
| HR | 104doc 40105 | Manual print | UINT16 | Write | 43520 = Stop (AA00H); 43521 = Start (AA01H) | ||||
| HR | 105doc 40106 | LIST print | UINT16 | Write | 43520 = Stop (AA00H); 43521 = Start (AA01H) | ||||
| HR | 106doc 40107 | ELIST print | UINT16 | Write | 43520 = Stop (AA00H); 43521 = Start (AA01H) | ||||
| HR | 107doc 40108 | Comments 1 print | UINT16 | Write | 43521 = Sync (AA01H); 43522 = Async (AA02H) | ||||
| HR | 108doc 40109 | Comments 2 print | UINT16 | Write | 43521 = Sync (AA01H); 43522 = Async (AA02H) | ||||
| HR | 109doc 40110 | Comments 3 print | UINT16 | Write | 43521 = Sync (AA01H); 43522 = Async (AA02H) | ||||
| HR | 110doc 40111 | Clock set | AA01H then year..second in one 7-register write (function 10H). | UINT16 | Write | 43521 = Run (AA01H) | |||
| HR | 111doc 40112 | Clock set year | 0-99; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 112doc 40113 | Clock set month | 1-12; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 113doc 40114 | Clock set day | 1-31; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 114doc 40115 | Clock set hour | 0-23; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 115doc 40116 | Clock set minute | 0-59; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 116doc 40117 | Clock set second | 0-59; part of the 7-register clock write. | UINT16 | Write | ||||
| HR | 200doc 40201 | CH1 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 201doc 40202 | CH1 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 202doc 40203 | CH1 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 203doc 40204 | CH1 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 204doc 40205 | CH1 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 205doc 40206 | CH1 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 206doc 40207 | CH1 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 207doc 40208 | CH1 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 216doc 40217 | CH1 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 222doc 40223 | CH1 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 223doc 40224 | CH1 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 224doc 40225 | CH1 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 225doc 40226 | CH1 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 226doc 40227 | CH1 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 227doc 40228 | CH1 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 228doc 40229 | CH1 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 229doc 40230 | CH1 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 230doc 40231 | CH1 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 231doc 40232 | CH1 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 232doc 40233 | CH1 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 233doc 40234 | CH1 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 234doc 40235 | CH1 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 235doc 40236 | CH1 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 236doc 40237 | CH1 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 237doc 40238 | CH1 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 238doc 40239 | CH1 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 239doc 40240 | CH1 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 240doc 40241 | CH1 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 241doc 40242 | CH1 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 300doc 40301 | CH2 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 301doc 40302 | CH2 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 302doc 40303 | CH2 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 303doc 40304 | CH2 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 304doc 40305 | CH2 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 305doc 40306 | CH2 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 306doc 40307 | CH2 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 307doc 40308 | CH2 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 316doc 40317 | CH2 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 322doc 40323 | CH2 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 323doc 40324 | CH2 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 324doc 40325 | CH2 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 325doc 40326 | CH2 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 326doc 40327 | CH2 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 327doc 40328 | CH2 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 328doc 40329 | CH2 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 329doc 40330 | CH2 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 330doc 40331 | CH2 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 331doc 40332 | CH2 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 332doc 40333 | CH2 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 333doc 40334 | CH2 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 334doc 40335 | CH2 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 335doc 40336 | CH2 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 336doc 40337 | CH2 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 337doc 40338 | CH2 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 338doc 40339 | CH2 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 339doc 40340 | CH2 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 340doc 40341 | CH2 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 341doc 40342 | CH2 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 400doc 40401 | CH3 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 401doc 40402 | CH3 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 402doc 40403 | CH3 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 403doc 40404 | CH3 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 404doc 40405 | CH3 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 405doc 40406 | CH3 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 406doc 40407 | CH3 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 407doc 40408 | CH3 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 416doc 40417 | CH3 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 422doc 40423 | CH3 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 423doc 40424 | CH3 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 424doc 40425 | CH3 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 425doc 40426 | CH3 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 426doc 40427 | CH3 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 427doc 40428 | CH3 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 428doc 40429 | CH3 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 429doc 40430 | CH3 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 430doc 40431 | CH3 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 431doc 40432 | CH3 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 432doc 40433 | CH3 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 433doc 40434 | CH3 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 434doc 40435 | CH3 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 435doc 40436 | CH3 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 436doc 40437 | CH3 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 437doc 40438 | CH3 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 438doc 40439 | CH3 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 439doc 40440 | CH3 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 440doc 40441 | CH3 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 441doc 40442 | CH3 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 500doc 40501 | CH4 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 501doc 40502 | CH4 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 502doc 40503 | CH4 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 503doc 40504 | CH4 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 504doc 40505 | CH4 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 505doc 40506 | CH4 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 506doc 40507 | CH4 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 507doc 40508 | CH4 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 516doc 40517 | CH4 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 522doc 40523 | CH4 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 523doc 40524 | CH4 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 524doc 40525 | CH4 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 525doc 40526 | CH4 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 526doc 40527 | CH4 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 527doc 40528 | CH4 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 528doc 40529 | CH4 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 529doc 40530 | CH4 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 530doc 40531 | CH4 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 531doc 40532 | CH4 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 532doc 40533 | CH4 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 533doc 40534 | CH4 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 534doc 40535 | CH4 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 535doc 40536 | CH4 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 536doc 40537 | CH4 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 537doc 40538 | CH4 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 538doc 40539 | CH4 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 539doc 40540 | CH4 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 540doc 40541 | CH4 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 541doc 40542 | CH4 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 600doc 40601 | CH5 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 601doc 40602 | CH5 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 602doc 40603 | CH5 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 603doc 40604 | CH5 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 604doc 40605 | CH5 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 605doc 40606 | CH5 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 606doc 40607 | CH5 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 607doc 40608 | CH5 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 616doc 40617 | CH5 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 622doc 40623 | CH5 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 623doc 40624 | CH5 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 624doc 40625 | CH5 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 625doc 40626 | CH5 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 626doc 40627 | CH5 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 627doc 40628 | CH5 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 628doc 40629 | CH5 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 629doc 40630 | CH5 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 630doc 40631 | CH5 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 631doc 40632 | CH5 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 632doc 40633 | CH5 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 633doc 40634 | CH5 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 634doc 40635 | CH5 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 635doc 40636 | CH5 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 636doc 40637 | CH5 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 637doc 40638 | CH5 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 638doc 40639 | CH5 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 639doc 40640 | CH5 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 640doc 40641 | CH5 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 641doc 40642 | CH5 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 700doc 40701 | CH6 mode | UINT16 | Read/write | 0 = Scaling OFF; 1 = Scaling ON; 2 = Square root (SQRT); 3 = Exponent display (DECAD); 4 = Difference (DELT); 5 = Sum (SIGM); 6 = Average (MEAN); 7 = Disable (writing it is an error); 8 = Skip | ||||
| HR | 701doc 40702 | CH6 input type (range code) | 0-34; range code table in manual section 6.5.5. | UINT16 | Read/write | ||||
| HR | 702doc 40703 | CH6 reference channel | Channel used by DELT/SIGM/MEAN; not settable on CH1. | UINT16 | Read/write | ||||
| HR | 703doc 40704 | CH6 measurement range low | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 704doc 40705 | CH6 measurement range high | Range-dependent integer. | INT16 | Read/write | ||||
| HR | 705doc 40706 | CH6 scaling range low | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 706doc 40707 | CH6 scaling range high | -32000..32000; uses the decimal point register. | INT16 | Read/write | ||||
| HR | 707doc 40708 | CH6 decimal point position | 0-4; applies when scaling is ON. | UINT16 | Read/write | ||||
| HR | 716doc 40717 | CH6 digital print | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 722doc 40723 | CH6 alarm 1 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 723doc 40724 | CH6 alarm 1 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 724doc 40725 | CH6 alarm 1 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 725doc 40726 | CH6 alarm 1 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 726doc 40727 | CH6 alarm 1 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 727doc 40728 | CH6 alarm 2 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 728doc 40729 | CH6 alarm 2 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 729doc 40730 | CH6 alarm 2 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 730doc 40731 | CH6 alarm 2 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 731doc 40732 | CH6 alarm 2 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 732doc 40733 | CH6 alarm 3 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 733doc 40734 | CH6 alarm 3 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 734doc 40735 | CH6 alarm 3 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 735doc 40736 | CH6 alarm 3 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 736doc 40737 | CH6 alarm 3 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 737doc 40738 | CH6 alarm 4 action | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 738doc 40739 | CH6 alarm 4 type | UINT16 | Read/write | 0 = H (high); 1 = L (low) | ||||
| HR | 739doc 40740 | CH6 alarm 4 set value | -32000..32000, scaling-dependent decimal point. | INT16 | Read/write | ||||
| HR | 740doc 40741 | CH6 alarm 4 relay output | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 741doc 40742 | CH6 alarm 4 DO number | Multipoint 0-5 (RLY1-6), pen 0-2 (RLY1-3). | UINT16 | Read/write | ||||
| HR | 802doc 40803 | Recording period | Multipoint type only. | UINT16 | Read/write | 0 = 10 s; 1 = 20 s; 2 = 30 s; 3 = 60 s | |||
| HR | 970doc 40971 | Host address | Slave address 1-32. | UINT16 | Read/write | ||||
| HR | 971doc 40972 | Communication speed | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps | ||||
| HR | 972doc 40973 | Data length | Modbus RTU needs 8 bit. | UINT16 | Read/write | 0 = 7 bit; 1 = 8 bit | |||
| HR | 973doc 40974 | Parity | UINT16 | Read/write | 0 = Even; 1 = Odd; 2 = OFF | ||||
| HR | 974doc 40975 | Stop bit | UINT16 | Read/write | 0 = 1 bit; 1 = 2 bit | ||||
| HR | 975doc 40976 | Communication protocol | UINT16 | Read/write | 0 = Original; 1 = Modbus RTU |
Notes on this map
- Measurement floats (30119-30130) are documented high-order word first, so ABCD.
- The holding-register float copies of scaling range and alarm set values (e.g. 40251-40262) are left out: the manual says IEEE but does not state their word order.
- Channel setup blocks repeat every 100 registers: CH1 40201, CH2 40301 ... CH6 40701. Tag, unit and partial-compression items are omitted.
- Parameter writes take effect only after writing AA01H to Save the settings (40104); operation commands act at once.
- Engineering parameters (40901-40970), print text and comment areas are omitted.
- Factory communication defaults are not stated in this manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
What Modbus registers does the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) have?
This map lists 240 registers: 44 input registers, 196 holding registers. 196 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints Modicon numbers (30001, 40101) next to a hex relative address; 30001 and 40001 are relative address 0, so subtract 30001 or 40001 to get the wire address. The manual's function 04 example reads relative address 0032H, which is 30051 (clock year).
What byte order does the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)?
Start with IR 118 CH1 measurement (float) (CH1 measured value (float)); IR 106 CH1 measurement (integer) (CH1 measured value (integer)); IR 112 CH1 decimal point position (CH1 decimal point); IR 100 CH1 channel status (CH1 alarm flags); IR 56 Recording status (Recording status); HR 100 Recording start/stop (Recording start/stop command); HR 103 Save the settings (Save settings command).
How do I enable Modbus control of the Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)?
Needs body firmware 4.00 or later. Set Communication protocol to Modbus RTU and data length to 8 bit in the recorder's communication settings (also exposed at 40973 and 40976).
Where is the official Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+) Modbus documentation?
The source is HR-700 Hybrid Recorder Communication Command Manual (No. HR7CE4), revision 2018-05, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/HR7CE4.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other valves, actuators & sensors register maps
- Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor
All valves, actuators & sensors Modbus register maps →
Source: HR-700 Hybrid Recorder Communication Command Manual · No. HR7CE4 · rev. 2018-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.