Sensor (digital temperature controller) · Modbus register map

Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus register map

Updated 17 November 2026

Short answer

The FC series are PID controllers with seven set value memories and a simple 7-step program mode. On the C (RS-232C) or C5 (RS-485) option they can speak Modbus ASCII, one 16-bit holding register per request. The map covers the seven memory blocks of SV, PID, alarm and output limits, step times, general settings, PV, MV and the status word.

This page lists 160 Modbus registers for the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) — 153 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
FC series digital indicating controller (C/C5 option, Modbus ASCII)
Equipment type
Sensor (digital temperature controller)
Registers
160 (153 writable)
Transport
Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
FCS-23A, FCR-13A, FCR-23A, FCD-13A
Source document
Communication Instruction Manual FC series (C, C5) · No.FC1CE11 · rev. 2006-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)

Integration in brief

Select Modbus ASCII as the protocol on the keypad and give each unit an instrument number; then read PV 0099H, OUT1 MV 009AH and status 009EH one register at a time with function 03, and write SV memory 1 at 0000H with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 153PVINT16Process valueRead
HR 0SV memory 1INT16SV memory 1Read/write
HR 105SV memory number / step numberINT16Active SV memory / stepRead/write
HR 154OUT1 MVINT16OUT1 manipulated valueRead
HR 158Status flagBITMAP16Output, alarm and over/underscale statusRead
HR 120Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C (RS-232C) or C5 (RS-485) option on a Modbus-capable model. Set instrument number, communication speed and Communication protocol = Modbus ASCII on the keypad; none of these can be changed over the bus.

Byte order & addressing

Network setup

Watch out for

Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

160 of 160 shown
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000HSV memory 1Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR1doc 0001HSV memory 2Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR2doc 0002HSV memory 3Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR3doc 0003HSV memory 4Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR4doc 0004HSV memory 5Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR5doc 0005HSV memory 6Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR6doc 0006HSV memory 7Set value (step SV in program control). Raw integer; apply the decimal point place (0078H).INT16Read/write
HR7doc 0007HOUT1 proportional band memory 1Sent without its decimal point.INT16Read/write
HR8doc 0008HOUT1 proportional band memory 2Sent without its decimal point.INT16Read/write
HR9doc 0009HOUT1 proportional band memory 3Sent without its decimal point.INT16Read/write
HR10doc 000AHOUT1 proportional band memory 4Sent without its decimal point.INT16Read/write
HR11doc 000BHOUT1 proportional band memory 5Sent without its decimal point.INT16Read/write
HR12doc 000CHOUT1 proportional band memory 6Sent without its decimal point.INT16Read/write
HR13doc 000DHOUT1 proportional band memory 7Sent without its decimal point.INT16Read/write
HR14doc 000EHOUT2 proportional band memory 1FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR15doc 000FHOUT2 proportional band memory 2FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR16doc 0010HOUT2 proportional band memory 3FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR17doc 0011HOUT2 proportional band memory 4FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR18doc 0012HOUT2 proportional band memory 5FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR19doc 0013HOUT2 proportional band memory 6FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR20doc 0014HOUT2 proportional band memory 7FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR21doc 0015HIntegral time memory 1INT16Read/write
HR22doc 0016HIntegral time memory 2INT16Read/write
HR23doc 0017HIntegral time memory 3INT16Read/write
HR24doc 0018HIntegral time memory 4INT16Read/write
HR25doc 0019HIntegral time memory 5INT16Read/write
HR26doc 001AHIntegral time memory 6INT16Read/write
HR27doc 001BHIntegral time memory 7INT16Read/write
HR28doc 001CHDerivative time memory 1INT16Read/write
HR29doc 001DHDerivative time memory 2INT16Read/write
HR30doc 001EHDerivative time memory 3INT16Read/write
HR31doc 001FHDerivative time memory 4INT16Read/write
HR32doc 0020HDerivative time memory 5INT16Read/write
HR33doc 0021HDerivative time memory 6INT16Read/write
HR34doc 0022HDerivative time memory 7INT16Read/write
HR35doc 0023HA1 value memory 1Raw integer; apply the decimal point place (0078H).INT16Read/write
HR36doc 0024HA1 value memory 2Raw integer; apply the decimal point place (0078H).INT16Read/write
HR37doc 0025HA1 value memory 3Raw integer; apply the decimal point place (0078H).INT16Read/write
HR38doc 0026HA1 value memory 4Raw integer; apply the decimal point place (0078H).INT16Read/write
HR39doc 0027HA1 value memory 5Raw integer; apply the decimal point place (0078H).INT16Read/write
HR40doc 0028HA1 value memory 6Raw integer; apply the decimal point place (0078H).INT16Read/write
HR41doc 0029HA1 value memory 7Raw integer; apply the decimal point place (0078H).INT16Read/write
HR42doc 002AHA2 value memory 1Raw integer; apply the decimal point place (0078H).INT16Read/write
HR43doc 002BHA2 value memory 2Raw integer; apply the decimal point place (0078H).INT16Read/write
HR44doc 002CHA2 value memory 3Raw integer; apply the decimal point place (0078H).INT16Read/write
HR45doc 002DHA2 value memory 4Raw integer; apply the decimal point place (0078H).INT16Read/write
HR46doc 002EHA2 value memory 5Raw integer; apply the decimal point place (0078H).INT16Read/write
HR47doc 002FHA2 value memory 6Raw integer; apply the decimal point place (0078H).INT16Read/write
HR48doc 0030HA2 value memory 7Raw integer; apply the decimal point place (0078H).INT16Read/write
HR49doc 0031HA3 value memory 1FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR50doc 0032HA3 value memory 2FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR51doc 0033HA3 value memory 3FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR52doc 0034HA3 value memory 4FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR53doc 0035HA3 value memory 5FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR54doc 0036HA3 value memory 6FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR55doc 0037HA3 value memory 7FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR56doc 0038HA4 value memory 1FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR57doc 0039HA4 value memory 2FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR58doc 003AHA4 value memory 3FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR59doc 003BHA4 value memory 4FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR60doc 003CHA4 value memory 5FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR61doc 003DHA4 value memory 6FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR62doc 003EHA4 value memory 7FCD-13A only. Raw integer; apply the decimal point place (0078H).INT16Read/write
HR63doc 003FHOverlap/dead band memory 1FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR64doc 0040HOverlap/dead band memory 2FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR65doc 0041HOverlap/dead band memory 3FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR66doc 0042HOverlap/dead band memory 4FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR67doc 0043HOverlap/dead band memory 5FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR68doc 0044HOverlap/dead band memory 6FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR69doc 0045HOverlap/dead band memory 7FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR70doc 0046HOUT1 high limit memory 1Sent without its decimal point.INT16Read/write
HR71doc 0047HOUT1 high limit memory 2Sent without its decimal point.INT16Read/write
HR72doc 0048HOUT1 high limit memory 3Sent without its decimal point.INT16Read/write
HR73doc 0049HOUT1 high limit memory 4Sent without its decimal point.INT16Read/write
HR74doc 004AHOUT1 high limit memory 5Sent without its decimal point.INT16Read/write
HR75doc 004BHOUT1 high limit memory 6Sent without its decimal point.INT16Read/write
HR76doc 004CHOUT1 high limit memory 7Sent without its decimal point.INT16Read/write
HR77doc 004DHOUT1 low limit memory 1Sent without its decimal point.INT16Read/write
HR78doc 004EHOUT1 low limit memory 2Sent without its decimal point.INT16Read/write
HR79doc 004FHOUT1 low limit memory 3Sent without its decimal point.INT16Read/write
HR80doc 0050HOUT1 low limit memory 4Sent without its decimal point.INT16Read/write
HR81doc 0051HOUT1 low limit memory 5Sent without its decimal point.INT16Read/write
HR82doc 0052HOUT1 low limit memory 6Sent without its decimal point.INT16Read/write
HR83doc 0053HOUT1 low limit memory 7Sent without its decimal point.INT16Read/write
HR84doc 0054HOUT2 high limit memory 1FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR85doc 0055HOUT2 high limit memory 2FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR86doc 0056HOUT2 high limit memory 3FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR87doc 0057HOUT2 high limit memory 4FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR88doc 0058HOUT2 high limit memory 5FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR89doc 0059HOUT2 high limit memory 6FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR90doc 005AHOUT2 high limit memory 7FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR91doc 005BHOUT2 low limit memory 1FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR92doc 005CHOUT2 low limit memory 2FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR93doc 005DHOUT2 low limit memory 3FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR94doc 005EHOUT2 low limit memory 4FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR95doc 005FHOUT2 low limit memory 5FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR96doc 0060HOUT2 low limit memory 6FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR97doc 0061HOUT2 low limit memory 7FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR98doc 0062HStep 1 timeProgram step duration in minutes.INT16minRead/write
HR99doc 0063HStep 2 timeProgram step duration in minutes.INT16minRead/write
HR100doc 0064HStep 3 timeProgram step duration in minutes.INT16minRead/write
HR101doc 0065HStep 4 timeProgram step duration in minutes.INT16minRead/write
HR102doc 0066HStep 5 timeProgram step duration in minutes.INT16minRead/write
HR103doc 0067HStep 6 timeProgram step duration in minutes.INT16minRead/write
HR104doc 0068HStep 7 timeProgram step duration in minutes.INT16minRead/write
HR105doc 0069HSV memory number / step numberSelected set value memory, or step in program control.INT16Read/write
HR106doc 006AHAT Perform/CancelINT16Read/write0 = Cancel; 1 = Perform
HR107doc 006BHOUT1 proportional cycleINT16Read/write
HR108doc 006CHOUT2 proportional cycleFCD-13A, FCR-13A, FCR-23A only.INT16Read/write
HR109doc 006DHManual resetSent without its decimal point.INT16Read/write
HR110doc 006EHHeater burnout alarm valueFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR111doc 006FHLoop break alarm action timeINT16Read/write
HR112doc 0070HLoop break alarm action spanSent without its decimal point.INT16Read/write
HR113doc 0071HSet value lockLock 3: written values are not kept after power off.INT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR114doc 0072HSV high limitRaw integer; apply the decimal point place (0078H).INT16Read/write
HR115doc 0073HSV low limitRaw integer; apply the decimal point place (0078H).INT16Read/write
HR116doc 0074HSensor correction valueSent without its decimal point.INT16Read/write
HR117doc 0075HRemote/LocalFCD-13A, FCR-13A, FCR-23A only.INT16Read/write0 = Local; 1 = Remote
HR118doc 0076HScaling high limitRaw integer; apply the decimal point place (0078H).INT16Read/write
HR119doc 0077HScaling low limitRaw integer; apply the decimal point place (0078H).INT16Read/write
HR120doc 0078HDecimal point placeINT16Read/write0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX
HR121doc 0079HPV filter time constantSent without its decimal point.INT16Read/write
HR122doc 007AHOUT1 ON/OFF hysteresisSent without its decimal point.INT16Read/write
HR123doc 007BHOUT2 action modeFCD-13A, FCR-13A, FCR-23A only.INT16Read/write0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power)
HR124doc 007CHOUT2 ON/OFF hysteresisFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR125doc 007DHA3 typeFCD-13A only. Changing it resets the A3 value to 0.INT16Read/write0 = No alarm; 1 = High limit alarm; 2 = High limit alarm with standby; 3 = Low limit alarm; 4 = Low limit alarm with standby; 5 = H/L limits alarm; 6 = H/L limits alarm with standby; 7 = H/L limit range alarm; 8 = H/L limit range alarm with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby
HR126doc 007EHA4 typeFCD-13A only. Changing it resets the A4 value to 0.INT16Read/write0 = No alarm; 1 = High limit alarm; 2 = High limit alarm with standby; 3 = Low limit alarm; 4 = Low limit alarm with standby; 5 = H/L limits alarm; 6 = H/L limits alarm with standby; 7 = H/L limit range alarm; 8 = H/L limit range alarm with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby
HR127doc 007FHA1 hysteresisSent without its decimal point.INT16Read/write
HR128doc 0080HA2 hysteresisSent without its decimal point.INT16Read/write
HR129doc 0081HA3 hysteresisFCD-13A only. Sent without its decimal point.INT16Read/write
HR130doc 0082HA4 hysteresisFCD-13A only. Sent without its decimal point.INT16Read/write
HR131doc 0083HA1 action delay timerINT16Read/write
HR132doc 0084HA2 action delay timerINT16Read/write
HR133doc 0085HA3 action delay timerFCD-13A only.INT16Read/write
HR134doc 0086HA4 action delay timerFCD-13A only.INT16Read/write
HR135doc 0087HExternal setting input high limitFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR136doc 0088HExternal setting input low limitFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR137doc 0089HTransmission output modeFCD-13A, FCR-13A, FCR-23A only.INT16Read/write0 = PV transmission; 1 = SV transmission; 2 = MV transmission
HR138doc 008AHTransmission output high limitFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR139doc 008BHTransmission output low limitFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read/write
HR140doc 008CHIndication when control output is OFFINT16Read/write0 = OFF indication; 1 = No indication; 2 = PV indication
HR141doc 008DHSV rise rateSent without its decimal point.INT16Read/write
HR142doc 008EHSV fall rateSent without its decimal point.INT16Read/write
HR143doc 008FHFixed value / program controlINT16Read/write0 = Fixed value control; 1 = Program control
HR144doc 0090HControl output OFF functionFixed control: 0 output ON, 1 OFF. Program control: 0 STOP, 1 RUN.INT16Read/write
HR145doc 0091HAuto/Manual controlFCD-13A, FCR-13A, FCR-23A only.INT16Read/write0 = Automatic; 1 = Manual
HR146doc 0092HManual MVFCD-13A, FCR-13A, FCR-23A only. Writable only in manual mode; range follows the output limits.INT16Read/write
HR147doc 0093HInfrared emissivitySent without its decimal point.INT16Read/write
HR148doc 0094HOutput OFF on excess inputINT16Read/write0 = Prohibited; 1 = Allowed
HR149doc 0095HA1 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR150doc 0096HA2 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR151doc 0097HA3 energized/de-energizedFCD-13A only.INT16Read/write0 = Energized; 1 = De-energized
HR152doc 0098HA4 energized/de-energizedFCD-13A only.INT16Read/write0 = Energized; 1 = De-energized
HR153doc 0099HPVProcess value. Raw integer; apply the decimal point place (0078H).INT16Read
HR154doc 009AHOUT1 MVSent without its decimal point.INT16Read
HR155doc 009BHOUT2 MVFCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point.INT16Read
HR156doc 009CHCurrent SV (program control)Raw integer; apply the decimal point place (0078H).INT16Read
HR157doc 009DHRemaining time (program control)INT16minRead
HR158doc 009EHStatus flagBITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 4 = A3 output on; bit 5 = A4 output on; bit 6 = Heater burnout alarm output; bit 7 = Loop break alarm output; bit 8 = Overscale; bit 9 = Underscale
HR159doc 009FHSelected SV memory / running stepINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)

What Modbus registers does the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) have?

This map lists 160 registers: 160 holding registers. 153 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as hex (0000H) and go into the request unchanged; the manual's example frames read SV memory 1 at address 0000H and PV at 0099H.

What are the minimum Modbus registers to integrate the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)?

Start with HR 153 PV (Process value); HR 0 SV memory 1 (SV memory 1); HR 105 SV memory number / step number (Active SV memory / step); HR 154 OUT1 MV (OUT1 manipulated value); HR 158 Status flag (Output, alarm and over/underscale status); HR 120 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)?

Requires the C (RS-232C) or C5 (RS-485) option on a Modbus-capable model. Set instrument number, communication speed and Communication protocol = Modbus ASCII on the keypad; none of these can be changed over the bus.

Where is the official Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus documentation?

The source is Communication Instruction Manual FC series (C, C5) (No.FC1CE11), revision 2006-12, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/FC1CE11.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual FC series (C, C5) · No.FC1CE11 · rev. 2006-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.