Sensor (digital temperature controller) · Modbus register map
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus register map
Updated 17 November 2026
The FC series are PID controllers with seven set value memories and a simple 7-step program mode. On the C (RS-232C) or C5 (RS-485) option they can speak Modbus ASCII, one 16-bit holding register per request. The map covers the seven memory blocks of SV, PID, alarm and output limits, step times, general settings, PV, MV and the status word.
This page lists 160 Modbus registers for the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) — 153 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- FC series digital indicating controller (C/C5 option, Modbus ASCII)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 160 (153 writable)
- Transport
- Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- FCS-23A, FCR-13A, FCR-23A, FCD-13A
Integration notes: Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Select Modbus ASCII as the protocol on the keypad and give each unit an instrument number; then read PV 0099H, OUT1 MV 009AH and status 009EH one register at a time with function 03, and write SV memory 1 at 0000H with function 06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 153 | PV | INT16 | Process value | Read |
| HR 0 | SV memory 1 | INT16 | SV memory 1 | Read/write |
| HR 105 | SV memory number / step number | INT16 | Active SV memory / step | Read/write |
| HR 154 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 158 | Status flag | BITMAP16 | Output, alarm and over/underscale status | Read |
| HR 120 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C (RS-232C) or C5 (RS-485) option on a Modbus-capable model. Set instrument number, communication speed and Communication protocol = Modbus ASCII on the keypad; none of these can be changed over the bus.
Byte order & addressing
- Modbus ASCII with 7 data bits, even parity, 1 stop bit; RTU masters will not talk to it.
- Only one register per request.
Network setup
- Factory defaults: instrument number 0, 9600 bps, Shinko protocol.
- Speeds 2400, 4800, 9600 or 19200 bps, selected on the keypad.
- On RS-485 fit a terminator at the far end of the line.
Watch out for
- Send A3/A4 type before the alarm value: changing the type resets the value to 0.
- AT Perform/Cancel returns an exception during PI or ON/OFF action, or if it repeats the current state.
- EEPROM write life is about one million writes; avoid cyclic writes.
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000H | SV memory 1 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 1doc 0001H | SV memory 2 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 2doc 0002H | SV memory 3 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 3doc 0003H | SV memory 4 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 4doc 0004H | SV memory 5 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 5doc 0005H | SV memory 6 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 6doc 0006H | SV memory 7 | Set value (step SV in program control). Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 7doc 0007H | OUT1 proportional band memory 1 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 8doc 0008H | OUT1 proportional band memory 2 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 9doc 0009H | OUT1 proportional band memory 3 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 10doc 000AH | OUT1 proportional band memory 4 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 11doc 000BH | OUT1 proportional band memory 5 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 12doc 000CH | OUT1 proportional band memory 6 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 13doc 000DH | OUT1 proportional band memory 7 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 14doc 000EH | OUT2 proportional band memory 1 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 15doc 000FH | OUT2 proportional band memory 2 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 16doc 0010H | OUT2 proportional band memory 3 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 17doc 0011H | OUT2 proportional band memory 4 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 18doc 0012H | OUT2 proportional band memory 5 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 19doc 0013H | OUT2 proportional band memory 6 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 20doc 0014H | OUT2 proportional band memory 7 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 21doc 0015H | Integral time memory 1 | INT16 | Read/write | |||||
| HR | 22doc 0016H | Integral time memory 2 | INT16 | Read/write | |||||
| HR | 23doc 0017H | Integral time memory 3 | INT16 | Read/write | |||||
| HR | 24doc 0018H | Integral time memory 4 | INT16 | Read/write | |||||
| HR | 25doc 0019H | Integral time memory 5 | INT16 | Read/write | |||||
| HR | 26doc 001AH | Integral time memory 6 | INT16 | Read/write | |||||
| HR | 27doc 001BH | Integral time memory 7 | INT16 | Read/write | |||||
| HR | 28doc 001CH | Derivative time memory 1 | INT16 | Read/write | |||||
| HR | 29doc 001DH | Derivative time memory 2 | INT16 | Read/write | |||||
| HR | 30doc 001EH | Derivative time memory 3 | INT16 | Read/write | |||||
| HR | 31doc 001FH | Derivative time memory 4 | INT16 | Read/write | |||||
| HR | 32doc 0020H | Derivative time memory 5 | INT16 | Read/write | |||||
| HR | 33doc 0021H | Derivative time memory 6 | INT16 | Read/write | |||||
| HR | 34doc 0022H | Derivative time memory 7 | INT16 | Read/write | |||||
| HR | 35doc 0023H | A1 value memory 1 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 36doc 0024H | A1 value memory 2 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 37doc 0025H | A1 value memory 3 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 38doc 0026H | A1 value memory 4 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 39doc 0027H | A1 value memory 5 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 40doc 0028H | A1 value memory 6 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 41doc 0029H | A1 value memory 7 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 42doc 002AH | A2 value memory 1 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 43doc 002BH | A2 value memory 2 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 44doc 002CH | A2 value memory 3 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 45doc 002DH | A2 value memory 4 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 46doc 002EH | A2 value memory 5 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 47doc 002FH | A2 value memory 6 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 48doc 0030H | A2 value memory 7 | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 49doc 0031H | A3 value memory 1 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 50doc 0032H | A3 value memory 2 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 51doc 0033H | A3 value memory 3 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 52doc 0034H | A3 value memory 4 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 53doc 0035H | A3 value memory 5 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 54doc 0036H | A3 value memory 6 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 55doc 0037H | A3 value memory 7 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 56doc 0038H | A4 value memory 1 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 57doc 0039H | A4 value memory 2 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 58doc 003AH | A4 value memory 3 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 59doc 003BH | A4 value memory 4 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 60doc 003CH | A4 value memory 5 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 61doc 003DH | A4 value memory 6 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 62doc 003EH | A4 value memory 7 | FCD-13A only. Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 63doc 003FH | Overlap/dead band memory 1 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 64doc 0040H | Overlap/dead band memory 2 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 65doc 0041H | Overlap/dead band memory 3 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 66doc 0042H | Overlap/dead band memory 4 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 67doc 0043H | Overlap/dead band memory 5 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 68doc 0044H | Overlap/dead band memory 6 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 69doc 0045H | Overlap/dead band memory 7 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 70doc 0046H | OUT1 high limit memory 1 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 71doc 0047H | OUT1 high limit memory 2 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 72doc 0048H | OUT1 high limit memory 3 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 73doc 0049H | OUT1 high limit memory 4 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 74doc 004AH | OUT1 high limit memory 5 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 75doc 004BH | OUT1 high limit memory 6 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 76doc 004CH | OUT1 high limit memory 7 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 77doc 004DH | OUT1 low limit memory 1 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 78doc 004EH | OUT1 low limit memory 2 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 79doc 004FH | OUT1 low limit memory 3 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 80doc 0050H | OUT1 low limit memory 4 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 81doc 0051H | OUT1 low limit memory 5 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 82doc 0052H | OUT1 low limit memory 6 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 83doc 0053H | OUT1 low limit memory 7 | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 84doc 0054H | OUT2 high limit memory 1 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 85doc 0055H | OUT2 high limit memory 2 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 86doc 0056H | OUT2 high limit memory 3 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 87doc 0057H | OUT2 high limit memory 4 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 88doc 0058H | OUT2 high limit memory 5 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 89doc 0059H | OUT2 high limit memory 6 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 90doc 005AH | OUT2 high limit memory 7 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 91doc 005BH | OUT2 low limit memory 1 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 92doc 005CH | OUT2 low limit memory 2 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 93doc 005DH | OUT2 low limit memory 3 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 94doc 005EH | OUT2 low limit memory 4 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 95doc 005FH | OUT2 low limit memory 5 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 96doc 0060H | OUT2 low limit memory 6 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 97doc 0061H | OUT2 low limit memory 7 | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 98doc 0062H | Step 1 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 99doc 0063H | Step 2 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 100doc 0064H | Step 3 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 101doc 0065H | Step 4 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 102doc 0066H | Step 5 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 103doc 0067H | Step 6 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 104doc 0068H | Step 7 time | Program step duration in minutes. | INT16 | min | Read/write | |||
| HR | 105doc 0069H | SV memory number / step number | Selected set value memory, or step in program control. | INT16 | Read/write | ||||
| HR | 106doc 006AH | AT Perform/Cancel | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 107doc 006BH | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 108doc 006CH | OUT2 proportional cycle | FCD-13A, FCR-13A, FCR-23A only. | INT16 | Read/write | ||||
| HR | 109doc 006DH | Manual reset | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 110doc 006EH | Heater burnout alarm value | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 111doc 006FH | Loop break alarm action time | INT16 | Read/write | |||||
| HR | 112doc 0070H | Loop break alarm action span | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 113doc 0071H | Set value lock | Lock 3: written values are not kept after power off. | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | |||
| HR | 114doc 0072H | SV high limit | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 115doc 0073H | SV low limit | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 116doc 0074H | Sensor correction value | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 117doc 0075H | Remote/Local | FCD-13A, FCR-13A, FCR-23A only. | INT16 | Read/write | 0 = Local; 1 = Remote | |||
| HR | 118doc 0076H | Scaling high limit | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 119doc 0077H | Scaling low limit | Raw integer; apply the decimal point place (0078H). | INT16 | Read/write | ||||
| HR | 120doc 0078H | Decimal point place | INT16 | Read/write | 0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX | ||||
| HR | 121doc 0079H | PV filter time constant | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 122doc 007AH | OUT1 ON/OFF hysteresis | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 123doc 007BH | OUT2 action mode | FCD-13A, FCR-13A, FCR-23A only. | INT16 | Read/write | 0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power) | |||
| HR | 124doc 007CH | OUT2 ON/OFF hysteresis | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 125doc 007DH | A3 type | FCD-13A only. Changing it resets the A3 value to 0. | INT16 | Read/write | 0 = No alarm; 1 = High limit alarm; 2 = High limit alarm with standby; 3 = Low limit alarm; 4 = Low limit alarm with standby; 5 = H/L limits alarm; 6 = H/L limits alarm with standby; 7 = H/L limit range alarm; 8 = H/L limit range alarm with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby | |||
| HR | 126doc 007EH | A4 type | FCD-13A only. Changing it resets the A4 value to 0. | INT16 | Read/write | 0 = No alarm; 1 = High limit alarm; 2 = High limit alarm with standby; 3 = Low limit alarm; 4 = Low limit alarm with standby; 5 = H/L limits alarm; 6 = H/L limits alarm with standby; 7 = H/L limit range alarm; 8 = H/L limit range alarm with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby | |||
| HR | 127doc 007FH | A1 hysteresis | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 128doc 0080H | A2 hysteresis | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 129doc 0081H | A3 hysteresis | FCD-13A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 130doc 0082H | A4 hysteresis | FCD-13A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 131doc 0083H | A1 action delay timer | INT16 | Read/write | |||||
| HR | 132doc 0084H | A2 action delay timer | INT16 | Read/write | |||||
| HR | 133doc 0085H | A3 action delay timer | FCD-13A only. | INT16 | Read/write | ||||
| HR | 134doc 0086H | A4 action delay timer | FCD-13A only. | INT16 | Read/write | ||||
| HR | 135doc 0087H | External setting input high limit | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 136doc 0088H | External setting input low limit | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 137doc 0089H | Transmission output mode | FCD-13A, FCR-13A, FCR-23A only. | INT16 | Read/write | 0 = PV transmission; 1 = SV transmission; 2 = MV transmission | |||
| HR | 138doc 008AH | Transmission output high limit | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 139doc 008BH | Transmission output low limit | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 140doc 008CH | Indication when control output is OFF | INT16 | Read/write | 0 = OFF indication; 1 = No indication; 2 = PV indication | ||||
| HR | 141doc 008DH | SV rise rate | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 142doc 008EH | SV fall rate | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 143doc 008FH | Fixed value / program control | INT16 | Read/write | 0 = Fixed value control; 1 = Program control | ||||
| HR | 144doc 0090H | Control output OFF function | Fixed control: 0 output ON, 1 OFF. Program control: 0 STOP, 1 RUN. | INT16 | Read/write | ||||
| HR | 145doc 0091H | Auto/Manual control | FCD-13A, FCR-13A, FCR-23A only. | INT16 | Read/write | 0 = Automatic; 1 = Manual | |||
| HR | 146doc 0092H | Manual MV | FCD-13A, FCR-13A, FCR-23A only. Writable only in manual mode; range follows the output limits. | INT16 | Read/write | ||||
| HR | 147doc 0093H | Infrared emissivity | Sent without its decimal point. | INT16 | Read/write | ||||
| HR | 148doc 0094H | Output OFF on excess input | INT16 | Read/write | 0 = Prohibited; 1 = Allowed | ||||
| HR | 149doc 0095H | A1 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 150doc 0096H | A2 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 151doc 0097H | A3 energized/de-energized | FCD-13A only. | INT16 | Read/write | 0 = Energized; 1 = De-energized | |||
| HR | 152doc 0098H | A4 energized/de-energized | FCD-13A only. | INT16 | Read/write | 0 = Energized; 1 = De-energized | |||
| HR | 153doc 0099H | PV | Process value. Raw integer; apply the decimal point place (0078H). | INT16 | Read | ||||
| HR | 154doc 009AH | OUT1 MV | Sent without its decimal point. | INT16 | Read | ||||
| HR | 155doc 009BH | OUT2 MV | FCD-13A, FCR-13A, FCR-23A only. Sent without its decimal point. | INT16 | Read | ||||
| HR | 156doc 009CH | Current SV (program control) | Raw integer; apply the decimal point place (0078H). | INT16 | Read | ||||
| HR | 157doc 009DH | Remaining time (program control) | INT16 | min | Read | ||||
| HR | 158doc 009EH | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = A1 output on; bit 3 = A2 output on; bit 4 = A3 output on; bit 5 = A4 output on; bit 6 = Heater burnout alarm output; bit 7 = Loop break alarm output; bit 8 = Overscale; bit 9 = Underscale | ||||
| HR | 159doc 009FH | Selected SV memory / running step | INT16 | Read |
Notes on this map
- Modbus ASCII only (no RTU). Function 03 reads exactly one register and function 06 writes one; multi-register reads are not supported.
- All data are 16-bit two's complement. Values with a decimal point are sent as whole numbers without it; PV-type values (PV, SV, alarm values, SV and scaling limits) follow the decimal point place (0078H).
- The Modbus addresses differ from the Shinko-protocol data items for the same setting (PV is 0080H in Shinko protocol but 0099H in Modbus).
- Units of PID times, cycles and MV are not printed in the command table.
- Items marked for certain models still accept writes on other models but do nothing.
- The manual is inconsistent about address 0: the Modbus section says a unit set to 0 answers normally (no broadcast), while the general notes say broadcast commands get no reply.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
What Modbus registers does the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) have?
This map lists 160 registers: 160 holding registers. 153 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as hex (0000H) and go into the request unchanged; the manual's example frames read SV memory 1 at address 0000H and PV at 0099H.
What are the minimum Modbus registers to integrate the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)?
Start with HR 153 PV (Process value); HR 0 SV memory 1 (SV memory 1); HR 105 SV memory number / step number (Active SV memory / step); HR 154 OUT1 MV (OUT1 manipulated value); HR 158 Status flag (Output, alarm and over/underscale status); HR 120 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)?
Requires the C (RS-232C) or C5 (RS-485) option on a Modbus-capable model. Set instrument number, communication speed and Communication protocol = Modbus ASCII on the keypad; none of these can be changed over the bus.
Where is the official Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII) Modbus documentation?
The source is Communication Instruction Manual FC series (C, C5) (No.FC1CE11), revision 2006-12, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/FC1CE11.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual FC series (C, C5) · No.FC1CE11 · rev. 2006-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.