Easy Modbus
  1. Home
  2. Modbus register maps
  3. Vaisala
  4. MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)

Sensor (transformer oil monitor) · Modbus register map

Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The MHT410 is a Vaisala transmitter mounted on a power transformer that measures hydrogen and moisture dissolved in the oil plus oil temperature. Its RS-485 line runs Modbus RTU by default. This map covers H2 averages and rate-of-change values, oil moisture values and temperature in float and integer form, and the device status bits.

This page lists 25 Modbus registers for the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
Equipment type
Sensor (transformer oil monitor)
Registers
25 (0 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
MHT410
Source document
MHT410 User Guide · M211737EN-J · rev. 2023-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)

Integration in brief

Read holding registers 1-28 in one request (CDAB floats) for all H2, moisture and temperature values, and 513 for status and the H2 alarm bit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0H2 1 hour averageFLOAT32 CDABH2 1 h averageRead
HR 2H2 24 hour averageFLOAT32 CDABH2 24 h averageRead
HR 16Oil moisture currentFLOAT32 CDABOil moisture ppmRead
HR 26Oil temperatureFLOAT32 CDABOil temperatureRead
HR 512Device status bitsBITMAP16Device statusRead

Enable Modbus control & writes

The RS-485 line on the screw terminals is in Modbus mode from the factory. Serial settings and the protocol (Modbus, DNP3 or Vaisala Industrial Protocol) are changed with serial commands over the service port.

Byte order & addressing

Network setup

Watch out for

Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

25 of 25 shown
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1H2 1 hour averageHydrogen dissolved in oil.FLOAT32CDABppmvRead
HR2doc 3H2 24 hour averageFLOAT32CDABppmvRead
HR4doc 5H2 daily rate of changeFLOAT32CDABppmvRead
HR6doc 7H2 weekly rate of changeFLOAT32CDABppmvRead
HR8doc 9H2 monthly rate of changeFLOAT32CDABppmvRead
HR14doc 15Oil moisture relative saturationFLOAT32CDAB%RSRead
HR16doc 17Oil moisture currentFLOAT32CDABppmwRead
HR18doc 19Oil moisture 24 h averageFLOAT32CDABppmwRead
HR20doc 21Oil moisture daily rate of changeFLOAT32CDABppmwRead
HR22doc 23Oil moisture weekly rate of changeFLOAT32CDABppmwRead
HR24doc 25Oil moisture monthly rate of changeFLOAT32CDABppmwRead
HR26doc 27Oil temperatureFLOAT32CDAB°CRead
HR256doc 257H2 1 h average (integer)INT16ppmvRead
HR257doc 258H2 24 h average (integer)INT16ppmvRead
HR258doc 259H2 daily ROC (integer)INT16ppmvRead
HR259doc 260H2 weekly ROC (integer)INT16ppmvRead
HR260doc 261H2 monthly ROC (integer)INT16ppmvRead
HR263doc 264Oil relative saturation (integer)INT16× 0.1%RSRead
HR264doc 265Oil moisture current (integer)INT16× 0.1ppmwRead
HR265doc 266Oil moisture 24 h average (integer)INT16× 0.1ppmwRead
HR266doc 267Oil moisture daily ROC (integer)INT16× 0.1ppmwRead
HR267doc 268Oil moisture weekly ROC (integer)INT16× 0.1ppmwRead
HR268doc 269Oil moisture monthly ROC (integer)INT16× 0.1ppmwRead
HR269doc 270Oil temperature (integer)INT16× 0.1°CRead
HR512doc 513Device status bits0 = OK; values add up.BITMAP16Readbit 0 = Critical error (maintenance needed); bit 1 = Error (may recover); bit 2 = RH measurement error; bit 3 = T measurement error; bit 4 = H2 measurement error; bit 5 = Other error; bit 6 = H2 alarm level exceeded

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)

What Modbus registers does the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) have?

This map lists 25 registers: 25 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)?

Start with HR 0 H2 1 hour average (H2 1 h average); HR 2 H2 24 hour average (H2 24 h average); HR 16 Oil moisture current (Oil moisture ppm); HR 26 Oil temperature (Oil temperature); HR 512 Device status bits (Device status).

How do I enable Modbus control of the Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)?

The RS-485 line on the screw terminals is in Modbus mode from the factory. Serial settings and the protocol (Modbus, DNP3 or Vaisala Industrial Protocol) are changed with serial commands over the service port.

Where is the official Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU) Modbus documentation?

The source is MHT410 User Guide (M211737EN-J), revision 2023-11, published free by Vaisala at https://docs.vaisala.com/r/M211737EN-J/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: MHT410 User Guide · M211737EN-J · rev. 2023-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.