Sensor (humidity and temperature probe) · Modbus register map

Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The HMP60 and HMP110 families are small Vaisala HUMICAP humidity and temperature probes. Units ordered with the Modbus option speak Modbus RTU on RS-485. This map covers the humidity and temperature readings and calculated parameters, error and status registers, filtering, serial settings and the test registers.

This page lists 27 Modbus registers for the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
Equipment type
Sensor (humidity and temperature probe)
Registers
27 (7 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T
Source document
HMP60 and HMP110 Series User Guide · M211060EN-N · rev. 2025-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)

Integration in brief

Read holding registers 1-4 for RH and temperature as CDAB floats; add 9-10 for dew point. Check register 513 for errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Relative humidityFLOAT32 CDABRelative humidityRead
HR 2TemperatureFLOAT32 CDABTemperatureRead
HR 8Dew/frost point temperatureFLOAT32 CDABDew/frost pointRead
HR 512Error statusUINT16Error statusRead
HR 515Error codeINT32 CDABError codeRead

Enable Modbus control & writes

Order the probe with the Modbus option, or connect through the service port and set the start-up mode with the smode modbus command, then reset or power cycle.

Byte order & addressing

Network setup

Watch out for

Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Relative humidityFLOAT32CDAB%RHRead
HR2doc 3TemperatureFLOAT32CDAB°CRead
HR8doc 9Dew/frost point temperatureFLOAT32CDAB°CRead
HR14doc 15Absolute humidityFLOAT32CDABg/m3Read
HR16doc 17Mixing ratioFLOAT32CDABg/kgRead
HR18doc 19Wet-bulb temperatureFLOAT32CDAB°CRead
HR26doc 27EnthalpyFLOAT32CDABkJ/kgRead
HR256doc 257Relative humidity (integer)INT16× 0.1%RHRead
HR257doc 258Temperature (integer)INT16× 0.1°CRead
HR260doc 261Dew/frost point (integer)INT16× 0.1°CRead
HR263doc 264Absolute humidity (integer)INT16× 0.1g/m3Read
HR264doc 265Mixing ratio (integer)INT16× 0.1g/kgRead
HR265doc 266Wet-bulb temperature (integer)INT16× 0.1°CRead
HR269doc 270Enthalpy (integer)INT16× 0.1kJ/kgRead
HR512doc 513Error statusUINT16Read0 = One or more errors active; 1 = No errors
HR515doc 516Error codeSum of active error codes.INT32CDABReadbit 0 = Temperature measurement error; bit 1 = Humidity measurement error; bit 2 = Humidity sensor failure; bit 3 = Capacitance reference error; bit 4 = Ambient temperature out of range; bit 5 = Firmware checksum mismatch; bit 6 = Device settings corrupted; bit 7 = Additional configuration settings corrupted; bit 8 = Sensor coefficients corrupted; bit 9 = Main configuration settings corrupted; bit 11 = Supply voltage out of range; bit 13 = Non-volatile memory read/write failure; bit 14 = Calibration certificate checksum mismatch
HR517doc 518Security hashChanges whenever settings or adjustments change.INT32CDABRead
HR784doc 785Measurement filtering factor0.001 = maximum filtering, 1.000 = none.FLOAT32CDABRead/write
HR1536doc 1537Modbus address1-247.INT16Read/write
HR1537doc 1538Bit rateTakes effect after restart.UINT16Read/write5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600
HR1538doc 1539Parity, data, stop bitsTakes effect after restart.UINT16Read/write0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2
HR1539doc 1540Response delay0-1020 ms.INT16msRead/write
HR1540doc 1541ProtocolUINT16Read/write6 = Modbus RTU
HR1541doc 1542Restart deviceWrite 1 to restart.INT16Write
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 7940Text string testReads the text "-123.45".STRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)

What Modbus registers does the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) have?

This map lists 27 registers: 27 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)?

Start with HR 0 Relative humidity (Relative humidity); HR 2 Temperature (Temperature); HR 8 Dew/frost point temperature (Dew/frost point); HR 512 Error status (Error status); HR 515 Error code (Error code).

How do I enable Modbus control of the Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)?

Order the probe with the Modbus option, or connect through the service port and set the start-up mode with the smode modbus command, then reset or power cycle.

Where is the official Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU) Modbus documentation?

The source is HMP60 and HMP110 Series User Guide (M211060EN-N), revision 2025-02, published free by Vaisala at https://docs.vaisala.com/r/M211060EN-N/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: HMP60 and HMP110 Series User Guide · M211060EN-N · rev. 2025-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.