- SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
Sensor (particulate matter) · Modbus register map
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) Modbus register map
Updated 17 November 2026
The SEN0662 is a maker-grade particulate sensor board built on the Bosch BMV080. With its DIP switch on the UART side it acts as a Modbus RTU slave. Input registers give PM1.0, PM2.5 and PM10 as big-endian floats plus status; holding registers set the address, serial format and measurement mode and start or stop measurement.
This page lists 26 Modbus registers for the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DFRobot’s own free documentation (linked below) and checked against it.
- Manufacturer
- DFRobot
- Model
- SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
- Equipment type
- Sensor (particulate matter)
- Registers
- 26 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 87
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V1.0.0 (0x1000), register map version 0x0004
- Also known as
- SEN0662, Gravity BMV080, BMV080 PM2.5 sensor, DFRobot BMV080
Integration notes: DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
At 9600 8N1, address 0x57: write 0x0001 to holding register 0x0003 to start measuring, then read six input registers from 0x0006 with function 04 for PM1.0, PM2.5 and PM10 as big-endian floats in ug/m3.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3 | Operation Command | UINT16 | Start measurement command | Write |
| IR 6 | PM1.0 | FLOAT32 ABCD | PM1.0 | Read |
| IR 8 | PM2.5 | FLOAT32 ABCD | PM2.5 | Read |
| IR 10 | PM10 | FLOAT32 ABCD | PM10 | Read |
| IR 14 | Status Flags | BITMAP16 | Status flags | Read |
| IR 4 | Operating Status | UINT16 | Operating status | Read |
Enable Modbus control & writes
Set the module's DIP switch to the UART side; Modbus RTU is then active at the stored address and baud rate.
Byte order & addressing
- Measurement must be started after every power cycle.
- Baud and parity changes take effect after a reboot.
- Changing the algorithm restarts measurement; blockage and vibration settings are re-applied when changed. After changing the measurement mode, send a start command.
Network setup
- Defaults: 9600 baud, 8 data bits, no parity, 1 stop bit, address 0x57.
- The wiki wiring example connects the board R/T pins to a UART adapter (RainbowLink V2).
Watch out for
- If a PM value reads 0 or NaN, check bit 9 of status flags (0x000E).
- Full-scale PM range is 1000 ug/m3; bit 1 of status flags flags PM2.5 out of range.
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 0x0000 | Product ID (PIDR) | Reads 0x0296 for this module. | UINT16 | Read | ||||
| IR | 1doc 0x0001 | Vendor ID (VIDR) | Reads 0x3343 (DFRobot). | UINT16 | Read | ||||
| IR | 2doc 0x0002 | Firmware Version | 0x1000 = V1.0.0. | UINT16 | Read | ||||
| IR | 3doc 0x0003 | Register Map Version | Default 0x0004. | UINT16 | Read | ||||
| IR | 4doc 0x0004 | Operating Status | UINT16 | Read | 0 = Booting; 1 = Ready, waiting for measurement; 2 = Continuous measurement running; 3 = Duty-cycle measurement running; 4 = Stopped; 5 = Error | ||||
| IR | 5doc 0x0005 | Last Status Code | Result of the last BMV080 SDK call; 0 = success. | UINT16 | Read | ||||
| IR | 6doc 0x0006 | PM1.0 | Mass concentration, IEEE 754 float, high word first. | FLOAT32 | ABCD | µg/m³ | Read | ||
| IR | 8doc 0x0008 | PM2.5 | Mass concentration, IEEE 754 float, high word first. | FLOAT32 | ABCD | µg/m³ | Read | ||
| IR | 10doc 0x000A | PM10 | Mass concentration, IEEE 754 float, high word first. | FLOAT32 | ABCD | µg/m³ | Read | ||
| IR | 12doc 0x000C | Operating Duration | Float, high word first. | FLOAT32 | ABCD | s | Read | ||
| IR | 14doc 0x000E | Status Flags | Status bits; bits 10-15 reserved. | BITMAP16 | Read | bit 0 = Sensor blockage; bit 1 = PM2.5 out of range; bit 2 = New PM data ready (cleared once data, flags and counter are read); bit 3 = Sensor initialisation complete; bit 4 = Measurement in progress; bit 5 = Parameter change pending; bit 6 = Parameters validated; bit 7 = Parameters being applied; bit 8 = Reserved (always 0 with float map); bit 9 = A float input was NaN/Inf and was written as 0 | |||
| IR | 15doc 0x000F | Sample Counter | Increments per sample; wraps after 65535. | UINT16 | Read | ||||
| IR | 16doc 0x0010 | SDK Major Version | UINT16 | Read | |||||
| IR | 17doc 0x0011 | SDK Minor Version | UINT16 | Read | |||||
| IR | 18doc 0x0012 | SDK Patch Version | UINT16 | Read | |||||
| IR | 19doc 0x0013 | Sensor Unique ID | 12 ASCII characters across 6 registers, high byte first. | STRING[12] | Read | ||||
| HR | 0doc 0x0000 | RTU Slave Address | 1-247, default 0x57; stored in non-volatile memory. | UINT16 | Read/write | ||||
| HR | 1doc 0x0001 | Baud Rate | Stored; applies after reboot. | UINT16 | Read/write | 1 = 2400; 2 = 4800; 3 = 9600; 4 = 14400; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200 | |||
| HR | 2doc 0x0002 | Parity & Stop Bit Configuration | High byte parity: 0 none, 1 even, 2 odd. Low byte stop bits: 1=1, 2=1.5, 3=2. | UINT16 | Read/write | ||||
| HR | 3doc 0x0003 | Operation Command | Reads back 0. Not stored. | UINT16 | Write | 1 = Start measurement; 2 = Stop measurement; 3 = Restore default configuration | |||
| HR | 4doc 0x0004 | Measurement Mode | Send a start command after changing. | UINT16 | Read/write | 0 = Continuous; 1 = Duty cycle | |||
| HR | 5doc 0x0005 | Measurement Algorithm | Duty-cycle mode forces Fast Response. | UINT16 | Read/write | 1 = Fast Response; 2 = Balanced; 3 = High Precision | |||
| HR | 6doc 0x0006 | Blockage Detection Switch | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 7doc 0x0007 | Vibration Filter Switch | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 8doc 0x0008 | Integration Time | Float, high word first; default 10.0. | FLOAT32 | ABCD | Read/write | |||
| HR | 10doc 0x000A | Duty-Cycle Period | Integration time plus sleep time; default 30. | UINT16 | s | Read/write |
Notes on this map
- Word order: the wiki says registers are big-endian and the high word comes first, and its example response 40 E0 00 00 decodes to 7.0 ug/m3, so floats are ABCD.
- The default slave address is 0x57 (decimal 87). The board's I2C address pins do not affect it.
- The sensor does not measure after power-up: write 1 to holding register 0x0003 after every power cycle before reading PM values.
- The Integration Time float has no unit printed in the table; it is listed without a unit.
- The wiki also documents a broadcast read of holding register 0x0000 (address scan) that only works with a single device on the bus; it is a vendor extension, not standard Modbus.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
What Modbus registers does the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) have?
This map lists 26 registers: 16 input registers, 10 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex protocol addresses from 0x0000 and sent unchanged; the wiki's example reads PM1.0 with start address 0x0006 on function 04.
What byte order does the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)?
Start with HR 3 Operation Command (Start measurement command); IR 6 PM1.0 (PM1.0); IR 8 PM2.5 (PM2.5); IR 10 PM10 (PM10); IR 14 Status Flags (Status flags); IR 4 Operating Status (Operating status).
How do I enable Modbus control of the DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)?
Set the module's DIP switch to the UART side; Modbus RTU is then active at the stored address and baud rate.
Where is the official DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU) Modbus documentation?
The source is Gravity: BMV080 PM2.5 Air Quality Sensor - Modbus Register Definitions (SEN0662 wiki), published free by DFRobot at https://wiki.dfrobot.com/sen0662/docs/25056.
Other valves, actuators & sensors register maps
- Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT - Sensor (CO2, humidity, temperature module)
Sensirion SCD30 CO2, humidity and temperature sensor module
Sensirion SCD30 sensor module with the SEL pin pulled high at power-up (Modbus mode), per interface description version 1.0.
Also known as: SCD30 - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
All valves, actuators & sensors Modbus register maps →
Source: Gravity: BMV080 PM2.5 Air Quality Sensor - Modbus Register Definitions (SEN0662 wiki). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.