Sensor (CO2, humidity, temperature module) · Modbus register map

Sensirion SCD30 CO2, humidity and temperature sensor module Modbus register map

Updated 17 November 2026

Short answer

The SCD30 is an NDIR CO2 module with on-board humidity and temperature sensing. With the SEL pin tied to VDD it speaks Modbus RTU (UART level) at a fixed address and baud rate. Measurements are big-endian IEEE-754 floats; configuration commands are single 16-bit register writes.

This page lists 13 Modbus registers for the Sensirion SCD30 CO2, humidity and temperature sensor module — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sensirion’s own free documentation (linked below) and checked against it.

Manufacturer
Sensirion
Model
SCD30 CO2, humidity and temperature sensor module
Equipment type
Sensor (CO2, humidity, temperature module)
Registers
13 (8 writable)
Transport
Modbus RTU
Default unit ID
97
Default serial
19200 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
SCD30
Source document
Interface Description Sensirion SCD30 Sensor Module · Version 1.0 - D1 · rev. 2020-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Sensirion SCD30 CO2, humidity and temperature sensor module

Integration in brief

Write 0 (or the ambient pressure in mbar) to 0x0036 once to start measuring; the setting survives power cycles. Then poll 0x0027 for data ready and read six registers from 0x0028 for CO2, temperature and humidity.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 54Start continuous measurementUINT16Start continuous measurementWrite
HR 39Data ready statusUINT16Data readyRead
HR 40CO2 concentrationFLOAT32 ABCDCO2Read
HR 42TemperatureFLOAT32 ABCDTemperatureRead
HR 44Relative humidityFLOAT32 ABCDHumidityRead

Enable Modbus control & writes

Pull the SEL pin to VDD during power-up to select Modbus instead of I2C.

Byte order & addressing

Network setup

Watch out for

Sensirion SCD30 CO2, humidity and temperature sensor module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

13 of 13 shown
Sensirion SCD30 CO2, humidity and temperature sensor module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR32doc 0x0020Firmware versionHigh byte = major, low byte = minor.UINT16Read
HR37doc 0x0025Measurement intervalContinuous measurement interval, 2 to 1800 s (default 2 s).UINT16sRead/write
HR39doc 0x0027Data ready status1 when a new measurement can be read.UINT16Read0 = No new data; 1 = Data ready
HR40doc 0x0028-0x0029CO2 concentrationFLOAT32ABCDppmRead
HR42doc 0x002A-0x002BTemperatureFLOAT32ABCD°CRead
HR44doc 0x002C-0x002DRelative humidityFLOAT32ABCD%Read
HR52doc 0x0034Soft resetWrite 1 to restart the sensor.UINT16Write
HR54doc 0x0036Start continuous measurementWrite ambient pressure 700-1400 mbar, or 0 to start without pressure compensation.UINT16mbarWrite
HR55doc 0x0037Stop continuous measurementWrite 1 to stop measuring.UINT16Write
HR56doc 0x0038Altitude compensationHeight above sea level in metres.UINT16mRead/write
HR57doc 0x0039Forced recalibration referenceReference CO2 concentration 400-2000 ppm for forced recalibration.UINT16ppmRead/write
HR58doc 0x003AAutomatic self-calibrationOff by default.UINT16Read/write0 = Off; 1 = On
HR59doc 0x003BTemperature offsetOffset for the on-board RH/T sensor in 0.01 °C steps.UINT16× 0.01°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Sensirion SCD30 CO2, humidity and temperature sensor module

What Modbus registers does the Sensirion SCD30 CO2, humidity and temperature sensor module have?

This map lists 13 registers: 13 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Sensirion SCD30 CO2, humidity and temperature sensor module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are given in hex exactly as they appear in the request frames (for example 0x61 0x03 0x00 0x28 reads from 0x0028), so they are wire addresses.

What byte order does the Sensirion SCD30 CO2, humidity and temperature sensor module use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Sensirion SCD30 CO2, humidity and temperature sensor module?

Start with HR 54 Start continuous measurement (Start continuous measurement); HR 39 Data ready status (Data ready); HR 40 CO2 concentration (CO2); HR 42 Temperature (Temperature); HR 44 Relative humidity (Humidity).

How do I enable Modbus control of the Sensirion SCD30 CO2, humidity and temperature sensor module?

Pull the SEL pin to VDD during power-up to select Modbus instead of I2C.

Where is the official Sensirion SCD30 CO2, humidity and temperature sensor module Modbus documentation?

The source is Interface Description Sensirion SCD30 Sensor Module (Version 1.0 - D1), revision 2020-05, published free by Sensirion at https://sensirion.com/media/documents/D7CEEF4A/6165372F/Sensirion_CO2_Sensors_SCD30_Interface_Description.pdf.

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Interface Description Sensirion SCD30 Sensor Module · Version 1.0 - D1 · rev. 2020-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.