Sensor (CO2, humidity, temperature module) · Modbus register map
Sensirion SCD30 CO2, humidity and temperature sensor module Modbus register map
Updated 17 November 2026
The SCD30 is an NDIR CO2 module with on-board humidity and temperature sensing. With the SEL pin tied to VDD it speaks Modbus RTU (UART level) at a fixed address and baud rate. Measurements are big-endian IEEE-754 floats; configuration commands are single 16-bit register writes.
This page lists 13 Modbus registers for the Sensirion SCD30 CO2, humidity and temperature sensor module — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sensirion’s own free documentation (linked below) and checked against it.
- Manufacturer
- Sensirion
- Model
- SCD30 CO2, humidity and temperature sensor module
- Equipment type
- Sensor (CO2, humidity, temperature module)
- Registers
- 13 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- 97
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SCD30
Integration notes: Sensirion SCD30 CO2, humidity and temperature sensor module
Write 0 (or the ambient pressure in mbar) to 0x0036 once to start measuring; the setting survives power cycles. Then poll 0x0027 for data ready and read six registers from 0x0028 for CO2, temperature and humidity.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 54 | Start continuous measurement | UINT16 | Start continuous measurement | Write |
| HR 39 | Data ready status | UINT16 | Data ready | Read |
| HR 40 | CO2 concentration | FLOAT32 ABCD | CO2 | Read |
| HR 42 | Temperature | FLOAT32 ABCD | Temperature | Read |
| HR 44 | Relative humidity | FLOAT32 ABCD | Humidity | Read |
Enable Modbus control & writes
Pull the SEL pin to VDD during power-up to select Modbus instead of I2C.
Byte order & addressing
- Address 0x61 and 19200 8N1 are fixed.
- The manual's read example fetches all six measurement registers from 0x0028 in one request (CO2, temperature, humidity, each high word first).
Network setup
- Power up with SEL high, connect TX/RX through a suitable transceiver, then send the start command.
Watch out for
- Continuous measurement and ASC states are stored in non-volatile memory and resume after power-up.
Sensirion SCD30 CO2, humidity and temperature sensor module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 32doc 0x0020 | Firmware version | High byte = major, low byte = minor. | UINT16 | Read | ||||
| HR | 37doc 0x0025 | Measurement interval | Continuous measurement interval, 2 to 1800 s (default 2 s). | UINT16 | s | Read/write | |||
| HR | 39doc 0x0027 | Data ready status | 1 when a new measurement can be read. | UINT16 | Read | 0 = No new data; 1 = Data ready | |||
| HR | 40doc 0x0028-0x0029 | CO2 concentration | FLOAT32 | ABCD | ppm | Read | |||
| HR | 42doc 0x002A-0x002B | Temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 44doc 0x002C-0x002D | Relative humidity | FLOAT32 | ABCD | % | Read | |||
| HR | 52doc 0x0034 | Soft reset | Write 1 to restart the sensor. | UINT16 | Write | ||||
| HR | 54doc 0x0036 | Start continuous measurement | Write ambient pressure 700-1400 mbar, or 0 to start without pressure compensation. | UINT16 | mbar | Write | |||
| HR | 55doc 0x0037 | Stop continuous measurement | Write 1 to stop measuring. | UINT16 | Write | ||||
| HR | 56doc 0x0038 | Altitude compensation | Height above sea level in metres. | UINT16 | m | Read/write | |||
| HR | 57doc 0x0039 | Forced recalibration reference | Reference CO2 concentration 400-2000 ppm for forced recalibration. | UINT16 | ppm | Read/write | |||
| HR | 58doc 0x003A | Automatic self-calibration | Off by default. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 59doc 0x003B | Temperature offset | Offset for the on-board RH/T sensor in 0.01 °C steps. | UINT16 | × 0.01 | °C | Read/write |
Notes on this map
- The read-measurement example returns 43 DB 8C 2E (439 ppm), 41 D9 E7 FF (27.2 °C) and 42 43 3A 1B (48.8 %RH), and the document states the values are big-endian floats, so all three are high word first.
- The sensor accepts function codes 3, 4 and 6 only; there is no multi-register write.
- The Modbus address 0x61 (97) and 19200 8N1 are fixed in this document; no command to change them is listed.
- The UART pins are at logic level; an RS-485 transceiver is needed to put the module on a bus.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Sensirion SCD30 CO2, humidity and temperature sensor module
What Modbus registers does the Sensirion SCD30 CO2, humidity and temperature sensor module have?
This map lists 13 registers: 13 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Sensirion SCD30 CO2, humidity and temperature sensor module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are given in hex exactly as they appear in the request frames (for example 0x61 0x03 0x00 0x28 reads from 0x0028), so they are wire addresses.
What byte order does the Sensirion SCD30 CO2, humidity and temperature sensor module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Sensirion SCD30 CO2, humidity and temperature sensor module?
Start with HR 54 Start continuous measurement (Start continuous measurement); HR 39 Data ready status (Data ready); HR 40 CO2 concentration (CO2); HR 42 Temperature (Temperature); HR 44 Relative humidity (Humidity).
How do I enable Modbus control of the Sensirion SCD30 CO2, humidity and temperature sensor module?
Pull the SEL pin to VDD during power-up to select Modbus instead of I2C.
Where is the official Sensirion SCD30 CO2, humidity and temperature sensor module Modbus documentation?
The source is Interface Description Sensirion SCD30 Sensor Module (Version 1.0 - D1), revision 2020-05, published free by Sensirion at https://sensirion.com/media/documents/D7CEEF4A/6165372F/Sensirion_CO2_Sensors_SCD30_Interface_Description.pdf.
Other valves, actuators & sensors register maps
- Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536
All valves, actuators & sensors Modbus register maps →
Source: Interface Description Sensirion SCD30 Sensor Module · Version 1.0 - D1 · rev. 2020-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.