Sensor (weather transmitter) · Modbus register map
Vaisala WXT530 series weather transmitters (Modbus RTU) Modbus register map
Updated 19 November 2026
The WXT530 series are compact Vaisala weather transmitters that measure wind, pressure, temperature, humidity, rain and (WXT536) external inputs. From firmware 3.85 the RS-485 user port can run Modbus RTU. All values are 16-bit integers with a scale factor; this map covers the configuration holding registers and the instant, min, max and average input registers in metric and imperial units.
This page lists 96 Modbus registers for the Vaisala WXT530 series weather transmitters (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- WXT530 series weather transmitters (Modbus RTU)
- Equipment type
- Sensor (weather transmitter)
- Registers
- 96 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- WXT531, WXT532, WXT533, WXT534, WXT535, WXT536
- Source document
- WXT530 Series User Guide · M211840EN-G · rev. 2023-05
Integration notes: Vaisala WXT530 series weather transmitters (Modbus RTU)
Read input registers 11-51 (function 04) for the metric weather values; divide by the scale factor. Holding registers 1-11 hold the configuration.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 31 | Air temperature instant | INT16 | Air temperature | Read |
| IR 10 | Relative humidity instant | INT16 | Relative humidity | Read |
| IR 14 | Relative air pressure instant | INT16 | Relative pressure | Read |
| IR 42 | Wind speed instant | INT16 | Wind speed | Read |
| IR 18 | Wind direction instant | INT16 | Wind direction | Read |
| IR 50 | Precipitation intensity | UINT16 | Rain intensity | Read |
Enable Modbus control & writes
Order with the RS-485 Modbus option (order code WXT53XU...), or on an existing unit with firmware 3.85 or newer switch from CLI to Modbus with Vaisala Configuration Tool 2.62+ or the service-port command ?XU,M=M!.
Byte order & addressing
- Register numbers start at 1; subtract 1 for the wire address.
- Precipitation counters saturate; write 0x3247 to holding register 8 to reset them.
Network setup
- Factory Modbus settings: address 1, 19200 baud, 8 data bits, even parity, 1 stop bit on the RS-485 user port.
- Change the address in holding register 10; baud, parity and stop bits can only be changed in CLI mode (?XU command), then switch back to Modbus.
Watch out for
- The RS-232 service port always uses CLI and cannot be used at the same time as the Modbus user port.
- Writing 0x0F to holding register 11 drops the unit out of Modbus mode.
- Switching between CLI and Modbus mode resets the accumulated precipitation values; moving an old unit to Modbus also rolls settings back to defaults.
- Firmware updates are only possible in CLI mode.
Vaisala WXT530 series weather transmitters (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 1 | Device identification | High byte = model (1-6 = WXT531...WXT536), low byte = last digits of SW version. | UINT16 | Read | ||||
| IR | 10doc 11 | Relative humidity instant | 32767 = invalid. | INT16 | × 0.1 | %RH | Read | ||
| IR | 11doc 12 | Relative humidity min | 32767 = invalid. | INT16 | × 0.1 | %RH | Read | ||
| IR | 12doc 13 | Relative humidity max | 32767 = invalid. | INT16 | × 0.1 | %RH | Read | ||
| IR | 13doc 14 | Relative humidity average | 32767 = invalid. | INT16 | × 0.1 | %RH | Read | ||
| IR | 14doc 15 | Relative air pressure instant | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 15doc 16 | Relative air pressure min | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 16doc 17 | Relative air pressure max | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 17doc 18 | Relative air pressure average | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 18doc 19 | Wind direction instant | 32767 = invalid. | INT16 | × 0.1 | ° | Read | ||
| IR | 19doc 20 | Wind direction min | 32767 = invalid. | INT16 | × 0.1 | ° | Read | ||
| IR | 20doc 21 | Wind direction max | 32767 = invalid. | INT16 | × 0.1 | ° | Read | ||
| IR | 21doc 22 | Wind direction average | 32767 = invalid. | INT16 | × 0.1 | ° | Read | ||
| IR | 22doc 23 | Wind direction raw | 32767 = invalid. | INT16 | × 0.1 | ° | Read | ||
| IR | 25doc 26 | Precipitation type | 32767 = invalid. | INT16 | Read | 0 = No precipitation; 40 = Precipitation; 90 = Hail | |||
| IR | 26doc 27 | Wind measurement quality | 65535 = invalid. | UINT16 | % | Read | |||
| IR | 27doc 28 | Global radiation instant | 32767 = invalid. | INT16 | × 0.1 | W/m2 | Read | ||
| IR | 28doc 29 | Global radiation min | 32767 = invalid. | INT16 | × 0.1 | W/m2 | Read | ||
| IR | 29doc 30 | Global radiation max | 32767 = invalid. | INT16 | × 0.1 | W/m2 | Read | ||
| IR | 30doc 31 | Global radiation average | 32767 = invalid. | INT16 | × 0.1 | W/m2 | Read | ||
| IR | 31doc 32 | Air temperature instant | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 32doc 33 | Air temperature min | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 33doc 34 | Air temperature max | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 34doc 35 | Air temperature average | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 35doc 36 | Dew point instant | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 36doc 37 | Dew point min | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 37doc 38 | Dew point max | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 38doc 39 | Dew point average | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 39doc 40 | Wind chill temperature | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 41doc 42 | Heater temperature | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 42doc 43 | Wind speed instant | 32767 = invalid. | INT16 | × 0.1 | m/s | Read | ||
| IR | 43doc 44 | Wind speed min | 32767 = invalid. | INT16 | × 0.1 | m/s | Read | ||
| IR | 44doc 45 | Wind speed max | 32767 = invalid. | INT16 | × 0.1 | m/s | Read | ||
| IR | 45doc 46 | Wind speed average | 32767 = invalid. | INT16 | × 0.1 | m/s | Read | ||
| IR | 47doc 48 | Wind speed raw | 32767 = invalid. | INT16 | × 0.1 | m/s | Read | ||
| IR | 48doc 49 | Precipitation accumulation (absolute) | Saturates at 655.30 mm; reset with hr 8. | UINT16 | × 0.01 | mm | Read | ||
| IR | 49doc 50 | Precipitation accumulation (since last read) | UINT16 | × 0.01 | mm | Read | |||
| IR | 50doc 51 | Precipitation intensity | UINT16 | × 0.01 | mm/h | Read | |||
| IR | 51doc 52 | Air temperature (°F) instant | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 52doc 53 | Air temperature (°F) min | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 53doc 54 | Air temperature (°F) max | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 54doc 55 | Air temperature (°F) average | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 55doc 56 | Dew point (°F) instant | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 56doc 57 | Dew point (°F) min | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 57doc 58 | Dew point (°F) max | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 58doc 59 | Dew point (°F) average | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 59doc 60 | Wind chill temperature (°F) | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 61doc 62 | Heater temperature (°F) | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 62doc 63 | Wind speed (mph) instant | 32767 = invalid. | INT16 | × 0.1 | mph | Read | ||
| IR | 63doc 64 | Wind speed (mph) min | 32767 = invalid. | INT16 | × 0.1 | mph | Read | ||
| IR | 64doc 65 | Wind speed (mph) max | 32767 = invalid. | INT16 | × 0.1 | mph | Read | ||
| IR | 65doc 66 | Wind speed (mph) average | 32767 = invalid. | INT16 | × 0.1 | mph | Read | ||
| IR | 67doc 68 | Wind speed raw (mph) | 32767 = invalid. | INT16 | × 0.1 | mph | Read | ||
| IR | 68doc 69 | Precipitation accumulation (absolute, in) | UINT16 | × 0.001 | in | Read | |||
| IR | 69doc 70 | Precipitation accumulation (since last read, in) | UINT16 | × 0.0001 | in | Read | |||
| IR | 70doc 71 | Precipitation intensity (in/h) | UINT16 | × 0.0001 | in/h | Read | |||
| IR | 71doc 72 | Absolute humidity instant | 32767 = invalid. | INT16 | × 0.1 | g/m3 | Read | ||
| IR | 72doc 73 | Absolute humidity min | 32767 = invalid. | INT16 | × 0.1 | g/m3 | Read | ||
| IR | 73doc 74 | Absolute humidity max | 32767 = invalid. | INT16 | × 0.1 | g/m3 | Read | ||
| IR | 74doc 75 | Absolute humidity average | 32767 = invalid. | INT16 | × 0.1 | g/m3 | Read | ||
| IR | 75doc 76 | Mixing ratio instant | 32767 = invalid. | INT16 | × 0.1 | g/kg | Read | ||
| IR | 76doc 77 | Mixing ratio min | 32767 = invalid. | INT16 | × 0.1 | g/kg | Read | ||
| IR | 77doc 78 | Mixing ratio max | 32767 = invalid. | INT16 | × 0.1 | g/kg | Read | ||
| IR | 78doc 79 | Mixing ratio average | 32767 = invalid. | INT16 | × 0.1 | g/kg | Read | ||
| IR | 79doc 80 | Absolute air pressure instant | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 80doc 81 | Absolute air pressure min | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 81doc 82 | Absolute air pressure max | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 82doc 83 | Absolute air pressure average | 32767 = invalid. | INT16 | × 0.1 | hPa | Read | ||
| IR | 83doc 84 | Wind speed (km/h) instant | 32767 = invalid. | INT16 | × 0.1 | km/h | Read | ||
| IR | 84doc 85 | Wind speed (km/h) min | 32767 = invalid. | INT16 | × 0.1 | km/h | Read | ||
| IR | 85doc 86 | Wind speed (km/h) max | 32767 = invalid. | INT16 | × 0.1 | km/h | Read | ||
| IR | 86doc 87 | Wind speed (km/h) average | 32767 = invalid. | INT16 | × 0.1 | km/h | Read | ||
| IR | 88doc 89 | Wind speed (knots) instant | 32767 = invalid. | INT16 | × 0.1 | kn | Read | ||
| IR | 89doc 90 | Wind speed (knots) min | 32767 = invalid. | INT16 | × 0.1 | kn | Read | ||
| IR | 90doc 91 | Wind speed (knots) max | 32767 = invalid. | INT16 | × 0.1 | kn | Read | ||
| IR | 91doc 92 | Wind speed (knots) average | 32767 = invalid. | INT16 | × 0.1 | kn | Read | ||
| IR | 93doc 94 | Wind speed raw (km/h) | 32767 = invalid. | INT16 | × 0.1 | km/h | Read | ||
| IR | 94doc 95 | Wind speed raw (knots) | 32767 = invalid. | INT16 | × 0.1 | kn | Read | ||
| IR | 98doc 99 | Wet-bulb temperature | 32767 = invalid. | INT16 | × 0.1 | °C | Read | ||
| IR | 99doc 100 | Wet-bulb temperature (°F) | 32767 = invalid. | INT16 | × 0.1 | °F | Read | ||
| IR | 100doc 101 | Specific enthalpy | 32767 = invalid. | INT16 | × 0.1 | kJ/kg | Read | ||
| IR | 101doc 102 | Air density | 32767 = invalid. | INT16 | × 0.001 | kg/m3 | Read | ||
| IR | 107doc 108 | External temperature (Pt1000) | WXT536 analog input. | INT16 | × 0.1 | °C | Read | ||
| IR | 108doc 109 | External temperature (Pt1000, °F) | WXT536 analog input. | INT16 | × 0.1 | °F | Read | ||
| IR | 109doc 110 | Wind measurement quality raw | 65535 = invalid. | UINT16 | % | Read | |||
| HR | 0doc 1 | Altitude | -100...5000, default 0. | INT16 | m | Read/write | |||
| HR | 1doc 2 | Wind direction deviation angle | -359.9...+359.9. | INT16 | × 0.1 | ° | Read/write | ||
| HR | 2doc 3 | Averaging interval T, RH, X, A, Tdw | 1-10, default 10. | UINT16 | min | Read/write | |||
| HR | 3doc 4 | Averaging interval air pressure | 1-10, default 10. | UINT16 | min | Read/write | |||
| HR | 4doc 5 | Averaging interval wind | 1-10, default 1. | UINT16 | min | Read/write | |||
| HR | 5doc 6 | Averaging interval solar radiation | 1-10, default 10. | UINT16 | min | Read/write | |||
| HR | 6doc 7 | Heating control | UINT16 | Read/write | 0 = Heating on; 1 = Heating on; 2 = Heating off; 3 = Heating on | ||||
| HR | 7doc 8 | Reset rain accumulation | Write 0x3247 to reset the precipitation counters. | UINT16 | Write | ||||
| HR | 8doc 9 | Reset device | Write 0x3247 to reset. | UINT16 | Write | ||||
| HR | 9doc 10 | Modbus address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 10doc 11 | CLI mode | Write 0x0F to leave Modbus and switch to CLI. | UINT16 | Write |
Notes on this map
- Holding registers 1-11 hold configuration and functions (read with function 03, write with function 16); measurements and device status are input registers (function 04).
- Every value is a single 16-bit register; there are no 32-bit values.
- Values are stored as value x scaling factor; divide the raw value by the listed factor. Signed values read 32767 when invalid or unavailable, unsigned values 65535.
- Available quantities depend on the model; input registers 3-8 tell which parameters and sensors are present (high/low byte 00 = available, 07 = not available).
- Do not poll faster than the update interval of the value (for example 1 min for averages).
- Tipping bucket rain gauges and level sensors are not supported over Modbus.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala WXT530 series weather transmitters (Modbus RTU)
What Modbus registers does the Vaisala WXT530 series weather transmitters (Modbus RTU) have?
This map lists 96 registers: 85 input registers, 11 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala WXT530 series weather transmitters (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every register table prints both the 1-based register number and the hex address (register 1 = 0x0000), and the text refers to holding register number 10 as 0x0009; the hex address is what goes on the wire.
What are the minimum Modbus registers to integrate the Vaisala WXT530 series weather transmitters (Modbus RTU)?
Start with IR 31 Air temperature instant (Air temperature); IR 10 Relative humidity instant (Relative humidity); IR 14 Relative air pressure instant (Relative pressure); IR 42 Wind speed instant (Wind speed); IR 18 Wind direction instant (Wind direction); IR 50 Precipitation intensity (Rain intensity).
How do I enable Modbus control of the Vaisala WXT530 series weather transmitters (Modbus RTU)?
Order with the RS-485 Modbus option (order code WXT53XU...), or on an existing unit with firmware 3.85 or newer switch from CLI to Modbus with Vaisala Configuration Tool 2.62+ or the service-port command ?XU,M=M!.
Where is the official Vaisala WXT530 series weather transmitters (Modbus RTU) Modbus documentation?
The source is WXT530 Series User Guide (M211840EN-G), revision 2023-05, published free by Vaisala at https://docs.vaisala.com/r/M211840EN-G/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Water treatment controller (Sensor / controller)
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Walchem WebMaster and WebMaster ONE controllers with the Modbus TCP/IP option, software s800/s801/s802/s811/s830 v017 and higher, per manual 180422 Rev G.
Also known as: WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830 - Sensor (Ethernet analog output module)
Acromag BusWorks XT1541-000 8-channel voltage output + 4 digital I/O (Modbus TCP)
BusWorks XT1541-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1541-000, XT1541, BusWorks XT1541 - Sensor (humidity / temperature transmitter)
E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
EE160 RH/T room/duct sensor with RS-485 interface in Modbus RTU mode, per user manual BA_EE160 v2.7 (04-2026).
Also known as: EE160, EE160-HT6, E+E EE160, EE 160 - Sensor (dissolved oxygen)
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
JUMO ecoLine O-DO type 202613 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613 - Sensor (weighing transmitter / mass converter)
Radwag MW-01-A / MW-01-A7 mass converter
Radwag MW-01-A and MW-01-A7 mass converters per the November 2021 Modbus manual.
Also known as: MW-01-A, MW-01-A7 - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200
All valves, actuators & sensors Modbus register maps →
Source: WXT530 Series User Guide · M211840EN-G · rev. 2023-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.