- EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
Sensor (humidity / temperature transmitter) · Modbus register map
E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) Modbus register map
Updated 17 November 2026
The EE160 is an HVAC humidity and temperature sensor with an RS-485 Modbus RTU port. It gives temperature and relative humidity as 32-bit floats and as 16-bit integers scaled by 100, plus serial number, firmware version and sensor name.
This page lists 7 Modbus registers for the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from E+E Elektronik’s own free documentation (linked below) and checked against it.
- Manufacturer
- E+E Elektronik
- Model
- EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
- Equipment type
- Sensor (humidity / temperature transmitter)
- Registers
- 7 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 245
- Default serial
- 9600 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- EE160, EE160-HT6, E+E EE160, EE 160
Integration notes: E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
Default 9600 baud 8E1, address 245. Read 2 registers at 0x19 for temperature and 2 at 0x1B for humidity (floats, low word first), or 0x12C/0x12D for x100 integers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 25 | Temperature T | FLOAT32 CDAB | Temperature, float | Read |
| HR 27 | Relative humidity RH | FLOAT32 CDAB | Relative humidity, float | Read |
| HR 300 | Temperature T (integer) | INT16 | Temperature, integer x100 | Read |
| HR 301 | Relative humidity RH (integer) | INT16 | Relative humidity, integer x100 | Read |
Enable Modbus control & writes
Modbus RTU is the interface. Set address and serial settings with PCS10 and the USB-C configuration stick HA011070; a non-zero DIP-switch address overrides any software-set address.
Byte order & addressing
- Floats are low word first (CDAB).
- Read both float registers in one request so both halves match.
- Serial number and sensor name need all 8 registers read at once.
Network setup
- Factory settings: 9600 baud, 8 data bits, even parity, 1 stop bit, Modbus address 245.
- Selectable: 9600-115200 baud, none/odd/even parity, 1 or 2 stop bits, address 1-247.
- All DIP switches at 0 means the address set in PCS10 is used.
- A jumper terminates the bus; it is off (not terminated) from the factory.
Watch out for
- Default address is 245, not 1.
- °C vs °F is an order option, not a setting.
E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 (0x00) | Serial number | ASCII text across 8 registers; read all 8. | STRING[16] | Read | ||||
| HR | 8doc 9 (0x08) | Firmware version | High byte = major release, low byte = minor release. | UINT16 | Read | ||||
| HR | 9doc 10 (0x09) | Sensor name | ASCII text across 8 registers; read all 8. | STRING[16] | Read | ||||
| HR | 25doc 26 (0x19) | Temperature T | Float; °F on non-metric order versions. | FLOAT32 | CDAB | °C | Read | ||
| HR | 27doc 28 (0x1B) | Relative humidity RH | Float. | FLOAT32 | CDAB | %RH | Read | ||
| HR | 300doc 301 (0x12C) | Temperature T (integer) | Value x100; °F on non-metric order versions. | INT16 | × 0.01 | °C | Read | ||
| HR | 301doc 302 (0x12D) | Relative humidity RH (integer) | Value x100. | INT16 | × 0.01 | %RH | Read |
Notes on this map
- Float word order: the manual's worked example reads 0x19 and gets 51 F0 41 BA, decoded as IEEE 754 0x41BA51F0 = 23.29 °C. The first register holds the low word, so floats are CDAB.
- Metric or US units are fixed by the order code and cannot be changed with PCS10; the unit fields show the metric case.
- The integer block uses scale 100 per the manual (2550 = 25.5).
- Left out: write-only setup registers 0x00 (Modbus address) and 0x01 (protocol settings); the manual refers to E+E note AN0103 for their coding.
- Measured values can be read with function 03 or 04; they are filed here as holding registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
What Modbus registers does the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) have?
This map lists 7 registers: 7 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a decimal register number starting at 1 and a hex register address starting at 0. Send the hex address: temperature is register 26, address 0x19, and the manual's example request reads 0x0019.
What byte order does the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)?
Start with HR 25 Temperature T (Temperature, float); HR 27 Relative humidity RH (Relative humidity, float); HR 300 Temperature T (integer) (Temperature, integer x100); HR 301 Relative humidity RH (integer) (Relative humidity, integer x100).
How do I enable Modbus control of the E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)?
Modbus RTU is the interface. Set address and serial settings with PCS10 and the USB-C configuration stick HA011070; a non-zero DIP-switch address overrides any software-set address.
Where is the official E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU) Modbus documentation?
The source is User Manual EE160 Humidity and Temperature Sensor for Building Automation (BA_EE160 v2.7), revision 2026-04, published free by E+E Elektronik at https://downloads.epluse.com/fileadmin/data/product/ee160/BA_EE160.pdf.
More E+E Elektronik Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (dissolved oxygen)
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
JUMO ecoLine O-DO type 202613 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613 - Sensor (weighing transmitter / mass converter)
Radwag MW-01-A / MW-01-A7 mass converter
Radwag MW-01-A and MW-01-A7 mass converters per the November 2021 Modbus manual.
Also known as: MW-01-A, MW-01-A7 - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series
All valves, actuators & sensors Modbus register maps →
Source: User Manual EE160 Humidity and Temperature Sensor for Building Automation · BA_EE160 v2.7 · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.