JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) Modbus register map
Updated 19 November 2026
The JUMO ecoLine O-DO is an optical (luminescence) dissolved oxygen sensor with a built-in RS-485 Modbus RTU interface. Measurements are started by the master. This map covers the start command, the measurement status word, temperature and oxygen readings and the compensation inputs.
This page lists 9 Modbus registers for the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from JUMO’s own free documentation (linked below) and checked against it.
- Manufacturer
- JUMO
- Model
- ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
- Equipment type
- Sensor (dissolved oxygen)
- Registers
- 9 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613
Integration notes: JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
Write the compensation values (93-98), write 7 to register 1, wait 300 ms, poll register 82 until no 3-bit field equals 7, then read 83-90 as ABCD floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Start measuring operation | UINT16 | Start a measurement | Write |
| HR 82 | Measuring operation status | UINT16 | Measurement status | Read |
| HR 83 | Temperature | FLOAT32 ABCD | Temperature | Read |
| HR 85 | Oxygen saturation | FLOAT32 ABCD | O2 saturation | Read |
| HR 87 | Oxygen concentration | FLOAT32 ABCD | O2 mg/l | Read |
Enable Modbus control & writes
Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.
Byte order & addressing
- Floats are high word first (ABCD).
- No Modbus requests are allowed for 300 ms after a start command; requests during that window are ignored.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit; address 1-247.
- Wire A/B on M12 pins 5/4; the sensor needs +5 V on pin 1.
Watch out for
- Resend the compensation values after every power-up; they are not stored.
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 1 (0x0001) | Start measuring operation | Starts one measurement cycle. | UINT16 | Write | 3 = Temperature + O2 %Sat; 7 = Temperature + O2 %Sat and mg/l; 11 = Temperature + O2 %Sat and ppm | |||
| HR | 82doc 82 (0x0052) | Measuring operation status | Bits 0-2 temp, 3-5 O2 %Sat, 6-8 mg/l, 9-11 ppm; field value 7 = not done. | UINT16 | Read | ||||
| HR | 83doc 83 (0x0053) | Temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 85doc 85 (0x0055) | Oxygen saturation | FLOAT32 | ABCD | %Sat | Read | |||
| HR | 87doc 87 (0x0057) | Oxygen concentration | FLOAT32 | ABCD | mg/l | Read | |||
| HR | 89doc 89 (0x0059) | Oxygen concentration | FLOAT32 | ABCD | ppm | Read | |||
| HR | 93doc 93 (0x005D) | Compensation temperature | Default 25 °C; not stored, resend after power-up. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 95doc 95 (0x005F) | Compensation air pressure | Default 1023 hPa. | FLOAT32 | ABCD | hPa | Read/write | ||
| HR | 97doc 97 (0x0061) | Compensation salt content | Default 0 g/kg. | FLOAT32 | ABCD | g/kg | Read/write |
Notes on this map
- Floats are IEEE 754 sent high word first (ABCD); the worked example returns 41 CA 66 66 = 25.3 °C for start address 0x0053.
- Measurements are triggered: write a start command to register 1, wait at least 300 ms without any Modbus traffic, poll the status word at 82 until no field reads 7, then read the values.
- Integers are unsigned 16-bit, high byte first.
- Each 3-bit field: 0 OK, 1 OK but outside sensor spec, 2 OK with reduced accuracy, 3 OK (reserved), 4 failed outside spec, 5 failed (membrane cap missing or damaged), 6 failed (reserved), 7 not yet complete.
- Only the values requested by the start command are valid after a cycle; ignore the others.
- Compensation values are not saved in the sensor; the master must write them before measuring if they differ from the defaults. Whether the sensor uses its own or the written temperature is chosen in JUMO DSM software.
- The membrane is rated for about 1 million measurements, so do not trigger faster than needed.
- The document gives the address range 1-247 but does not state a factory default address.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
What Modbus registers does the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) have?
This map lists 9 registers: 9 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables list the Modbus PDU address in decimal and hex; the value goes into the request unchanged (the example reads the temperature at start address 0x0053).
What byte order does the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)?
Start with HR 1 Start measuring operation (Start a measurement); HR 82 Measuring operation status (Measurement status); HR 83 Temperature (Temperature); HR 85 Oxygen saturation (O2 saturation); HR 87 Oxygen concentration (O2 mg/l).
How do I enable Modbus control of the JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)?
Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.
Where is the official JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU) Modbus documentation?
The source is JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description (20261300T92Z003K000 V1.01/EN/00692386), published free by JUMO at https://www.jumo.net/attachments/JUMO/attachmentdownload?id=494310.
More JUMO Modbus register maps
- Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (turbidity)
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
JUMO ecoLine NTU type 202670 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202670, JUMO ecoLine NTU, ecoLine NTU type 202670 - Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM
Other valves, actuators & sensors register maps
- Sensor (weighing transmitter / mass converter)
Radwag MW-01-A / MW-01-A7 mass converter
Radwag MW-01-A and MW-01-A7 mass converters per the November 2021 Modbus manual.
Also known as: MW-01-A, MW-01-A7 - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110
All valves, actuators & sensors Modbus register maps →
Source: JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description · 20261300T92Z003K000 V1.01/EN/00692386. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.