Sensor (turbidity) · Modbus register map
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus register map
Updated 19 November 2026
The JUMO ecoLine NTU is an optical turbidity sensor with a built-in RS-485 Modbus RTU interface. Measurements are started by the master. This map covers the start command, the measurement status word, temperature and turbidity in NTU and FNU.
This page lists 5 Modbus registers for the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from JUMO’s own free documentation (linked below) and checked against it.
- Manufacturer
- JUMO
- Model
- ecoLine NTU digital turbidity sensor (Modbus RTU)
- Equipment type
- Sensor (turbidity)
- Registers
- 5 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 202670, JUMO ecoLine NTU, ecoLine NTU type 202670
Integration notes: JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
Write 3 (NTU) or 5 (FNU) to register 1, wait 300 ms, poll register 82 until no 3-bit field equals 7, then read 83-88 as ABCD floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Start measuring operation | UINT16 | Start a measurement | Write |
| HR 82 | Measuring operation status | UINT16 | Measurement status | Read |
| HR 83 | Temperature | FLOAT32 ABCD | Temperature | Read |
| HR 85 | Turbidity | FLOAT32 ABCD | Turbidity NTU | Read |
Enable Modbus control & writes
Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.
Byte order & addressing
- Floats are high word first (ABCD).
- No Modbus requests are allowed for 300 ms after a start command.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit; address 1-247.
- Wire A/B on M12 pins 5/4; the sensor needs +5 V on pin 1.
Watch out for
- Strong ambient light makes readings fail (status 5) or lose accuracy (status 2).
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 1 (0x0001) | Start measuring operation | Starts one measurement cycle. | UINT16 | Write | 1 = Temperature only; 3 = Temperature + turbidity NTU; 5 = Temperature + turbidity FNU | |||
| HR | 82doc 82 (0x0052) | Measuring operation status | Bits 0-2 temp, 3-5 NTU, 6-8 FNU; field value 7 = not done. | UINT16 | Read | ||||
| HR | 83doc 83 (0x0053) | Temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 85doc 85 (0x0055) | Turbidity | FLOAT32 | ABCD | NTU | Read | |||
| HR | 87doc 87 (0x0057) | Turbidity | FLOAT32 | ABCD | FNU | Read |
Notes on this map
- Floats are IEEE 754 sent high word first (ABCD); the worked example returns 41 CA 66 66 = 25.3 °C for start address 0x0053.
- Measurements are triggered: write a start command to register 1, wait at least 300 ms without any Modbus traffic, poll the status word at 82 until no field reads 7, then read the values.
- Integers are unsigned 16-bit, high byte first.
- Each 3-bit field: 0 OK, 1 OK but outside sensor spec, 2 OK with reduced accuracy, 3 OK (reserved), 4 failed outside spec, 5 failed (too much extraneous light), 6 failed (reserved), 7 not yet complete.
- The status table names the third field FTU while the value table uses FNU; both refer to the formazin nephelometric reading.
- The NTU step-by-step text mentions a start value of 31, but the address table lists only 1, 3 and 5; this map follows the table.
- The document gives the address range 1-247 but does not state a factory default address.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
What Modbus registers does the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) have?
This map lists 5 registers: 5 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables list the Modbus PDU address in decimal and hex; the value goes into the request unchanged (the example reads the temperature at start address 0x0053).
What byte order does the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)?
Start with HR 1 Start measuring operation (Start a measurement); HR 82 Measuring operation status (Measurement status); HR 83 Temperature (Temperature); HR 85 Turbidity (Turbidity NTU).
How do I enable Modbus control of the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)?
Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.
Where is the official JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus documentation?
The source is JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description (20261300T92Z003K000 V1.01/EN/00692386), published free by JUMO at https://www.jumo.net/attachments/JUMO/attachmentdownload?id=494310.
More JUMO Modbus register maps
- Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (dissolved oxygen)
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
JUMO ecoLine O-DO type 202613 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613 - Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM
Other valves, actuators & sensors register maps
- Sensor (vibration / temperature)
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
Machine Saver TriVibe triaxial vibration sensors on RS-485 Modbus RTU, per the 'Modbus Registers Map' page of the Machine Saver online library (revision #12).
Also known as: TriVibe, Machine Saver TriVibe - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus
All valves, actuators & sensors Modbus register maps →
Source: JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description · 20261300T92Z003K000 V1.01/EN/00692386. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.