Sensor (turbidity) · Modbus register map

JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The JUMO ecoLine NTU is an optical turbidity sensor with a built-in RS-485 Modbus RTU interface. Measurements are started by the master. This map covers the start command, the measurement status word, temperature and turbidity in NTU and FNU.

This page lists 5 Modbus registers for the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from JUMO’s own free documentation (linked below) and checked against it.

Manufacturer
JUMO
Model
ecoLine NTU digital turbidity sensor (Modbus RTU)
Equipment type
Sensor (turbidity)
Registers
5 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
202670, JUMO ecoLine NTU, ecoLine NTU type 202670
Source document
JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description · 20261300T92Z003K000 V1.01/EN/00692386
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)

Integration in brief

Write 3 (NTU) or 5 (FNU) to register 1, wait 300 ms, poll register 82 until no 3-bit field equals 7, then read 83-88 as ABCD floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Start measuring operationUINT16Start a measurementWrite
HR 82Measuring operation statusUINT16Measurement statusRead
HR 83TemperatureFLOAT32 ABCDTemperatureRead
HR 85TurbidityFLOAT32 ABCDTurbidity NTURead

Enable Modbus control & writes

Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.

Byte order & addressing

Network setup

Watch out for

JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

5 of 5 shown
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 1 (0x0001)Start measuring operationStarts one measurement cycle.UINT16Write1 = Temperature only; 3 = Temperature + turbidity NTU; 5 = Temperature + turbidity FNU
HR82doc 82 (0x0052)Measuring operation statusBits 0-2 temp, 3-5 NTU, 6-8 FNU; field value 7 = not done.UINT16Read
HR83doc 83 (0x0053)TemperatureFLOAT32ABCD°CRead
HR85doc 85 (0x0055)TurbidityFLOAT32ABCDNTURead
HR87doc 87 (0x0057)TurbidityFLOAT32ABCDFNURead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)

What Modbus registers does the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) have?

This map lists 5 registers: 5 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables list the Modbus PDU address in decimal and hex; the value goes into the request unchanged (the example reads the temperature at start address 0x0053).

What byte order does the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)?

Start with HR 1 Start measuring operation (Start a measurement); HR 82 Measuring operation status (Measurement status); HR 83 Temperature (Temperature); HR 85 Turbidity (Turbidity NTU).

How do I enable Modbus control of the JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)?

Modbus RTU is the sensor's native interface; set the address with JUMO DSM software.

Where is the official JUMO ecoLine NTU digital turbidity sensor (Modbus RTU) Modbus documentation?

The source is JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description (20261300T92Z003K000 V1.01/EN/00692386), published free by JUMO at https://www.jumo.net/attachments/JUMO/attachmentdownload?id=494310.

More JUMO Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: JUMO ecoLine O-DO/NTU - Digital sensors for turbidity and oxygen measurement - Modbus interface description · 20261300T92Z003K000 V1.01/EN/00692386. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.