Sensor (humidity / temperature probe) · Modbus register map
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) Modbus register map
Updated 17 November 2026
The EE260 is an M12-connected humidity and temperature probe for weather stations, with two analogue outputs and an RS-485 Modbus RTU port. It publishes every measured and calculated humidity quantity twice: as 32-bit floats and as scaled 16-bit integers, in metric and US units. This map lists both blocks.
This page lists 52 Modbus registers for the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from E+E Elektronik’s own free documentation (linked below) and checked against it.
- Manufacturer
- E+E Elektronik
- Model
- EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
- Equipment type
- Sensor (humidity / temperature probe)
- Registers
- 52 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 235
- Default serial
- 9600 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- EE260, E+E EE260, EE 260
Integration notes: E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
Connect at 9600 baud, 8E1, address 235, and read two registers from 0x3EA for temperature (float, low word first) and from 0x3FC for relative humidity. If the master cannot swap words, read the scaled integers at 0xFA1 (T x100) and 0xFAA (RH x100).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1002 | Temperature T (°C) | FLOAT32 CDAB | Temperature, float °C | Read |
| HR 1020 | Relative humidity RH (%RH) | FLOAT32 CDAB | Relative humidity, float %RH | Read |
| HR 1104 | Dew point temperature Td (°C) | FLOAT32 CDAB | Dew point, float °C | Read |
| HR 4001 | Temperature T (°C, integer) | INT16 | Temperature, integer °C x100 | Read |
| HR 4010 | Relative humidity RH (%RH, integer) | INT16 | Relative humidity, integer x100 | Read |
Enable Modbus control & writes
Address, baud rate, parity and stop bits are set with the free PCS10 software through the HA011018 adapter and HA011020 cable.
Byte order & addressing
- Floats are low word first (CDAB).
- Integer °F temperature uses divisor 50, not 100.
- Register numbers in the guide are 1-based; subtract 1.
Network setup
- Factory settings: 9600 baud, 8 data bits, even parity, 1 stop bit, address 235.
- Selectable: 9600-115200 baud, none/odd/even parity, 1 or 2 stop bits, address 1-247.
- Supply 7-30 V DC; RS-485 A (D+) is pin 6, B (D-) is pin 2 on the M12 plug.
Watch out for
- The factory address is 235, not 1.
- Use a shielded cable to stay inside the EMC figures.
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1002doc 1003 (0x3EA) | Temperature T (°C) | IEEE 754 float. | FLOAT32 | CDAB | °C | Read | ||
| HR | 1004doc 1005 (0x3EC) | Temperature T (°F) | IEEE 754 float. | FLOAT32 | CDAB | °F | Read | ||
| HR | 1020doc 1021 (0x3FC) | Relative humidity RH (%RH) | IEEE 754 float. | FLOAT32 | CDAB | %RH | Read | ||
| HR | 1100doc 1101 (0x44C) | Water vapour partial pressure e (mbar) | IEEE 754 float. | FLOAT32 | CDAB | mbar | Read | ||
| HR | 1102doc 1103 (0x44E) | Water vapour partial pressure e (psi) | IEEE 754 float. | FLOAT32 | CDAB | psi | Read | ||
| HR | 1104doc 1105 (0x450) | Dew point temperature Td (°C) | IEEE 754 float. | FLOAT32 | CDAB | °C | Read | ||
| HR | 1106doc 1107 (0x452) | Dew point temperature Td (°F) | IEEE 754 float. | FLOAT32 | CDAB | °F | Read | ||
| HR | 1108doc 1109 (0x454) | Wet bulb temperature Tw (°C) | IEEE 754 float. | FLOAT32 | CDAB | °C | Read | ||
| HR | 1110doc 1111 (0x456) | Wet bulb temperature Tw (°F) | IEEE 754 float. | FLOAT32 | CDAB | °F | Read | ||
| HR | 1112doc 1113 (0x458) | Absolute humidity dv (g/m3) | IEEE 754 float. | FLOAT32 | CDAB | g/m3 | Read | ||
| HR | 1114doc 1115 (0x45A) | Absolute humidity dv (gr/ft3) | IEEE 754 float. | FLOAT32 | CDAB | gr/ft3 | Read | ||
| HR | 1120doc 1121 (0x460) | Mixing ratio r (g/kg) | IEEE 754 float. | FLOAT32 | CDAB | g/kg | Read | ||
| HR | 1122doc 1123 (0x462) | Mixing ratio r (gr/lb) | IEEE 754 float. | FLOAT32 | CDAB | gr/lb | Read | ||
| HR | 1124doc 1125 (0x464) | Specific enthalpy h (kJ/kg) | IEEE 754 float. | FLOAT32 | CDAB | kJ/kg | Read | ||
| HR | 1128doc 1129 (0x468) | Specific enthalpy h (BTU/lb) | IEEE 754 float. | FLOAT32 | CDAB | BTU/lb | Read | ||
| HR | 1130doc 1131 (0x46A) | Frost point temperature Tf (°C) | IEEE 754 float. | FLOAT32 | CDAB | °C | Read | ||
| HR | 1132doc 1133 (0x46C) | Frost point temperature Tf (°F) | IEEE 754 float. | FLOAT32 | CDAB | °F | Read | ||
| HR | 1150doc 1151 (0x47E) | Volume concentration Wv (ppm) | IEEE 754 float. | FLOAT32 | CDAB | ppm | Read | ||
| HR | 1220doc 1221 (0x4C4) | Saturation vapour pressure over water ew (mbar) | IEEE 754 float. | FLOAT32 | CDAB | mbar | Read | ||
| HR | 1222doc 1223 (0x4C6) | Saturation vapour pressure over water ew (psi) | IEEE 754 float. | FLOAT32 | CDAB | psi | Read | ||
| HR | 1224doc 1225 (0x4C8) | Saturation vapour pressure over ice ei (mbar) | IEEE 754 float. | FLOAT32 | CDAB | mbar | Read | ||
| HR | 1226doc 1227 (0x4CA) | Saturation vapour pressure over ice ei (psi) | IEEE 754 float. | FLOAT32 | CDAB | psi | Read | ||
| HR | 1236doc 1237 (0x4D4) | Ice bulb temperature Ti (°C) | IEEE 754 float. | FLOAT32 | CDAB | °C | Read | ||
| HR | 1238doc 1239 (0x4D6) | Ice bulb temperature Ti (°F) | IEEE 754 float. | FLOAT32 | CDAB | °F | Read | ||
| HR | 1246doc 1247 (0x4DE) | Specific humidity qv (g/kg) | IEEE 754 float. | FLOAT32 | CDAB | g/kg | Read | ||
| HR | 1248doc 1249 (0x4E0) | Specific humidity qv (gr/lb) | IEEE 754 float. | FLOAT32 | CDAB | gr/lb | Read | ||
| HR | 4001doc 4002 (0xFA1) | Temperature T (°C, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °C | Read | ||
| HR | 4002doc 4003 (0xFA2) | Temperature T (°F, integer) | Raw value divided by 50 (scale column). | INT16 | × 0.02 | °F | Read | ||
| HR | 4010doc 4011 (0xFAA) | Relative humidity RH (%RH, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | %RH | Read | ||
| HR | 4050doc 4051 (0xFD2) | Water vapour partial pressure e (mbar, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | mbar | Read | ||
| HR | 4051doc 4052 (0xFD3) | Water vapour partial pressure e (psi, integer) | Raw value divided by 1000 (scale column). | INT16 | × 0.001 | psi | Read | ||
| HR | 4052doc 4053 (0xFD4) | Dew point temperature Td (°C, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °C | Read | ||
| HR | 4053doc 4054 (0xFD5) | Dew point temperature Td (°F, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °F | Read | ||
| HR | 4054doc 4055 (0xFD6) | Wet bulb temperature Tw (°C, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °C | Read | ||
| HR | 4055doc 4056 (0xFD7) | Wet bulb temperature Tw (°F, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °F | Read | ||
| HR | 4056doc 4057 (0xFD8) | Absolute humidity dv (g/m3, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | g/m3 | Read | ||
| HR | 4057doc 4058 (0xFD9) | Absolute humidity dv (gr/ft3, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | gr/ft3 | Read | ||
| HR | 4060doc 4061 (0xFDC) | Mixing ratio r (g/kg, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | g/kg | Read | ||
| HR | 4061doc 4062 (0xFDD) | Mixing ratio r (gr/lb, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | gr/lb | Read | ||
| HR | 4062doc 4063 (0xFDE) | Specific enthalpy h (kJ/kg, integer) | Raw value divided by 1 (scale column). | INT16 | kJ/kg | Read | |||
| HR | 4064doc 4065 (0xFE0) | Specific enthalpy h (BTU/lb, integer) | Raw value divided by 1 (scale column). | INT16 | BTU/lb | Read | |||
| HR | 4065doc 4066 (0xFE1) | Frost point temperature Tf (°C, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °C | Read | ||
| HR | 4066doc 4067 (0xFE2) | Frost point temperature Tf (°F, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °F | Read | ||
| HR | 4075doc 4076 (0xFEB) | Volume concentration Wv (ppm, integer) | Raw value divided by 0.1 (scale column). | INT16 | × 10 | ppm | Read | ||
| HR | 4110doc 4111 (0x100E) | Saturation vapour pressure over water ew (mbar, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | mbar | Read | ||
| HR | 4111doc 4112 (0x100F) | Saturation vapour pressure over water ew (psi, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | psi | Read | ||
| HR | 4112doc 4113 (0x1010) | Saturation vapour pressure over ice ei (mbar, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | mbar | Read | ||
| HR | 4113doc 4114 (0x1011) | Saturation vapour pressure over ice ei (psi, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | psi | Read | ||
| HR | 4118doc 4119 (0x1016) | Ice bulb temperature Ti (°C, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °C | Read | ||
| HR | 4119doc 4120 (0x1017) | Ice bulb temperature Ti (°F, integer) | Raw value divided by 100 (scale column). | INT16 | × 0.01 | °F | Read | ||
| HR | 4123doc 4124 (0x101B) | Specific humidity qv (g/kg, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | g/kg | Read | ||
| HR | 4124doc 4125 (0x101C) | Specific humidity qv (gr/lb, integer) | Raw value divided by 10 (scale column). | INT16 | × 0.1 | gr/lb | Read |
Notes on this map
- Float word order comes from E+E application note AN0103 Rev. 1.4 (11/2020), section 7.2, which the quick guide points to: the two byte pairs of a float are swapped (bytes 3-4 first, then 1-2), i.e. low word first (CDAB). The note's write example (1013.25 mbar sent as 49 9A 44 7D) also puts the high word 44 7D second. AN0103: https://downloads.epluse.com/fileadmin/data/product/ee071/AN0103.pdf
- Integer scaling: the quick guide's scale column is a divisor (scale 100: a reading of 2550 = 25.5; scale 50: 2550 = 51). The scale field here is the matching multiplier, so the ppm row with divisor 0.1 becomes x10.
- Measured values can be read with function 03 or 04 (both are listed); they are filed here as holding registers.
- Left out: the slave-address register (0x00) and communication-settings register (0x01). AN0103 says they are write-only and does not fully define the settings byte coding.
- Read each float with one request for both registers, so both halves come from the same measurement (AN0103 advice).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
What Modbus registers does the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) have?
This map lists 52 registers: 52 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The quick guide prints a decimal register number that starts at 1 and a hex register address that starts at 0 (1003 = 0x3EA). Send the hex address on the wire: register number minus 1.
What byte order does the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)?
Start with HR 1002 Temperature T (°C) (Temperature, float °C); HR 1020 Relative humidity RH (%RH) (Relative humidity, float %RH); HR 1104 Dew point temperature Td (°C) (Dew point, float °C); HR 4001 Temperature T (°C, integer) (Temperature, integer °C x100); HR 4010 Relative humidity RH (%RH, integer) (Relative humidity, integer x100).
How do I enable Modbus control of the E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)?
Address, baud rate, parity and stop bits are set with the free PCS10 software through the HA011018 adapter and HA011020 cable.
Where is the official E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU) Modbus documentation?
The source is Quick Guide EE260 - Humidity and Temperature Probe for Meteorological Applications (QG_EE260 v1.3 (194928)), revision 2025-10, published free by E+E Elektronik at https://downloads.epluse.com/fileadmin/data/product/ee260/QG_EE260.pdf.
More E+E Elektronik Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM - Sensor (weighing indicator)
Radwag PUE C32 / PUE HX7 / PUE HX5.EX weighing indicators
Radwag PUE C32, PUE HX7 and PUE HX5.EX weighing indicators per the May 2024 Modbus manual; platform 2 registers exist on PUE HX7 only.
Also known as: PUE C32, PUE HX7, PUE HX5.EX - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143
All valves, actuators & sensors Modbus register maps →
Source: Quick Guide EE260 - Humidity and Temperature Probe for Meteorological Applications · QG_EE260 v1.3 (194928) · rev. 2025-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.