Sensor (HVAC humidity, temperature and CO2 transmitter) · Modbus register map

Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Origo10 is Vaisala's modular HVAC transmitter: a duct or wall housing that takes up to two probes (XMP10 humidity/temperature, CO2, temperature) and up to three plug-in modules such as the DIO10 relay/binary-input module. The Origo10A version offers Modbus RTU (or BACnet MS/TP) on RS-485. Each probe or module gets its own 4096-register block; this map lists probe A in full, the main probe B readings, module 1 relay/input, transmitter status, serial settings and test registers.

This page lists 43 Modbus registers for the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Equipment type
Sensor (HVAC humidity, temperature and CO2 transmitter)
Registers
43 (5 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter
Source document
Origo10 User Guide · M213293EN-B · rev. 2026-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)

Integration in brief

Read registers 257-260 (wire 256-259) for probe A humidity and temperature as low-word-first floats, add 277 for CO2 if a CO2 probe is fitted, and watch the transmitter status code at 49153.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 256Probe A relative humidityFLOAT32 CDABProbe A relative humidityRead
HR 258Probe A temperatureFLOAT32 CDABProbe A temperatureRead
HR 260Probe A dew point temperatureFLOAT32 CDABDew pointRead
HR 276Probe A CO2 concentration (ppm)FLOAT32 CDABCO2 ppm (CO2 probe)Read
HR 48Probe A status codeUINT32 CDABProbe A statusRead
HR 49152Transmitter status code lowUINT32 CDABTransmitter error/warning bitsRead

Enable Modbus control & writes

Order Origo10A with the Modbus RTU output option. Serial settings and the Modbus address can be changed in Vaisala Insight PC software over the USB-C service port or through registers 51202-51205.

Byte order & addressing

Network setup

Watch out for

Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Probe A product code32-character text.STRING[32]Read
HR16doc 17Probe A serial numberSTRING[32]Read
HR32doc 33Probe A versionSTRING[32]Read
HR48doc 49Probe A status codeUINT32CDABReadbit 0 = Failure active; bit 1 = Error active; bit 2 = Warning active; bit 3 = Information active; bit 4 = Calibration mode active
HR256doc 257Probe A relative humidityFLOAT32CDAB%RHRead
HR258doc 259Probe A temperatureFLOAT32CDAB°CRead
HR260doc 261Probe A dew point temperatureFLOAT32CDAB°CRead
HR262doc 263Probe A dew/frost point temperatureFLOAT32CDAB°CRead
HR264doc 265Probe A absolute humidityFLOAT32CDABg/m3Read
HR266doc 267Probe A mixing ratioFLOAT32CDABg/kgRead
HR268doc 269Probe A wet-bulb temperatureFLOAT32CDAB°CRead
HR270doc 271Probe A water vapor pressureFLOAT32CDABhPaRead
HR272doc 273Probe A water vapor saturation pressureFLOAT32CDABhPaRead
HR274doc 275Probe A enthalpyFLOAT32CDABkJ/kgRead
HR276doc 277Probe A CO2 concentration (ppm)With a CO2 probe connected.FLOAT32CDABppmRead
HR278doc 279Probe A CO2 concentration (%)FLOAT32CDAB%Read
HR512doc 513Probe A relative humidity (non-metric block)FLOAT32CDAB%RHRead
HR514doc 515Probe A temperature (non-metric block)FLOAT32CDAB°FRead
HR516doc 517Probe A dew point temperature (non-metric block)FLOAT32CDAB°FRead
HR530doc 531Probe A enthalpy (non-metric block)FLOAT32CDABBTU/lbRead
HR768doc 769Probe A RH measurement status0 = status OK.BITMAP16Readbit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready
HR769doc 770Probe A T measurement statusBITMAP16Readbit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready
HR778doc 779Probe A CO2 ppm measurement statusBITMAP16Readbit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready
HR4352doc 4353Probe B relative humiditySame layout as probe A, offset by 4096.FLOAT32CDAB%RHRead
HR4354doc 4355Probe B temperatureFLOAT32CDAB°CRead
HR4372doc 4373Probe B CO2 concentration (ppm)FLOAT32CDABppmRead
HR8242doc 8243Module 1 relay output controlDIO10 module in slot M1.UINT16Read0 = Inactive; 1 = Active; 2 = N/A
HR8472doc 8473Module 1 binary inputUINT16Read0 = Loop open; 1 = Loop closed; 2 = N/A
HR8474doc 8475Module 1 relay outputUINT16Read0 = Inactive; 1 = Active; 2 = N/A
HR49152doc 49153Transmitter status code lowUINT32CDABReadbit 0 = Non-volatile memory read/write failure; bit 1 = Device settings corrupted; bit 2 = Factory settings corrupted; bit 4 = Probe current limit exceeded; bit 7 = Probe type not supported; bit 8 = Module type not supported; bit 11 = Probe missing; bit 12 = Module missing; bit 16 = Cannot read all measurement parameters; bit 17 = Analog output 1 out of range; bit 18 = Analog output 2 out of range; bit 19 = Analog output 3 out of range; bit 20 = Analog output 1 test mode active; bit 21 = Analog output 2 test mode active; bit 22 = Analog output 3 test mode active; bit 23 = Analog output 1 calibration active; bit 24 = Analog output 2 calibration active; bit 25 = Analog output 3 calibration active; bit 26 = Supply voltage out of range; bit 27 = Probe 1 not detected; bit 28 = Probe 2 not detected; bit 29 = Module 1 not detected; bit 30 = Module 2 not detected; bit 31 = Module 3 not detected
HR49154doc 49155Transmitter status code highUINT32CDABReadbit 0 = Restart to apply settings; bit 1 = Configuration locked; bit 2 = Configuration unlocked
HR49156doc 49157Firmware versionSTRING[32]Read
HR49172doc 49173Security hashINT32CDABRead
HR49174doc 49175Vendor nameSTRING[16]Read
HR49206doc 49207Product codeSTRING[16]Read
HR49262doc 49263Serial numberSTRING[8]Read
HR49664doc 49665Restart deviceWrite 1 to restart.INT16Read/write
HR50949doc 50950Signed integer testAlways reads -12345.INT16Read
HR50950doc 50951Floating point testAlways reads -123.45.FLOAT32CDABRead
HR51201doc 51202Modbus address1-247, default 240.INT16Read/write
HR51202doc 51203Bit rateUINT16Read/write0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600; 9 = 76800; 10 = 115200
HR51203doc 51204Parity, data, stop bitsUINT16Read/write0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2
HR51204doc 51205Response delay0-1000 ms, default 20.INT16msRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)

What Modbus registers does the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) have?

This map lists 43 registers: 43 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered in decimal from 1 and the guide also prints the 0-based hex PDU address; register 1 is address 0x0000. Subdevice blocks: register = base + X * 4096, with X = 0 probe A, 1 probe B, 2-4 modules 1-3 (hex address 0xX000 style).

What byte order does the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)?

Start with HR 256 Probe A relative humidity (Probe A relative humidity); HR 258 Probe A temperature (Probe A temperature); HR 260 Probe A dew point temperature (Dew point); HR 276 Probe A CO2 concentration (ppm) (CO2 ppm (CO2 probe)); HR 48 Probe A status code (Probe A status); HR 49152 Transmitter status code low (Transmitter error/warning bits).

How do I enable Modbus control of the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)?

Order Origo10A with the Modbus RTU output option. Serial settings and the Modbus address can be changed in Vaisala Insight PC software over the USB-C service port or through registers 51202-51205.

Where is the official Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus documentation?

The source is Origo10 User Guide (M213293EN-B), revision 2026-05, published free by Vaisala at https://docs.vaisala.com/r/M213293EN-B/en-US.