- Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Sensor (HVAC humidity, temperature and CO2 transmitter) · Modbus register map
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus register map
Updated 19 November 2026
Origo10 is Vaisala's modular HVAC transmitter: a duct or wall housing that takes up to two probes (XMP10 humidity/temperature, CO2, temperature) and up to three plug-in modules such as the DIO10 relay/binary-input module. The Origo10A version offers Modbus RTU (or BACnet MS/TP) on RS-485. Each probe or module gets its own 4096-register block; this map lists probe A in full, the main probe B readings, module 1 relay/input, transmitter status, serial settings and test registers.
This page lists 43 Modbus registers for the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
- Equipment type
- Sensor (HVAC humidity, temperature and CO2 transmitter)
- Registers
- 43 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter
- Source document
- Origo10 User Guide · M213293EN-B · rev. 2026-05
Integration notes: Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Read registers 257-260 (wire 256-259) for probe A humidity and temperature as low-word-first floats, add 277 for CO2 if a CO2 probe is fitted, and watch the transmitter status code at 49153.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | Probe A relative humidity | FLOAT32 CDAB | Probe A relative humidity | Read |
| HR 258 | Probe A temperature | FLOAT32 CDAB | Probe A temperature | Read |
| HR 260 | Probe A dew point temperature | FLOAT32 CDAB | Dew point | Read |
| HR 276 | Probe A CO2 concentration (ppm) | FLOAT32 CDAB | CO2 ppm (CO2 probe) | Read |
| HR 48 | Probe A status code | UINT32 CDAB | Probe A status | Read |
| HR 49152 | Transmitter status code low | UINT32 CDAB | Transmitter error/warning bits | Read |
Enable Modbus control & writes
Order Origo10A with the Modbus RTU output option. Serial settings and the Modbus address can be changed in Vaisala Insight PC software over the USB-C service port or through registers 51202-51205.
Byte order & addressing
- Floats are low word first (CDAB); choose a word-swapped float format in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
- Register blocks are per subdevice: add 4096 for probe B and 8192/12288/16384 for modules 1-3.
Network setup
- Defaults: address 240, 19200 baud, no parity, 8 data bits, 1 stop bit, response delay 20 ms.
- Up to 24 transmitters on one RS-485 line, each with a unique address.
- Use the RS-485 termination jumper on the component board at the line ends.
Watch out for
- Origo10L transmitters are analog only.
- Read the test registers 50950-50952 first to confirm addressing and float format.
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Probe A product code | 32-character text. | STRING[32] | Read | ||||
| HR | 16doc 17 | Probe A serial number | STRING[32] | Read | |||||
| HR | 32doc 33 | Probe A version | STRING[32] | Read | |||||
| HR | 48doc 49 | Probe A status code | UINT32 | CDAB | Read | bit 0 = Failure active; bit 1 = Error active; bit 2 = Warning active; bit 3 = Information active; bit 4 = Calibration mode active | |||
| HR | 256doc 257 | Probe A relative humidity | FLOAT32 | CDAB | %RH | Read | |||
| HR | 258doc 259 | Probe A temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 260doc 261 | Probe A dew point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 262doc 263 | Probe A dew/frost point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 264doc 265 | Probe A absolute humidity | FLOAT32 | CDAB | g/m3 | Read | |||
| HR | 266doc 267 | Probe A mixing ratio | FLOAT32 | CDAB | g/kg | Read | |||
| HR | 268doc 269 | Probe A wet-bulb temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 270doc 271 | Probe A water vapor pressure | FLOAT32 | CDAB | hPa | Read | |||
| HR | 272doc 273 | Probe A water vapor saturation pressure | FLOAT32 | CDAB | hPa | Read | |||
| HR | 274doc 275 | Probe A enthalpy | FLOAT32 | CDAB | kJ/kg | Read | |||
| HR | 276doc 277 | Probe A CO2 concentration (ppm) | With a CO2 probe connected. | FLOAT32 | CDAB | ppm | Read | ||
| HR | 278doc 279 | Probe A CO2 concentration (%) | FLOAT32 | CDAB | % | Read | |||
| HR | 512doc 513 | Probe A relative humidity (non-metric block) | FLOAT32 | CDAB | %RH | Read | |||
| HR | 514doc 515 | Probe A temperature (non-metric block) | FLOAT32 | CDAB | °F | Read | |||
| HR | 516doc 517 | Probe A dew point temperature (non-metric block) | FLOAT32 | CDAB | °F | Read | |||
| HR | 530doc 531 | Probe A enthalpy (non-metric block) | FLOAT32 | CDAB | BTU/lb | Read | |||
| HR | 768doc 769 | Probe A RH measurement status | 0 = status OK. | BITMAP16 | Read | bit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready | |||
| HR | 769doc 770 | Probe A T measurement status | BITMAP16 | Read | bit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready | ||||
| HR | 778doc 779 | Probe A CO2 ppm measurement status | BITMAP16 | Read | bit 0 = Measurement not available; bit 1 = Measurement not reliable; bit 2 = Under range; bit 3 = Over range; bit 4 = Noisy; bit 5 = Value locked; bit 6 = Calibration expired; bit 7 = Sensor failure; bit 8 = Measurement not ready | ||||
| HR | 4352doc 4353 | Probe B relative humidity | Same layout as probe A, offset by 4096. | FLOAT32 | CDAB | %RH | Read | ||
| HR | 4354doc 4355 | Probe B temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 4372doc 4373 | Probe B CO2 concentration (ppm) | FLOAT32 | CDAB | ppm | Read | |||
| HR | 8242doc 8243 | Module 1 relay output control | DIO10 module in slot M1. | UINT16 | Read | 0 = Inactive; 1 = Active; 2 = N/A | |||
| HR | 8472doc 8473 | Module 1 binary input | UINT16 | Read | 0 = Loop open; 1 = Loop closed; 2 = N/A | ||||
| HR | 8474doc 8475 | Module 1 relay output | UINT16 | Read | 0 = Inactive; 1 = Active; 2 = N/A | ||||
| HR | 49152doc 49153 | Transmitter status code low | UINT32 | CDAB | Read | bit 0 = Non-volatile memory read/write failure; bit 1 = Device settings corrupted; bit 2 = Factory settings corrupted; bit 4 = Probe current limit exceeded; bit 7 = Probe type not supported; bit 8 = Module type not supported; bit 11 = Probe missing; bit 12 = Module missing; bit 16 = Cannot read all measurement parameters; bit 17 = Analog output 1 out of range; bit 18 = Analog output 2 out of range; bit 19 = Analog output 3 out of range; bit 20 = Analog output 1 test mode active; bit 21 = Analog output 2 test mode active; bit 22 = Analog output 3 test mode active; bit 23 = Analog output 1 calibration active; bit 24 = Analog output 2 calibration active; bit 25 = Analog output 3 calibration active; bit 26 = Supply voltage out of range; bit 27 = Probe 1 not detected; bit 28 = Probe 2 not detected; bit 29 = Module 1 not detected; bit 30 = Module 2 not detected; bit 31 = Module 3 not detected | |||
| HR | 49154doc 49155 | Transmitter status code high | UINT32 | CDAB | Read | bit 0 = Restart to apply settings; bit 1 = Configuration locked; bit 2 = Configuration unlocked | |||
| HR | 49156doc 49157 | Firmware version | STRING[32] | Read | |||||
| HR | 49172doc 49173 | Security hash | INT32 | CDAB | Read | ||||
| HR | 49174doc 49175 | Vendor name | STRING[16] | Read | |||||
| HR | 49206doc 49207 | Product code | STRING[16] | Read | |||||
| HR | 49262doc 49263 | Serial number | STRING[8] | Read | |||||
| HR | 49664doc 49665 | Restart device | Write 1 to restart. | INT16 | Read/write | ||||
| HR | 50949doc 50950 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 50950doc 50951 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read | |||
| HR | 51201doc 51202 | Modbus address | 1-247, default 240. | INT16 | Read/write | ||||
| HR | 51202doc 51203 | Bit rate | UINT16 | Read/write | 0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600; 9 = 76800; 10 = 115200 | ||||
| HR | 51203doc 51204 | Parity, data, stop bits | UINT16 | Read/write | 0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2 | ||||
| HR | 51204doc 51205 | Response delay | 0-1000 ms, default 20. | INT16 | ms | Read/write |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16.
- 32-bit floats and 32-bit integers/bitfields put the least significant word at the listed register (CDAB), as the guide states for both formats.
- Only probe A is listed in full. Probe B uses the same layout plus 4096 (e.g. RH at register 4353), and modules 1-3 add 8192, 12288 and 16384. Registers for parameters the fitted probe cannot measure are unavailable.
- Left out: the 16-bit integer copies of the measurements (897-910 + X*4096). The guide prints a 'scale factor' column (10, and 0.01 for CO2 ppm) but never says whether to multiply or divide the raw value by it, so the floats are listed instead. 0x8000 in an integer register means not available.
- Left out: most non-metric floats except RH, T, dew point and enthalpy, the remaining measurement-status registers (same bit layout), and the long identification strings (vendor URL, product name, manufacturing data).
- Modbus is only available on Origo10A transmitters. The protocol can be changed to BACnet MS/TP in Insight.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
What Modbus registers does the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) have?
This map lists 43 registers: 43 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered in decimal from 1 and the guide also prints the 0-based hex PDU address; register 1 is address 0x0000. Subdevice blocks: register = base + X * 4096, with X = 0 probe A, 1 probe B, 2-4 modules 1-3 (hex address 0xX000 style).
What byte order does the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)?
Start with HR 256 Probe A relative humidity (Probe A relative humidity); HR 258 Probe A temperature (Probe A temperature); HR 260 Probe A dew point temperature (Dew point); HR 276 Probe A CO2 concentration (ppm) (CO2 ppm (CO2 probe)); HR 48 Probe A status code (Probe A status); HR 49152 Transmitter status code low (Transmitter error/warning bits).
How do I enable Modbus control of the Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)?
Order Origo10A with the Modbus RTU output option. Serial settings and the Modbus address can be changed in Vaisala Insight PC software over the USB-C service port or through registers 51202-51205.
Where is the official Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU) Modbus documentation?
The source is Origo10 User Guide (M213293EN-B), revision 2026-05, published free by Vaisala at https://docs.vaisala.com/r/M213293EN-B/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other hvac equipment register maps
- Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus
All hvac equipment Modbus register maps →
Source: Origo10 User Guide · M213293EN-B · rev. 2026-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.