Air handler humidifier (gas-fired steam) · Modbus register map
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus register map
Updated 19 November 2026
The Neptronic SKG4 is a gas-fired steam humidifier built from up to four burner modules. Its Modbus RTU module exposes holding registers only: signal voltages, room and supply RH, per-module chimney, water and ambient temperatures, fan feedback, demand and maximum output, PID and boiler settings, per-module inputs and valve states as 0/1 registers, and module state, request and alarm codes.
This page lists 245 Modbus registers for the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) — 87 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKG4 gas-fired steam humidifier (Modbus communication module)
- Equipment type
- Air handler humidifier (gas-fired steam)
- Registers
- 245 (87 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus
Integration notes: Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Read Room RH (6005), Humidity Demand (6054), System Power Output (6055) and each module's State and Alarm (15015-15026). For BAS control set Control Profile (15004) and Demand Source (15011) to network options and write Humidity Control Network Demand (6052) within the Network Timeout.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6005 | Room RH | UINT16 | Room RH | Read |
| HR 6039 | Room RH Setpoint | UINT16 | Room RH set point | Read/write |
| HR 6054 | Humidity Demand | UINT16 | Humidity demand | Read |
| HR 6055 | System Power Output | UINT16 | System power output | Read |
| HR 15015 | Module 1 State | UINT16 | Module 1 state | Read |
| HR 15017 | Module 1 Alarm | UINT16 | Module 1 alarm | Read |
| HR 15014 | System Power State | UINT16 | System on/off | Read/write |
| HR 6052 | Humidity Control Network Demand | UINT16 | Network demand | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.
Communication loss & watchdog
Network Timeout (6158, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12051) shows a fault.
Byte order & addressing
- All points, binary ones included, are holding registers (FC03/06/16 only).
- Default framing is no parity with 2 stop bits.
Network setup
- RS-485 two-wire, RTU; 9600-57600 baud or auto baud detection.
- Parity/stop bits via register 2 or the Modbus Comport Config menu item.
Watch out for
- Module 2-4 registers only respond meaningfully on units with that many burner modules.
- System Mode (15034) chooses parallel, sequential or hybrid staging of modules.
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud rate / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Supply RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2001doc 2001 / 402002 | Room RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Control Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2003doc 2003 / 402004 | Board Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2004doc 2004 / 402005 | Main Power Supply | UINT16 | × 0.1 | V | Read | |||
| HR | 4000doc 4000 / 404001 | Power Output Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 6000doc 6000 / 406001 | Water Level Replace Interval | UINT16 | days | Read/write | ||||
| HR | 6001doc 6001 / 406002 | Supply High Limit RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6002doc 6002 / 406003 | Supply High Limit RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6003doc 6003 / 406004 | Supply High Limit RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6004doc 6004 / 406005 | Supply High Limit RH Bias | INT16 | × 0.01 | %RH | Read/write | |||
| HR | 6005doc 6005 / 406006 | Room RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6006doc 6006 / 406007 | Room RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6007doc 6007 / 406008 | Room RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6009doc 6009 / 406010 | Control Input | UINT16 | × 0.01 | % | Read | |||
| HR | 6010doc 6010 / 406011 | Control Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6011doc 6011 / 406012 | Control Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6012doc 6012 / 406013 | Control Bias | INT16 | × 0.01 | %RH | Read/write | |||
| HR | 6013doc 6013 / 406014 | Board Temperature | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6014doc 6014 / 406015 | Power Output Feedback Bias | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6015doc 6015 / 406016 | Power Output Feedback Min | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6016doc 6016 / 406017 | Power Output Feedback Max | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6017doc 6017 / 406018 | Power Output Feedback | UINT16 | × 0.01 | % | Read | |||
| HR | 6019doc 6019 / 406020 | Module 1 Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6020doc 6020 / 406021 | Module 1 Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6021doc 6021 / 406022 | Module 1 Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6022doc 6022 / 406023 | Module 1 Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6024doc 6024 / 406025 | Module 2 Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6025doc 6025 / 406026 | Module 2 Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6026doc 6026 / 406027 | Module 2 Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6027doc 6027 / 406028 | Module 2 Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6029doc 6029 / 406030 | Module 3 Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6030doc 6030 / 406031 | Module 3 Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6031doc 6031 / 406032 | Module 3 Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6032doc 6032 / 406033 | Module 3 Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6034doc 6034 / 406035 | Module 4 Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6035doc 6035 / 406036 | Module 4 Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6036doc 6036 / 406037 | Module 4 Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6037doc 6037 / 406038 | Module 4 Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6038doc 6038 / 406039 | Room RH Network Reading | Room RH written by the BAS when Room RH Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6039doc 6039 / 406040 | Room RH Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6040doc 6040 / 406041 | Room RH Unoccupied Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6041doc 6041 / 406042 | Room RH Vacant Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6042doc 6042 / 406043 | Room Demand Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6043doc 6043 / 406044 | Room Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6044doc 6044 / 406045 | Room Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6045doc 6045 / 406046 | Room Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6046doc 6046 / 406047 | Supply High Limit Network Reading | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6047doc 6047 / 406048 | Supply High Limit Setpoint | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6048doc 6048 / 406049 | Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6049doc 6049 / 406050 | Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6050doc 6050 / 406051 | Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6051doc 6051 / 406052 | Supply High Limit Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6052doc 6052 / 406053 | Humidity Control Network Demand | Demand written by the BAS when Demand Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6053doc 6053 / 406054 | Humidity Control Network High Limit | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6054doc 6054 / 406055 | Humidity Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6055doc 6055 / 406056 | System Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6056doc 6056 / 406057 | System Steam Capacity | UINT16 | × 0.1 | kg/h / lb/h | Read | |||
| HR | 6057doc 6057 / 406058 | Module 1 Chimney Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6058doc 6058 / 406059 | Module 1 Water Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6059doc 6059 / 406060 | Module 1 Water Frequency | UINT16 | Hz | Read | ||||
| HR | 6060doc 6060 / 406061 | Module 1 Ambient Temp | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6061doc 6061 / 406062 | Module 1 Fan Feedback | UINT16 | Hz | Read | ||||
| HR | 6062doc 6062 / 406063 | Module 1 Fan PWM | UINT16 | × 0.01 | % | Read | |||
| HR | 6079doc 6079 / 406080 | Module 1 Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6080doc 6080 / 406081 | Module 1 Max Steam Output | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6081doc 6081 / 406082 | Module 2 Chimney Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6082doc 6082 / 406083 | Module 2 Water Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6083doc 6083 / 406084 | Module 2 Water Frequency | UINT16 | Hz | Read | ||||
| HR | 6084doc 6084 / 406085 | Module 2 Ambient Temp | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6085doc 6085 / 406086 | Module 2 Fan Feedback | UINT16 | Hz | Read | ||||
| HR | 6086doc 6086 / 406087 | Module 2 Fan PWM | UINT16 | × 0.01 | % | Read | |||
| HR | 6103doc 6103 / 406104 | Module 2 Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6104doc 6104 / 406105 | Module 2 Max Steam Output | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6105doc 6105 / 406106 | Module 3 Chimney Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6106doc 6106 / 406107 | Module 3 Water Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6107doc 6107 / 406108 | Module 3 Water Frequency | UINT16 | Hz | Read | ||||
| HR | 6108doc 6108 / 406109 | Module 3 Ambient Temp | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6109doc 6109 / 406110 | Module 3 Fan Feedback | UINT16 | Hz | Read | ||||
| HR | 6110doc 6110 / 406111 | Module 3 Fan PWM | UINT16 | × 0.01 | % | Read | |||
| HR | 6127doc 6127 / 406128 | Module 3 Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6128doc 6128 / 406129 | Module 3 Max Steam Output | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6129doc 6129 / 406130 | Module 4 Chimney Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6130doc 6130 / 406131 | Module 4 Water Temp | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6131doc 6131 / 406132 | Module 4 Water Frequency | UINT16 | Hz | Read | ||||
| HR | 6132doc 6132 / 406133 | Module 4 Ambient Temp | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6133doc 6133 / 406134 | Module 4 Fan Feedback | UINT16 | Hz | Read | ||||
| HR | 6134doc 6134 / 406135 | Module 4 Fan PWM | UINT16 | × 0.01 | % | Read | |||
| HR | 6151doc 6151 / 406152 | Module 4 Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6152doc 6152 / 406153 | Module 4 Max Steam Output | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6153doc 6153 / 406154 | Boiler Blowdown Rate | UINT16 | % | Read/write | ||||
| HR | 6154doc 6154 / 406155 | Boiler Drain Interval | UINT16 | h | Read/write | ||||
| HR | 6156doc 6156 / 406157 | Boiler Idle Time Drain | UINT16 | h | Read/write | ||||
| HR | 6157doc 6157 / 406158 | Boiler Service Interval | UINT16 | h | Read/write | ||||
| HR | 6158doc 6158 / 406159 | Network Timeout | Time allowed between network writes before a network fault. | UINT16 | s | Read/write | |||
| HR | 6159doc 6159 / 406160 | Boiler Idle Tank Rinse Interval | UINT16 | days | Read/write | ||||
| HR | 6160doc 6160 / 406161 | Boiler Minimum Steam Output | UINT16 | % | Read/write | ||||
| HR | 6161doc 6161 / 406162 | Boiler Drain Volume | UINT16 | % | Read/write | ||||
| HR | 6180doc 6180 / 406181 | HRL Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6181doc 6181 / 406182 | HRL Humidity | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6182doc 6182 / 406183 | Room Demand Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6183doc 6183 / 406184 | Supply High Limit Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6184doc 6184 / 406185 | Modbus TCP IP Keep Alive Time Out | UINT16 | min | Read/write | ||||
| HR | 6201doc 6201 / 406202 | HRL Temperature Bas | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6202doc 6202 / 406203 | HRL Humidity Bias | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 10000doc 10000 / 410001 | Water Leak Detection | UINT16 | Read | 0 = Ok; 1 = Leak | ||||
| HR | 10001doc 10001 / 410002 | Binary External Demand | UINT16 | Read | 0 = 0%; 1 = 100% | ||||
| HR | 10002doc 10002 / 410003 | Interlock | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10003doc 10003 / 410004 | Supply High Limit | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10004doc 10004 / 410005 | Air Flow | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10005doc 10005 / 410006 | RS485 Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10006doc 10006 / 410007 | Ethernet Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 11000doc 11000 / 411001 | Service Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Alarm Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11002doc 11002 / 411003 | Alarm LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11003doc 11003 / 411004 | Power LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Buzzer | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12000doc 12000 / 412001 | Module 1 Burner Inlet Pressure | UINT16 | Read | 0 = Normal; 1 = Blocked | ||||
| HR | 12001doc 12001 / 412002 | Module 1 Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12002doc 12002 / 412003 | Module 1 Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12003doc 12003 / 412004 | Module 1 Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12004doc 12004 / 412005 | Module 1 Gas Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12005doc 12005 / 412006 | Module 1 Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12006doc 12006 / 412007 | Module 1 Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12007doc 12007 / 412008 | Module 1 Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12008doc 12008 / 412009 | Module 1 Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12009doc 12009 / 412010 | Module 1 Ignition Control | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12010doc 12010 / 412011 | Module 1 AlarmLED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12011doc 12011 / 412012 | Module 2 Burner Inlet Pressure | UINT16 | Read | 0 = Normal; 1 = Blocked | ||||
| HR | 12012doc 12012 / 412013 | Module 2 Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12013doc 12013 / 412014 | Module 2 Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12014doc 12014 / 412015 | Module 2 Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12015doc 12015 / 412016 | Module 2 Gas Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12016doc 12016 / 412017 | Module 2 Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12017doc 12017 / 412018 | Module 2 Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12018doc 12018 / 412019 | Module 2 Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12019doc 12019 / 412020 | Module 2 Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12020doc 12020 / 412021 | Boiler Line Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12021doc 12021 / 412022 | Module 2 Ignition Control | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12022doc 12022 / 412023 | Module 2 AlarmLED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12023doc 12023 / 412024 | Module 3 Burner Inlet Pressure | UINT16 | Read | 0 = Normal; 1 = Blocked | ||||
| HR | 12024doc 12024 / 412025 | Module 3 Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12025doc 12025 / 412026 | Module 3 Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12026doc 12026 / 412027 | Module 3 Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12027doc 12027 / 412028 | Module 3 Gas Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12028doc 12028 / 412029 | Module 3 Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12029doc 12029 / 412030 | Module 3 Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12030doc 12030 / 412031 | Module 3 Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12031doc 12031 / 412032 | Module 3 Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12032doc 12032 / 412033 | Module 3 Ignition Control | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12033doc 12033 / 412034 | Module 3 AlarmLED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12034doc 12034 / 412035 | Module 4 Burner Inlet Pressure | UINT16 | Read | 0 = Normal; 1 = Blocked | ||||
| HR | 12035doc 12035 / 412036 | Module 4 Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12036doc 12036 / 412037 | Module 4 Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12037doc 12037 / 412038 | Module 4 Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12038doc 12038 / 412039 | Module 4 Gas Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12039doc 12039 / 412040 | Module 4 Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12040doc 12040 / 412041 | Module 4 Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12041doc 12041 / 412042 | Module 4 Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12042doc 12042 / 412043 | Module 4 Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12043doc 12043 / 412044 | Module 4 Ignition Control | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12044doc 12044 / 412045 | Module 4 AlarmLED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12045doc 12045 / 412046 | Boiler Service Operation | UINT16 | Read/write | 0 = NotAllowed; 1 = Allowed | ||||
| HR | 12046doc 12046 / 412047 | Module 1 Foam State | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12047doc 12047 / 412048 | Module 1 Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12048doc 12048 / 412049 | Module 2 Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12049doc 12049 / 412050 | Module 3 Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12050doc 12050 / 412051 | Module 4 Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12051doc 12051 / 412052 | Network Control State | UINT16 | Read/write | 0 = Normal; 1 = Fault | ||||
| HR | 12052doc 12052 / 412053 | Module 2 Foam State | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12053doc 12053 / 412054 | Module 3 Foam State | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12054doc 12054 / 412055 | Module 4 Foam State | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12055doc 12055 / 412056 | HRL Lock Setpoint | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 12056doc 12056 / 412057 | Module 1 Drain Valve | UINT16 | Read | 0 = On; 1 = Off | ||||
| HR | 12057doc 12057 / 412058 | Module 2 Drain Valve | UINT16 | Read | 0 = On; 1 = Off | ||||
| HR | 12058doc 12058 / 412059 | Module 3 Drain Valve | UINT16 | Read | 0 = On; 1 = Off | ||||
| HR | 12059doc 12059 / 412060 | Module 4 Drain Valve | UINT16 | Read | 0 = On; 1 = Off | ||||
| HR | 12060doc 12060 / 412061 | Inhibit Resistive Probe 1 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12061doc 12061 / 412062 | Inhibit Resistive Probe 2 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12062doc 12062 / 412063 | Inhibit Resistive Probe 3 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12063doc 12063 / 412064 | Inhibit Resistive Probe 4 | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12064doc 12064 / 412065 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12065doc 12065 / 412066 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12066doc 12066 / 412067 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12067doc 12067 / 412068 | Module 1 Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12068doc 12068 / 412069 | Module 2 Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12069doc 12069 / 412070 | Module 3 Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12070doc 12070 / 412071 | Module 4 Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12071doc 12071 / 412072 | Module 1 AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 12072doc 12072 / 412073 | Module 2 AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 12073doc 12073 / 412074 | Module 3 AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 12074doc 12074 / 412075 | Module 4 AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 15000doc 15000 / 415001 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15001doc 15001 / 415002 | Supply RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15002doc 15002 / 415003 | Room RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15003doc 15003 / 415004 | Control Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15004doc 15004 / 415005 | Control Profile | UINT16 | Read/write | 0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom | ||||
| HR | 15005doc 15005 / 415006 | Modulating High Limit Profile | UINT16 | Read/write | 0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom | ||||
| HR | 15006doc 15006 / 415007 | Occupancy State | UINT16 | Read | 0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off | ||||
| HR | 15007doc 15007 / 415008 | Room RH Source | UINT16 | Read/write | 0 = None; 1 = RoomRH; 2 = Network; 3 = HRL | ||||
| HR | 15008doc 15008 / 415009 | Room RH Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15009doc 15009 / 415010 | Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = Supply HLRH; 2 = Network | ||||
| HR | 15010doc 15010 / 415011 | Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15011doc 15011 / 415012 | Humidity Control Demand Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network | ||||
| HR | 15012doc 15012 / 415013 | Humidity Control High Limit Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network | ||||
| HR | 15013doc 15013 / 415014 | Humidity Control Cutout State | UINT16 | Read | 0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = AirFlow; 5 = Interlock | ||||
| HR | 15014doc 15014 / 415015 | System Power State | Humidifier on/off. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 15015doc 15015 / 415016 | Module 1 State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir | ||||
| HR | 15016doc 15016 / 415017 | Module 1 Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir | ||||
| HR | 15017doc 15017 / 415018 | Module 1 Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay | ||||
| HR | 15018doc 15018 / 415019 | Module 2 State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir | ||||
| HR | 15019doc 15019 / 415020 | Module 2 Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir | ||||
| HR | 15020doc 15020 / 415021 | Module 2 Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay | ||||
| HR | 15021doc 15021 / 415022 | Module 3 State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir | ||||
| HR | 15022doc 15022 / 415023 | Module 3 Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir | ||||
| HR | 15023doc 15023 / 415024 | Module 3 Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay | ||||
| HR | 15024doc 15024 / 415025 | Module 4 State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir | ||||
| HR | 15025doc 15025 / 415026 | Module 4 Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir | ||||
| HR | 15026doc 15026 / 415027 | Module 4 Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay | ||||
| HR | 15027doc 15027 / 415028 | Boiler Fill Mode | UINT16 | Read/write | 0 = OneShot; 1 = Pulsed | ||||
| HR | 15028doc 15028 / 415029 | Boiler Idle Tank Rinse Off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15029doc 15029 / 415030 | Boiler Idle Tank Rinse On | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15030doc 15030 / 415031 | Water Probe 1 Auto Calib | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15031doc 15031 / 415032 | Water Probe 2 Auto Calib | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15032doc 15032 / 415033 | Water Probe 3 Auto Calib | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15033doc 15033 / 415034 | Water Probe 4 Auto Calib | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15034doc 15034 / 415035 | System Mode | UINT16 | Read/write | 0 = Parallel; 1 = Sequential; 2 = Hybrid | ||||
| HR | 15035doc 15035 / 415036 | Boiler Startup Tank Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15036doc 15036 / 415037 | Module 1 Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15037doc 15037 / 415038 | Module 2 Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15038doc 15038 / 415039 | Module 3 Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15039doc 15039 / 415040 | Module 4 Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15040doc 15040 / 415041 | Water Level 1 Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15041doc 15041 / 415042 | Water Level 2 Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15042doc 15042 / 415043 | Water Level 3 Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15043doc 15043 / 415044 | Water Level 4 Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15044doc 15044 / 415045 | Module 1 Water Level Probe Alarm | UINT16 | Read | 0 = Ok; 1 = Defect; 2 = NoCalib | ||||
| HR | 15045doc 15045 / 415046 | Module 2 Water Level Probe Alarm | UINT16 | Read | 0 = Ok; 1 = Defect; 2 = NoCalib | ||||
| HR | 15046doc 15046 / 415047 | Module 3 Water Level Probe Alarm | UINT16 | Read | 0 = Ok; 1 = Defect; 2 = NoCalib | ||||
| HR | 15047doc 15047 / 415048 | Module 4 Water Level Probe Alarm | UINT16 | Read | 0 = Ok; 1 = Defect; 2 = NoCalib |
Notes on this map
- Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.
- 'Scale N' with 'Value x N' means the raw value is the engineering value times N; this map stores the multiplier 1/N.
- Temperature and capacity units follow Modbus Server Units (415001): 0 metric, 1 imperial.
- The guide text calls automatic baud detection the default, while register 1 lists 19200 as its default value; the baud default is left blank here.
- Default unit address is not stated; it is set from the device menu or register 0.
- Left out: product name ASCII registers 3-6; Room RH Bias 6008 (a bias printed with a 0-100 % range and 100 % default); module water levels 6018/6023/6028/6033 (Scale 10 but 'Value x 100' example); Boiler Idle Temperature Setpoint 6155 (scale and example disagree); Humidity Demand Low Dead Band 6162-6163 and the ignition counters 6164-6179, and all run/on/service time and calibration counters, which span two or four registers with no stated word order.
- Module 1-4 Drain Valve (12056-12059) are printed with 0 = On, 1 = Off, the reverse of the other valve points; copied as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
What Modbus registers does the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) have?
This map lists 245 registers: 245 holding registers. 87 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)?
Start with HR 6005 Room RH (Room RH); HR 6039 Room RH Setpoint (Room RH set point); HR 6054 Humidity Demand (Humidity demand); HR 6055 System Power Output (System power output); HR 15015 Module 1 State (Module 1 state); HR 15017 Module 1 Alarm (Module 1 alarm); HR 15014 System Power State (System on/off); HR 6052 Humidity Control Network Demand (Network demand).
How do I enable Modbus control of the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)?
Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.
What happens when the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) loses Modbus communication?
Network Timeout (6158, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12051) shows a fault.
Where is the official Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus documentation?
The source is SKG4 Gas Fired Humidifier - Modbus Communication Module User Guide (SKG4-Modbus Guide-221114 (V2.04)), revision 2022-11-14, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKG4/20230526/SKG4-Modbus%20Guide-221114%20(V2.04).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Thermostat / temperature controller
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Watlow EZ-ZONE PM panel-mount controllers (PID, limit and integrated models) with Modbus RTU, per communications manual 0600-0056-0000 Rev. B (Nov 2007).
Also known as: EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated - Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
DriSteem humidifiers and humidification systems controlled by Vapor-logic firmware 6.X.X, per IOM form VL6-IOM-EN-REVH-0225.
Also known as: Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523
All hvac equipment Modbus register maps →
Source: SKG4 Gas Fired Humidifier - Modbus Communication Module User Guide · SKG4-Modbus Guide-221114 (V2.04) · rev. 2022-11-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.