Air handler humidifier (gas-fired steam) · Modbus register map

Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The Neptronic SKG4 is a gas-fired steam humidifier built from up to four burner modules. Its Modbus RTU module exposes holding registers only: signal voltages, room and supply RH, per-module chimney, water and ambient temperatures, fan feedback, demand and maximum output, PID and boiler settings, per-module inputs and valve states as 0/1 registers, and module state, request and alarm codes.

This page lists 245 Modbus registers for the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) — 87 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKG4 gas-fired steam humidifier (Modbus communication module)
Equipment type
Air handler humidifier (gas-fired steam)
Registers
245 (87 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus
Source document
SKG4 Gas Fired Humidifier - Modbus Communication Module User Guide · SKG4-Modbus Guide-221114 (V2.04) · rev. 2022-11-14
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)

Integration in brief

Read Room RH (6005), Humidity Demand (6054), System Power Output (6055) and each module's State and Alarm (15015-15026). For BAS control set Control Profile (15004) and Demand Source (15011) to network options and write Humidity Control Network Demand (6052) within the Network Timeout.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6005Room RHUINT16Room RHRead
HR 6039Room RH SetpointUINT16Room RH set pointRead/write
HR 6054Humidity DemandUINT16Humidity demandRead
HR 6055System Power OutputUINT16System power outputRead
HR 15015Module 1 StateUINT16Module 1 stateRead
HR 15017Module 1 AlarmUINT16Module 1 alarmRead
HR 15014System Power StateUINT16System on/offRead/write
HR 6052Humidity Control Network DemandUINT16Network demandRead/write

Enable Modbus control & writes

Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.

Communication loss & watchdog

Network Timeout (6158, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12051) shows a fault.

Byte order & addressing

Network setup

Watch out for

Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

245 of 245 shown
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud rate / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Supply RH SignalUINT16× 0.001VRead
HR2001doc 2001 / 402002Room RH SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Control SignalUINT16× 0.001VRead
HR2003doc 2003 / 402004Board Temperature SignalUINT16× 0.001VRead
HR2004doc 2004 / 402005Main Power SupplyUINT16× 0.1VRead
HR4000doc 4000 / 404001Power Output Feedback SignalUINT16× 0.001VRead
HR6000doc 6000 / 406001Water Level Replace IntervalUINT16daysRead/write
HR6001doc 6001 / 406002Supply High Limit RHUINT16× 0.01%RHRead
HR6002doc 6002 / 406003Supply High Limit RH MinUINT16× 0.01%RHRead/write
HR6003doc 6003 / 406004Supply High Limit RH MaxUINT16× 0.01%RHRead/write
HR6004doc 6004 / 406005Supply High Limit RH BiasINT16× 0.01%RHRead/write
HR6005doc 6005 / 406006Room RHUINT16× 0.01%RHRead
HR6006doc 6006 / 406007Room RH MinUINT16× 0.01%RHRead/write
HR6007doc 6007 / 406008Room RH MaxUINT16× 0.01%RHRead/write
HR6009doc 6009 / 406010Control InputUINT16× 0.01%Read
HR6010doc 6010 / 406011Control MinUINT16× 0.01%Read/write
HR6011doc 6011 / 406012Control MaxUINT16× 0.01%Read/write
HR6012doc 6012 / 406013Control BiasINT16× 0.01%RHRead/write
HR6013doc 6013 / 406014Board TemperatureUINT16× 0.01°C / °FRead
HR6014doc 6014 / 406015Power Output Feedback BiasUINT16× 0.001VRead/write
HR6015doc 6015 / 406016Power Output Feedback MinUINT16× 0.001VRead/write
HR6016doc 6016 / 406017Power Output Feedback MaxUINT16× 0.001VRead/write
HR6017doc 6017 / 406018Power Output FeedbackUINT16× 0.01%Read
HR6019doc 6019 / 406020Module 1 Water Probe Low Pos ReadingUINT16HzRead
HR6020doc 6020 / 406021Module 1 Water Probe High Pos ReadingUINT16HzRead
HR6021doc 6021 / 406022Module 1 Water Probe Abs Low Pos ReadingUINT16HzRead
HR6022doc 6022 / 406023Module 1 Water Probe Abs High Pos ReadingUINT16HzRead
HR6024doc 6024 / 406025Module 2 Water Probe Low Pos ReadingUINT16HzRead
HR6025doc 6025 / 406026Module 2 Water Probe High Pos ReadingUINT16HzRead
HR6026doc 6026 / 406027Module 2 Water Probe Abs Low Pos ReadingUINT16HzRead
HR6027doc 6027 / 406028Module 2 Water Probe Abs High Pos ReadingUINT16HzRead
HR6029doc 6029 / 406030Module 3 Water Probe Low Pos ReadingUINT16HzRead
HR6030doc 6030 / 406031Module 3 Water Probe High Pos ReadingUINT16HzRead
HR6031doc 6031 / 406032Module 3 Water Probe Abs Low Pos ReadingUINT16HzRead
HR6032doc 6032 / 406033Module 3 Water Probe Abs High Pos ReadingUINT16HzRead
HR6034doc 6034 / 406035Module 4 Water Probe Low Pos ReadingUINT16HzRead
HR6035doc 6035 / 406036Module 4 Water Probe High Pos ReadingUINT16HzRead
HR6036doc 6036 / 406037Module 4 Water Probe Abs Low Pos ReadingUINT16HzRead
HR6037doc 6037 / 406038Module 4 Water Probe Abs High Pos ReadingUINT16HzRead
HR6038doc 6038 / 406039Room RH Network ReadingRoom RH written by the BAS when Room RH Source = Network.UINT16× 0.01%RHRead/write
HR6039doc 6039 / 406040Room RH SetpointUINT16× 0.01%RHRead/write
HR6040doc 6040 / 406041Room RH Unoccupied SetpointUINT16× 0.01%RHRead/write
HR6041doc 6041 / 406042Room RH Vacant SetpointUINT16× 0.01%RHRead/write
HR6042doc 6042 / 406043Room Demand Proportional GainUINT16× 0.1Read/write
HR6043doc 6043 / 406044Room Demand Integral TimeUINT16× 0.1sRead/write
HR6044doc 6044 / 406045Room Demand Derivative TimeUINT16× 0.1sRead/write
HR6045doc 6045 / 406046Room DemandUINT16× 0.01%RHRead
HR6046doc 6046 / 406047Supply High Limit Network ReadingUINT16× 0.01%RHRead/write
HR6047doc 6047 / 406048Supply High Limit SetpointUINT16× 0.01%Read/write
HR6048doc 6048 / 406049Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6049doc 6049 / 406050Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6050doc 6050 / 406051Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6051doc 6051 / 406052Supply High Limit DemandUINT16× 0.01%RHRead
HR6052doc 6052 / 406053Humidity Control Network DemandDemand written by the BAS when Demand Source = Network.UINT16× 0.01%RHRead/write
HR6053doc 6053 / 406054Humidity Control Network High LimitUINT16× 0.01%RHRead/write
HR6054doc 6054 / 406055Humidity DemandUINT16× 0.01%RHRead
HR6055doc 6055 / 406056System Power OutputUINT16× 0.01%Read
HR6056doc 6056 / 406057System Steam CapacityUINT16× 0.1kg/h / lb/hRead
HR6057doc 6057 / 406058Module 1 Chimney TempUINT16× 0.01°C / °FRead
HR6058doc 6058 / 406059Module 1 Water TempUINT16× 0.01°C / °FRead
HR6059doc 6059 / 406060Module 1 Water FrequencyUINT16HzRead
HR6060doc 6060 / 406061Module 1 Ambient TempINT16× 0.01°C / °FRead
HR6061doc 6061 / 406062Module 1 Fan FeedbackUINT16HzRead
HR6062doc 6062 / 406063Module 1 Fan PWMUINT16× 0.01%Read
HR6079doc 6079 / 406080Module 1 DemandUINT16× 0.01%Read/write
HR6080doc 6080 / 406081Module 1 Max Steam OutputUINT16× 0.01%Read/write
HR6081doc 6081 / 406082Module 2 Chimney TempUINT16× 0.01°C / °FRead
HR6082doc 6082 / 406083Module 2 Water TempUINT16× 0.01°C / °FRead
HR6083doc 6083 / 406084Module 2 Water FrequencyUINT16HzRead
HR6084doc 6084 / 406085Module 2 Ambient TempINT16× 0.01°C / °FRead
HR6085doc 6085 / 406086Module 2 Fan FeedbackUINT16HzRead
HR6086doc 6086 / 406087Module 2 Fan PWMUINT16× 0.01%Read
HR6103doc 6103 / 406104Module 2 DemandUINT16× 0.01%Read/write
HR6104doc 6104 / 406105Module 2 Max Steam OutputUINT16× 0.01%Read/write
HR6105doc 6105 / 406106Module 3 Chimney TempUINT16× 0.01°C / °FRead
HR6106doc 6106 / 406107Module 3 Water TempUINT16× 0.01°C / °FRead
HR6107doc 6107 / 406108Module 3 Water FrequencyUINT16HzRead
HR6108doc 6108 / 406109Module 3 Ambient TempINT16× 0.01°C / °FRead
HR6109doc 6109 / 406110Module 3 Fan FeedbackUINT16HzRead
HR6110doc 6110 / 406111Module 3 Fan PWMUINT16× 0.01%Read
HR6127doc 6127 / 406128Module 3 DemandUINT16× 0.01%Read/write
HR6128doc 6128 / 406129Module 3 Max Steam OutputUINT16× 0.01%Read/write
HR6129doc 6129 / 406130Module 4 Chimney TempUINT16× 0.01°C / °FRead
HR6130doc 6130 / 406131Module 4 Water TempUINT16× 0.01°C / °FRead
HR6131doc 6131 / 406132Module 4 Water FrequencyUINT16HzRead
HR6132doc 6132 / 406133Module 4 Ambient TempINT16× 0.01°C / °FRead
HR6133doc 6133 / 406134Module 4 Fan FeedbackUINT16HzRead
HR6134doc 6134 / 406135Module 4 Fan PWMUINT16× 0.01%Read
HR6151doc 6151 / 406152Module 4 DemandUINT16× 0.01%Read/write
HR6152doc 6152 / 406153Module 4 Max Steam OutputUINT16× 0.01%Read/write
HR6153doc 6153 / 406154Boiler Blowdown RateUINT16%Read/write
HR6154doc 6154 / 406155Boiler Drain IntervalUINT16hRead/write
HR6156doc 6156 / 406157Boiler Idle Time DrainUINT16hRead/write
HR6157doc 6157 / 406158Boiler Service IntervalUINT16hRead/write
HR6158doc 6158 / 406159Network TimeoutTime allowed between network writes before a network fault.UINT16sRead/write
HR6159doc 6159 / 406160Boiler Idle Tank Rinse IntervalUINT16daysRead/write
HR6160doc 6160 / 406161Boiler Minimum Steam OutputUINT16%Read/write
HR6161doc 6161 / 406162Boiler Drain VolumeUINT16%Read/write
HR6180doc 6180 / 406181HRL TemperatureINT16× 0.01°C / °FRead
HR6181doc 6181 / 406182HRL HumidityUINT16× 0.01%RHRead
HR6182doc 6182 / 406183Room Demand Proportional BandUINT16× 0.1%Read/write
HR6183doc 6183 / 406184Supply High Limit Proportional BandUINT16× 0.1%Read/write
HR6184doc 6184 / 406185Modbus TCP IP Keep Alive Time OutUINT16minRead/write
HR6201doc 6201 / 406202HRL Temperature BasINT16× 0.1°C / °FRead/write
HR6202doc 6202 / 406203HRL Humidity BiasINT16× 0.1%RHRead/write
HR10000doc 10000 / 410001Water Leak DetectionUINT16Read0 = Ok; 1 = Leak
HR10001doc 10001 / 410002Binary External DemandUINT16Read0 = 0%; 1 = 100%
HR10002doc 10002 / 410003InterlockUINT16Read0 = Closed; 1 = Open
HR10003doc 10003 / 410004Supply High LimitUINT16Read0 = Closed; 1 = Open
HR10004doc 10004 / 410005Air FlowUINT16Read0 = Closed; 1 = Open
HR10005doc 10005 / 410006RS485 InterfaceUINT16Read0 = No; 1 = Yes
HR10006doc 10006 / 410007Ethernet InterfaceUINT16Read0 = No; 1 = Yes
HR11000doc 11000 / 411001Service Warning RelayUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Alarm Warning RelayUINT16Read0 = Off; 1 = On
HR11002doc 11002 / 411003Alarm LEDUINT16Read0 = Off; 1 = On
HR11003doc 11003 / 411004Power LEDUINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005BuzzerUINT16Read0 = Off; 1 = On
HR12000doc 12000 / 412001Module 1 Burner Inlet PressureUINT16Read0 = Normal; 1 = Blocked
HR12001doc 12001 / 412002Module 1 Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12002doc 12002 / 412003Module 1 Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12003doc 12003 / 412004Module 1 Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12004doc 12004 / 412005Module 1 Gas ValveUINT16Read0 = Off; 1 = On
HR12005doc 12005 / 412006Module 1 Tank Water ValveUINT16Read0 = Off; 1 = On
HR12006doc 12006 / 412007Module 1 Water Level ValveUINT16Read0 = Off; 1 = On
HR12007doc 12007 / 412008Module 1 Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR12008doc 12008 / 412009Module 1 Drain PumpUINT16Read0 = Off; 1 = On
HR12009doc 12009 / 412010Module 1 Ignition ControlUINT16Read0 = Off; 1 = On
HR12010doc 12010 / 412011Module 1 AlarmLEDUINT16Read0 = Off; 1 = On
HR12011doc 12011 / 412012Module 2 Burner Inlet PressureUINT16Read0 = Normal; 1 = Blocked
HR12012doc 12012 / 412013Module 2 Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12013doc 12013 / 412014Module 2 Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12014doc 12014 / 412015Module 2 Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12015doc 12015 / 412016Module 2 Gas ValveUINT16Read0 = Off; 1 = On
HR12016doc 12016 / 412017Module 2 Tank Water ValveUINT16Read0 = Off; 1 = On
HR12017doc 12017 / 412018Module 2 Water Level ValveUINT16Read0 = Off; 1 = On
HR12018doc 12018 / 412019Module 2 Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR12019doc 12019 / 412020Module 2 Drain PumpUINT16Read0 = Off; 1 = On
HR12020doc 12020 / 412021Boiler Line RinseUINT16Read/write0 = Off; 1 = On
HR12021doc 12021 / 412022Module 2 Ignition ControlUINT16Read0 = Off; 1 = On
HR12022doc 12022 / 412023Module 2 AlarmLEDUINT16Read0 = Off; 1 = On
HR12023doc 12023 / 412024Module 3 Burner Inlet PressureUINT16Read0 = Normal; 1 = Blocked
HR12024doc 12024 / 412025Module 3 Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12025doc 12025 / 412026Module 3 Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12026doc 12026 / 412027Module 3 Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12027doc 12027 / 412028Module 3 Gas ValveUINT16Read0 = Off; 1 = On
HR12028doc 12028 / 412029Module 3 Tank Water ValveUINT16Read0 = Off; 1 = On
HR12029doc 12029 / 412030Module 3 Water Level ValveUINT16Read0 = Off; 1 = On
HR12030doc 12030 / 412031Module 3 Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR12031doc 12031 / 412032Module 3 Drain PumpUINT16Read0 = Off; 1 = On
HR12032doc 12032 / 412033Module 3 Ignition ControlUINT16Read0 = Off; 1 = On
HR12033doc 12033 / 412034Module 3 AlarmLEDUINT16Read0 = Off; 1 = On
HR12034doc 12034 / 412035Module 4 Burner Inlet PressureUINT16Read0 = Normal; 1 = Blocked
HR12035doc 12035 / 412036Module 4 Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12036doc 12036 / 412037Module 4 Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12037doc 12037 / 412038Module 4 Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12038doc 12038 / 412039Module 4 Gas ValveUINT16Read0 = Off; 1 = On
HR12039doc 12039 / 412040Module 4 Tank Water ValveUINT16Read0 = Off; 1 = On
HR12040doc 12040 / 412041Module 4 Water Level ValveUINT16Read0 = Off; 1 = On
HR12041doc 12041 / 412042Module 4 Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR12042doc 12042 / 412043Module 4 Drain PumpUINT16Read0 = Off; 1 = On
HR12043doc 12043 / 412044Module 4 Ignition ControlUINT16Read0 = Off; 1 = On
HR12044doc 12044 / 412045Module 4 AlarmLEDUINT16Read0 = Off; 1 = On
HR12045doc 12045 / 412046Boiler Service OperationUINT16Read/write0 = NotAllowed; 1 = Allowed
HR12046doc 12046 / 412047Module 1 Foam StateUINT16Read0 = Ok; 1 = Detected
HR12047doc 12047 / 412048Module 1 Service DueUINT16Read0 = No; 1 = Yes
HR12048doc 12048 / 412049Module 2 Service DueUINT16Read0 = No; 1 = Yes
HR12049doc 12049 / 412050Module 3 Service DueUINT16Read0 = No; 1 = Yes
HR12050doc 12050 / 412051Module 4 Service DueUINT16Read0 = No; 1 = Yes
HR12051doc 12051 / 412052Network Control StateUINT16Read/write0 = Normal; 1 = Fault
HR12052doc 12052 / 412053Module 2 Foam StateUINT16Read0 = Ok; 1 = Detected
HR12053doc 12053 / 412054Module 3 Foam StateUINT16Read0 = Ok; 1 = Detected
HR12054doc 12054 / 412055Module 4 Foam StateUINT16Read0 = Ok; 1 = Detected
HR12055doc 12055 / 412056HRL Lock SetpointUINT16Read/write0 = Unlock; 1 = Lock
HR12056doc 12056 / 412057Module 1 Drain ValveUINT16Read0 = On; 1 = Off
HR12057doc 12057 / 412058Module 2 Drain ValveUINT16Read0 = On; 1 = Off
HR12058doc 12058 / 412059Module 3 Drain ValveUINT16Read0 = On; 1 = Off
HR12059doc 12059 / 412060Module 4 Drain ValveUINT16Read0 = On; 1 = Off
HR12060doc 12060 / 412061Inhibit Resistive Probe 1UINT16Read/write0 = No; 1 = Yes
HR12061doc 12061 / 412062Inhibit Resistive Probe 2UINT16Read/write0 = No; 1 = Yes
HR12062doc 12062 / 412063Inhibit Resistive Probe 3UINT16Read/write0 = No; 1 = Yes
HR12063doc 12063 / 412064Inhibit Resistive Probe 4UINT16Read/write0 = No; 1 = Yes
HR12064doc 12064 / 412065Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12065doc 12065 / 412066Notify WarningUINT16Read/write0 = Off; 1 = On
HR12066doc 12066 / 412067Notify App MsgUINT16Read/write0 = Off; 1 = On
HR12067doc 12067 / 412068Module 1 Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12068doc 12068 / 412069Module 2 Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12069doc 12069 / 412070Module 3 Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12070doc 12070 / 412071Module 4 Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12071doc 12071 / 412072Module 1 AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR12072doc 12072 / 412073Module 2 AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR12073doc 12073 / 412074Module 3 AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR12074doc 12074 / 412075Module 4 AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR15000doc 15000 / 415001Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15001doc 15001 / 415002Supply RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15002doc 15002 / 415003Room RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15003doc 15003 / 415004Control Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15004doc 15004 / 415005Control ProfileUINT16Read/write0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom
HR15005doc 15005 / 415006Modulating High Limit ProfileUINT16Read/write0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom
HR15006doc 15006 / 415007Occupancy StateUINT16Read0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off
HR15007doc 15007 / 415008Room RH SourceUINT16Read/write0 = None; 1 = RoomRH; 2 = Network; 3 = HRL
HR15008doc 15008 / 415009Room RH Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15009doc 15009 / 415010Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = Supply HLRH; 2 = Network
HR15010doc 15010 / 415011Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15011doc 15011 / 415012Humidity Control Demand SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network
HR15012doc 15012 / 415013Humidity Control High Limit SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network
HR15013doc 15013 / 415014Humidity Control Cutout StateUINT16Read0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = AirFlow; 5 = Interlock
HR15014doc 15014 / 415015System Power StateHumidifier on/off.UINT16Read/write0 = Off; 1 = On
HR15015doc 15015 / 415016Module 1 StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir
HR15016doc 15016 / 415017Module 1 RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir
HR15017doc 15017 / 415018Module 1 AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay
HR15018doc 15018 / 415019Module 2 StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir
HR15019doc 15019 / 415020Module 2 RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir
HR15020doc 15020 / 415021Module 2 AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay
HR15021doc 15021 / 415022Module 3 StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir
HR15022doc 15022 / 415023Module 3 RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir
HR15023doc 15023 / 415024Module 3 AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay
HR15024doc 15024 / 415025Module 4 StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm; 9 = PurgeAir
HR15025doc 15025 / 415026Module 4 RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib; 6 = PurgeAir
HR15026doc 15026 / 415027Module 4 AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = OverHeat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = BurnerLocked; 10 = FanDefect; 11 = FailedComm; 12 = ChimTempHi; 13 = RefillTimeout; 14 = FanBlocked; 15 = SystBlck; 16 = TankBlocked; 17 = RefillDelay
HR15027doc 15027 / 415028Boiler Fill ModeUINT16Read/write0 = OneShot; 1 = Pulsed
HR15028doc 15028 / 415029Boiler Idle Tank Rinse OffUINT16Read/write0 = Off; 1 = On
HR15029doc 15029 / 415030Boiler Idle Tank Rinse OnUINT16Read/write0 = Off; 1 = On
HR15030doc 15030 / 415031Water Probe 1 Auto CalibUINT16Read/write0 = Off; 1 = On
HR15031doc 15031 / 415032Water Probe 2 Auto CalibUINT16Read/write0 = Off; 1 = On
HR15032doc 15032 / 415033Water Probe 3 Auto CalibUINT16Read/write0 = Off; 1 = On
HR15033doc 15033 / 415034Water Probe 4 Auto CalibUINT16Read/write0 = Off; 1 = On
HR15034doc 15034 / 415035System ModeUINT16Read/write0 = Parallel; 1 = Sequential; 2 = Hybrid
HR15035doc 15035 / 415036Boiler Startup Tank RinseUINT16Read/write0 = Off; 1 = On
HR15036doc 15036 / 415037Module 1 Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15037doc 15037 / 415038Module 2 Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15038doc 15038 / 415039Module 3 Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15039doc 15039 / 415040Module 4 Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15040doc 15040 / 415041Water Level 1 Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15041doc 15041 / 415042Water Level 2 Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15042doc 15042 / 415043Water Level 3 Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15043doc 15043 / 415044Water Level 4 Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15044doc 15044 / 415045Module 1 Water Level Probe AlarmUINT16Read0 = Ok; 1 = Defect; 2 = NoCalib
HR15045doc 15045 / 415046Module 2 Water Level Probe AlarmUINT16Read0 = Ok; 1 = Defect; 2 = NoCalib
HR15046doc 15046 / 415047Module 3 Water Level Probe AlarmUINT16Read0 = Ok; 1 = Defect; 2 = NoCalib
HR15047doc 15047 / 415048Module 4 Water Level Probe AlarmUINT16Read0 = Ok; 1 = Defect; 2 = NoCalib

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)

What Modbus registers does the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) have?

This map lists 245 registers: 245 holding registers. 87 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)?

Start with HR 6005 Room RH (Room RH); HR 6039 Room RH Setpoint (Room RH set point); HR 6054 Humidity Demand (Humidity demand); HR 6055 System Power Output (System power output); HR 15015 Module 1 State (Module 1 state); HR 15017 Module 1 Alarm (Module 1 alarm); HR 15014 System Power State (System on/off); HR 6052 Humidity Control Network Demand (Network demand).

How do I enable Modbus control of the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)?

Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.

What happens when the Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) loses Modbus communication?

Network Timeout (6158, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12051) shows a fault.

Where is the official Neptronic SKG4 gas-fired steam humidifier (Modbus communication module) Modbus documentation?

The source is SKG4 Gas Fired Humidifier - Modbus Communication Module User Guide (SKG4-Modbus Guide-221114 (V2.04)), revision 2022-11-14, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKG4/20230526/SKG4-Modbus%20Guide-221114%20(V2.04).pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SKG4 Gas Fired Humidifier - Modbus Communication Module User Guide · SKG4-Modbus Guide-221114 (V2.04) · rev. 2022-11-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.