Easy Modbus
  1. Home
  2. Modbus register maps
  3. Neptronic
  4. EFCB Series networkable fan coil controller (Modbus RTU)

Thermostat / fan coil controller · Modbus register map

Neptronic EFCB Series networkable fan coil controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The EFCB is a Neptronic fan coil unit controller that pairs with a TFL/TDF digital room sensor and talks Modbus RTU on RS-485. Everything is in one holding-register table: sensor readings, heating/cooling/fan demands, relay and analog output states, mode, fan speed and setpoints, plus the full configuration set for outputs, inputs, humidity and CO2 options.

This page lists 171 Modbus registers for the Neptronic EFCB Series networkable fan coil controller (Modbus RTU) — 135 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
EFCB Series networkable fan coil controller (Modbus RTU)
Equipment type
Thermostat / fan coil controller
Registers
171 (135 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller
Source document
EFCB Series Modbus Communication Module User Guide · EFCB-Modbus Guide-260626
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic EFCB Series networkable fan coil controller (Modbus RTU)

Integration in brief

Read holding registers with function 03 at the wire address shown in the guide's Protocol Address column (Modicon 40001 = address 0). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 11Internal temperature sensor readingUINT16Internal (room) temperature x100Read
HR 14Control temperature readingUINT16Control temperature x100Read/write
HR 45System mode statusUINT16System modeRead/write
HR 46Fan speed selection by userUINT16Fan speedRead/write
HR 47Temperature setpoint in occupancy or day modeINT16Occupied setpoint x10Read/write
HR 24Actual heating demandUINT16Heating demandRead
HR 26Actual cooling demandUINT16Cooling demandRead
HR 9System Status 1BITMAP16Status 1 (fault, filter, changeover)Read
HR 10System Status 2BITMAP16Status 2 (alarms)Read
HR 48System options1BITMAP16System options 1 (bit 1 = Modbus temp unit)Read/write

Enable Modbus control & writes

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Byte order & addressing

Network setup

Watch out for

Neptronic EFCB Series networkable fan coil controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

171 of 171 shown
Neptronic EFCB Series networkable fan coil controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Address - Neptronic ID and Modbus address of current deviceUINT16Read/write
HR1doc 40002Baud rate (baud / 100)0 = automatic detection.UINT16× 100Read/write
HR2doc 40003Communication port configurationUINT16Read/write1 = No parity, 2 Stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 Stop bit
HR7doc 40008Product actual firmware versionUINT16Read
HR8doc 40009Product actual EEPROM versionUINT16Read
HR9doc 40010System Status 1BITMAP16Readbit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB (0 = Normal, 1 = OFF); bit 3 = Change Over Mode (0 = Cooling, 1 = Heating); bit 4 = Flow Switch Alarm (0 = No alarm, 1 = Alarm activated); bit 6 = Dirty Filter Alarm (0 = No alarm, 1 = Alarm activated); bit 12 = Analog Input 3 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 13 = Analog Input 4 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 14 = Analog Input 5 mode (0 = Temp 10kΩ, 1 = 0-10Vdc); bit 15 = Analog Input 6 Mode (0 = Temp 10kΩ, 1 = 0-10Vdc)
HR10doc 40011System Status 2BITMAP16Readbit 7 = Override Alarm (0 = Off, 1 = On); bit 8 = Window Opened Alarm (0 = Off, 1 = On); bit 9 = Door Opened Alarm (0 = Off, 1 = On); bit 10 = DI1 Alarm (0 = Off, 1 = On); bit 11 = DI2 Alarm (0 = Off, 1 = On); bit 13 = DI4 Alarm (0 = Off, 1 = On); bit 15 = Overheat Alarm (0 = Off, 1 = On)
HR11doc 40012Internal temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR12doc 40013External temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR13doc 40014Changeover temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead
HR14doc 40015Control temperature readingUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.01°C / °FRead/write
HR15doc 40016Internal humidity sensor readingNot on every model.UINT16× 0.1%RHRead
HR16doc 40017External Humidity sensor readingNot on every model.UINT16× 0.1%RHRead
HR17doc 40018Analog input 3 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR18doc 40019Analog input 4 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR19doc 40020Analog input 5 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR20doc 40021Analog input 6 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR21doc 40022Digital input status of 4 digital inputsBITMAP16Readbit 0 = Digital input 1 (0 = Open, 1 = Close); bit 1 = Digital input 2 (0 = Open, 1 = Close); bit 2 = Digital input 3 (0 = Open, 1 = Close); bit 3 = Digital input 4 (0 = Open, 1 = Close); bit 4 = AI3 Digital input (0 = Open, 1 = Close); bit 5 = AI4 Digital input (0 = Open, 1 = Close); bit 6 = AI5 Digital input (0 = Open, 1 = Close); bit 7 = AI6 Digital input (0 = Open, 1 = Close)
HR22doc 40023Actual system occupancy stateUINT16Read1 = NoOccupancy; 2 = Occupancy; 3 = Override
HR23doc 40024Actual night setback state of the systemNot on every model.UINT16Read1 = Day; 2 = Night; 3 = Override
HR24doc 40025Actual heating demandUINT16× 0.1%Read
HR25doc 40026Actual local reheat demandUINT16× 0.1%Read
HR26doc 40027Actual cooling demandUINT16× 0.1%Read
HR27doc 40028Actual changeover demandUINT16× 0.1%Read
HR28doc 40029Actual fan demandUINT16× 0.1%Read
HR29doc 40030Actual dehumidification demandNot on every model.UINT16× 0.1%Read
HR30doc 40031Actual humidification demandNot on every model.UINT16× 0.1%Read
HR31doc 40032Switch timer countdown until the system is able to swap the demandUINT16minRead
HR32doc 40033Analog output 1 valueUINT16× 0.1%Read/write
HR33doc 40034Analog output 2 valueUINT16× 0.1%Read/write
HR34doc 40035Analog output 3 valueUINT16× 0.1%Read/write
HR35doc 40036Analog output 4 valueUINT16× 0.1%Read/write
HR36doc 40037Floating output 1 valueUINT16× 0.1%Read
HR37doc 40038Floating output 2 valueUINT16× 0.1%Read
HR38doc 40039Pulsing output 1 valueUINT16× 0.1%Read
HR39doc 40040Pulsing output 2 valueUINT16× 0.1%Read
HR40doc 40041Pulsing output 3 valueINT16× 0.1%Read
HR41doc 40042Pulsing output 4 valueINT16× 0.1%Read
HR42doc 40043TRIAC output on-off mode statusBITMAP16Read/writebit 0 = On Off output 1 (0 = Off, 1 = On); bit 1 = On Off output 2 (0 = Off, 1 = On); bit 2 = On Off output 3 (0 = Off, 1 = On); bit 3 = On Off output 4 (0 = Off, 1 = On)
HR43doc 40044Digital output - 7 relays output statusBITMAP16Read/writebit 0 = Digital output 1 (0 = Open, 1 = Close); bit 1 = Digital output 2 (0 = Open, 1 = Close); bit 2 = Digital output 3 (0 = Open, 1 = Close); bit 3 = Digital output 4 (0 = Open, 1 = Close); bit 4 = FAN Output High (0 = Open, 1 = Close); bit 5 = FAN Output Med (0 = Open, 1 = Close); bit 6 = FAN Output Low (0 = Open, 1 = Close)
HR44doc 40045System commandBITMAP16Read/writebit 0 = Service Display Address (0 = Off; 1 = Display address on LCD); bit 1 = Cooling Ramp Lock (0 = Off; 1 = On); bit 2 = Condensation Alarm (0 = Off; 1 = On); bit 3 = Heating Ramp Lock (0 = Off; 1 = On); bit 4 = Reheat Ramp Lock (0 = Off; 1 = On); bit 5 = Changeover Ramp Lock (0 = Off; 1 = On); bit 7 = Humidify Ramp Lock (0 = Off; 1 = On); bit 8 = Dehumidify Ramp Lock (0 = Off; 1 = On)
HR45doc 40046System mode statusUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Off
HR46doc 40047Fan speed selection by userUINT16Read/write1 = Auto; 2 = Low; 3 = Med; 4 = High
HR47doc 40048Temperature setpoint in occupancy or day modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR48doc 40049System options1BITMAP16Read/writebit 0 = Temp unit displayed on Digital Room Sensor (0 = °C, 1 = °F); bit 1 = Temp unit displayed in Modbus (0 = °C, 1 = °F); bit 2 = Temp SetPoint Lock (0 = Off, 1 = On); bit 3 = Humidity SetPoint Lock (0 = Off, 1 = On); bit 4 = Program Mode Lock (0 = Off, 1 = On); bit 5 = Floating TO1/TO2 Direction (0 = Direct, 1 = Reverse); bit 6 = Floating TO3/TO4 Direction (0 = Direct, 1 = Reverse); bit 7 = Freeze Protection Alarm (0 = Off, 1 = On); bit 8 = User System Off Modes (0 = Enable, 1 = Disable); bit 9 = Keypad Bottom Left Lock (0 = Off, 1 = On); bit 10 = Keypad Upper Left Lock (0 = Off, 1 = On); bit 11 = Keypad Arrows Lock (0 = Off, 1 = On); bit 12 = User Fan Auto Mode (0 = Enable, 1 = Disable); bit 13 = Night SetBack Mode (0 = Setpoint, 1 = OFF); bit 14 = Humidity Control Source (0 = Intern Sensor, 1 = Extern Sensor); bit 15 = Time Mode (0 = 24h, 1 = 12h)
HR49doc 40050System options 2BITMAP16Read/writebit 2 = Baud Rate (0 = Auto, 1 = Manual); bit 3 = Schedule On or Off (0 = Off, 1 = On); bit 4 = Analog Output 1 Direction (0 = Direct, 1 = Reverse); bit 5 = Analog Output 2 Direction (0 = Direct, 1 = Reverse); bit 6 = Analog Output 3 Direction (0 = Direct, 1 = Reverse); bit 7 = Analog Output 4 Direction (0 = Direct, 1 = Reverse); bit 8 = TO1 Direction (0 = Direct, 1 = Reverse); bit 9 = TO2 Direction (0 = Direct, 1 = Reverse); bit 10 = TO3 Direction (0 = Direct, 1 = Reverse); bit 11 = TO4 Direction (0 = Direct, 1 = Reverse); bit 12 = Digital Output 1 Direction (0 = Direct, 1 = Reverse); bit 13 = Digital Output 2 Direction (0 = Direct, 1 = Reverse); bit 14 = Digital Output 3 Direction (0 = Direct, 1 = Reverse); bit 15 = Digital Output 4 Direction (0 = Direct, 1 = Reverse)
HR50doc 40051System options 3BITMAP16Read/writebit 1 = ECM Fan Enable (0 = Off, 1 = On); bit 3 = Display CO2 (0 = Off, 1 = On); bit 4 = CO2 Source Select (0 = TFL, 1 = Analog); bit 7 = Occupancy Control Source (0 = DigitalInput3, 1 = InternSensor)
HR52doc 40053TFL/TDF display informationUINT16Read/write1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off
HR53doc 40054Temperature control sourceUINT16Read/write1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp
HR54doc 40055Network fallback timeout Present ValueUINT16minRead/write
HR55doc 40056Minimum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR56doc 40057Maximum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR57doc 40058Cooling temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR58doc 40059Heating temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR59doc 40060Heating proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR60doc 40061Local reheat proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR61doc 40062Cooling proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR62doc 40063Change over proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR63doc 40064Heating dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR64doc 40065Local reheat dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR65doc 40066Cooling dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR66doc 40067Change over dead bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR67doc 40068Change over setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR68doc 40069Fan time out in secondsUINT16sRead/write
HR69doc 40070Fan damping factor in secondsUINT16sRead/write
HR70doc 40071Heating integral time factor in secondsUINT16sRead/write
HR71doc 40072Cooling integral time factor in secondsUINT16sRead/write
HR72doc 40073Delay between cooling and heating or vice versaUINT16minRead/write
HR73doc 40074Cooling anticycle delay in minutesUINT16minRead/write
HR74doc 40075NSB override delay in minutesUINT16minRead/write
HR75doc 40076Unoccupied override delay in minutesUINT16minRead/write
HR76doc 40077Occupancy minimum time in minutesUINT16minRead/write
HR77doc 40078Unoccupied override delay countdownUINT16minRead/write
HR78doc 40079System Control modeUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool
HR79doc 40080Digital input 3 modeUINT16Read/write1 = Off; 2 = Occupancy normally open; 3 = Occupancy normally close; 4 = NSB normally open; 5 = NSB normally close
HR80doc 40081Override system occupancy or NSB modeOptions available depend on the DI3 mode (register 40080).UINT16Read/write1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night
HR81doc 40082Internal temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR82doc 40083External temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR83doc 40084Change over analog input signalUINT16Read/write3 = Sensor; 4 = Normally Cool; 5 = Normally Heat
HR84doc 40085Change over control modeUINT16Read/write1 = Local; 2 = Cool; 3 = Heat
HR85doc 40086External temperature 0-10V input on analog inputUINT16Read/write1 = Off; 2 = 2-10V; 3 = 0-10V
HR86doc 40087Minimum analog input external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR87doc 40088Maximum analog input external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR88doc 40089Fan output signalUINT16Read/write1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog
HR89doc 40090Ramp to control analog output 1UINT16Read/write1 = Off; 2 = Alarm; 3 = Changeover with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR90doc 40091Minimum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR91doc 40092Maximum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR92doc 40093Ramp to control analog output 2UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR93doc 40094Minimum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR94doc 40095Maximum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR95doc 40096Ramp to control analog output 3UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Reserved; 10 = Cooling or Heating
HR96doc 40097Minimum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR97doc 40098Maximum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR98doc 40099Ramp to control analog output 4UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor); 9 = Fan; 10 = Cooling or Heating
HR99doc 40100Minimum voltage for analog output 4 (volt)UINT16× 0.1VRead/write
HR100doc 40101Maximum voltage for analog output 4 (volt)UINT16× 0.1VRead/write
HR101doc 40102Timing of floating motor TO1-TO2 in secondsUINT16sRead/write
HR102doc 40103Timing of floating motor TO3-TO4 in secondsUINT16sRead/write
HR103doc 40104Ramp to control TRIAC output 1UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR104doc 40105Signal output configuration for TRIAC output 1UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR105doc 40106TRIAC output 1 when set to closeUINT16%Read/write
HR106doc 40107TRIAC output 1 when set to openUINT16%Read/write
HR107doc 40108Ramp to control TRIAC output 2UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR108doc 40109Signal output configuration for TRIAC output 2UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR109doc 40110TRIAC output 2 when set to closeUINT16%Read/write
HR110doc 40111TRIAC output 2 when set to openUINT16%Read/write
HR111doc 40112Ramp to control TRIAC output 3UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR112doc 40113Signal output configuration for TRIAC output 3UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR113doc 40114TRIAC output 3 when set to closeUINT16%Read/write
HR114doc 40115TRIAC output 3 when set to openUINT16%Read/write
HR115doc 40116Ramp to control TRIAC output 4UINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat
HR116doc 40117Signal output configuration for TRIAC output 4UINT16Read/write1 = Pulsing mode; 2 = On/Off mode; 3 = Floating mode
HR117doc 40118TRIAC output 4 when set to closeUINT16%Read/write
HR118doc 40119TRIAC output 4 when set to openUINT16%Read/write
HR119doc 40120Configuration of DO1 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR120doc 40121Delay before activation of DO1 in minutesUINT16minRead/write
HR121doc 40122Close position percentage for contact DO1UINT16%Read/write
HR122doc 40123Open position percentage for contact DO1UINT16%Read/write
HR123doc 40124Configuration of DO2 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR124doc 40125Activation delay for contact DO2 in minutesUINT16minRead/write
HR125doc 40126Close position percentage for contact DO2UINT16%Read/write
HR126doc 40127Open position percentage for contact DO2UINT16%Read/write
HR127doc 40128Configuration of DO3 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR128doc 40129Activation delay for contact DO3 in minutesUINT16minRead/write
HR129doc 40130Close position percentage for contact DO3UINT16%Read/write
HR130doc 40131Open position percentage for contact DO3UINT16%Read/write
HR131doc 40132Configuration of DO4 modeUINT16Read/write1 = Off; 2 = Alarm; 3 = Change Over with fan; 4 = Cooling with fan; 5 = Heating with fan; 6 = Local Reheat with fan; 7 = Local Reheat; 8 = Humidify with fan (needs a TFLH/TDF humidity room sensor)
HR132doc 40133Activation delay for contact DO4 in minutesUINT16minRead/write
HR133doc 40134Close position percentage for contact DO4UINT16%Read/write
HR134doc 40135Open position percentage for contact DO4UINT16%Read/write
HR135doc 40136Digital input contact of DI1 to DI4BITMAP16Read/writebit 0 = Digital input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Digital input 2 (0 = Normally Open, 1 = Normally Close); bit 2 = Digital input 3 (0 = Normally Open, 1 = Normally Close); bit 4 = Digital input 4 (0 = Normally Open, 1 = Normally Close)
HR136doc 40137Configuration of DI1 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat
HR137doc 40138Delay before activation of DI1 in minutesUINT16minRead/write
HR138doc 40139Configuration of DI2 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat
HR139doc 40140Delay before activation of DI2 in minutesUINT16minRead/write
HR140doc 40141Configuration of DI4 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat
HR141doc 40142Delay before activation of DI4 in minutesUINT16minRead/write
HR142doc 40143Humidity control mode statusNot on every model.UINT16Read/write1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off
HR143doc 40144Humidity setpoint (%RH) in occupancy or day modeNot on every model.UINT16× 0.1%RHRead/write
HR144doc 40145Dehumidification setpoint (%RH) in unoccupied or night modeNot on every model.UINT16× 0.1%RHRead/write
HR145doc 40146Humidification setpoint (%RH) in unoccupied or night modeNot on every model.UINT16× 0.1%RHRead/write
HR146doc 40147Minimum user setpointNot on every model.UINT16× 0.1%RHRead/write
HR147doc 40148Maximum user setpointNot on every model.UINT16× 0.1%RHRead/write
HR148doc 40149Humidity proportional bandNot on every model.UINT16× 0.1%RHRead/write
HR149doc 40150Humidity deadband (Cfg_HumDeadBand)Not on every model.UINT16× 0.1%RHRead/write
HR151doc 40152Internal humidity sensor offset correctionINT16× 0.1%RHRead/write
HR152doc 40153External humidity sensor offset correctionINT16× 0.1%RHRead/write
HR153doc 40154Internal CO2 sensor readingNot on every model.UINT16ppmRead
HR154doc 40155Maximum limit of CO2 concentrationNot on every model.UINT16× 0.1ppmRead/write
HR155doc 40156System status 3UINT16Read0 = Off; 1 = On
HR156doc 40157Maximum range for the CO2 sensorNot on every model.UINT16× 0.02ppmRead/write
HR157doc 40158External CO2 sensor readingNot on every model.UINT16ppmRead
HR158doc 40159Internal light sensor reading in LuxesNot on every model.UINT16lxRead
HR159doc 40160Internal PIR sensor readingNot on every model.UINT16Read0 = No Occupancy; 1 = Occupancy
HR160doc 40161Internal VOC sensor reading in ppbNot on every model.UINT16ppbRead
HR161doc 40162Configuration of AI3 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR162doc 40163Configuration of AI4 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR163doc 40164Configuration of AI5 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR164doc 40165Configuration of AI6 modeUINT16Read/write1 = Off; 2 = Temperature; 3 = CO2; 4 = Humidity
HR165doc 40166Configuration of TO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR166doc 40167Configuration of TO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR167doc 40168Configuration of TO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR168doc 40169Configuration of TO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR169doc 40170Configuration of AO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR170doc 40171Configuration of AO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR171doc 40172Configuration of AO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR172doc 40173Configuration of AO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR173doc 40174Configuration of DO1 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR174doc 40175Configuration of DO2 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR175doc 40176Configuration of DO3 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2
HR176doc 40177Configuration of DO4 alarm sourceUINT16Read/write1 = Alarm Override; 2 = Alarm Overheat; 3 = Alarm Door; 4 = Alarm Window Contact; 5 = Alarm FlowSwitch; 6 = Alarm CO2

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic EFCB Series networkable fan coil controller (Modbus RTU)

What Modbus registers does the Neptronic EFCB Series networkable fan coil controller (Modbus RTU) have?

This map lists 171 registers: 171 holding registers. 135 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic EFCB Series networkable fan coil controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both the protocol (wire) address, starting at 0, and the 40001-style notation; e.g. 40046 is protocol address 45. The documented field holds the 4xxxx notation.

What are the minimum Modbus registers to integrate the Neptronic EFCB Series networkable fan coil controller (Modbus RTU)?

Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 45 System mode status (System mode); HR 46 Fan speed selection by user (Fan speed); HR 47 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 24 Actual heating demand (Heating demand); HR 26 Actual cooling demand (Cooling demand); HR 9 System Status 1 (Status 1 (fault, filter, changeover)); HR 10 System Status 2 (Status 2 (alarms)); HR 48 System options1 (System options 1 (bit 1 = Modbus temp unit)).

How do I enable Modbus control of the Neptronic EFCB Series networkable fan coil controller (Modbus RTU)?

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Where is the official Neptronic EFCB Series networkable fan coil controller (Modbus RTU) Modbus documentation?

The source is EFCB Series Modbus Communication Module User Guide (EFCB-Modbus Guide-260626), published free by Neptronic at https://www.neptronic.com/controls/PDF/2026/EFCB-Modbus%20Guide-260626.pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: EFCB Series Modbus Communication Module User Guide · EFCB-Modbus Guide-260626. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.