Air handler (in-row data-centre cooling unit) · Modbus register map
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus register map
Updated 19 November 2026
The InRow ACRD60x and ACRC60x are in-row cooling units for data-centre rows and contained aisles. Their controller answers Modbus RTU and Modbus TCP with everything in holding registers. This map covers the cooling-group values (output, demand, setpoints, airflow), the unit's operating mode, supply/return/rack-inlet temperatures, humidity, fan speed, chilled-water and refrigerant readings, compressor VFD data, run hours, service settings, thresholds and 80-plus alarm flags.
This page lists 216 Modbus registers for the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) — 53 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.
- Manufacturer
- APC (Schneider Electric)
- Model
- InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
- Equipment type
- Air handler (in-row data-centre cooling unit)
- Registers
- 216 (53 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786
Integration notes: APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
Read the unit operating mode (1206, ENUM) and the supply/return air temperatures (1225, 1227), rack inlet temperatures (1238-1243) and fan speed (1235), which are UINT32 values in tenths, high word first. Write the group cool setpoint at 1023 (tenths of deg C, two registers with function 16).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1206 | Operating Mode | INT16 | Operating mode | Read |
| HR 1225 | Supply Air Temperature | UINT32 ABCD | Supply air temperature | Read |
| HR 1227 | Return Air Temperature | UINT32 ABCD | Return air temperature | Read |
| HR 1238 | Rack Inlet Temperature 1 | UINT32 ABCD | Rack inlet temperature 1 | Read |
| HR 1235 | Fan Speed | UINT32 ABCD | Fan speed | Read |
| HR 1023 | Group: Cool Setpoint | UINT32 ABCD | Group cool setpoint | Read/write |
| HR 1000 | Group: Overall Status | INT16 | Overall status | Read |
| HR 512 | Internal Communication Error | INT16 | First alarm flag (alarm block starts here) | Read |
Enable Modbus control & writes
Not described in the register map.
Byte order & addressing
- The decimal 'Absolute Starting Register Number' is the wire address; the Modicon column is that number plus 40001.
- Every UINT32/INT32 takes two registers, most-significant word first; write them with function code 16.
- Temperatures such as supply and rack-inlet are listed as UINT32 even though they are in tenths of deg C.
Network setup
- Both Modbus RTU (serial) and Modbus TCP are supported per the map; the serial settings and unit ID are not listed in this document.
Watch out for
- A single large read can take 2 s or more; if requests time out, read fewer registers at a time or raise the timeout.
- Reading before the controller has data ready returns an invalid-address error.
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 512doc 40513 | Internal Communication Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 513doc 40514 | A-link isolation relay fault exists | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 514doc 40515 | External communication fault | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 515doc 40516 | Cool Function Unavailable | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 516doc 40517 | Rack Inlet 1 High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 517doc 40518 | Rack Inlet 2 High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 518doc 40519 | Rack Inlet 3 High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 519doc 40520 | High Return Humidity Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 520doc 40521 | Low Return Humidity Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 521doc 40522 | Air Filter Clogged | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 522doc 40523 | Return Air Temperature Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 523doc 40524 | Upper Supply Air Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 524doc 40525 | Rack Temperature Sensor 1 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 525doc 40526 | Rack Temperature Sensor 2 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 526doc 40527 | Rack Temperature Sensor 3 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 527doc 40528 | Chilled Water Valve Actuator Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 528doc 40529 | High Discharge Pressure Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 529doc 40530 | Low Suction Pressure Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 530doc 40531 | High Suction Pressure Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 531doc 40532 | Humidifier Error Tolerance Exceed Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 532doc 40533 | Fan 1 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 533doc 40534 | Fan 2 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 534doc 40535 | Fan 3 Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 535doc 40536 | Water Detected Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 536doc 40537 | Check Condensate Management System | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 538doc 40539 | Humidifier High Water Conductivity | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 539doc 40540 | Humidifier Low Water Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 540doc 40541 | Humidifier Excessive Output Reduction Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 541doc 40542 | Humidifier Drain Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 542doc 40543 | Humidifier Cylinder Full Unit Off Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 543doc 40544 | Humidifier Replace Cylinder Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 544doc 40545 | Compressor Drive Failure | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 545doc 40546 | Compressor Drive Warning | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 546doc 40547 | Entering Chilled Water High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 547doc 40548 | Entering Chilled Water Temperature Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 548doc 40549 | Leaving Chilled Water Temperature Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 549doc 40550 | Primary Power Source Unavailable | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 550doc 40551 | Humidifier Communication Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 551doc 40552 | Compressor Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 552doc 40553 | Heater 1 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 553doc 40554 | Heater 2 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 554doc 40555 | Heater 3 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 555doc 40556 | Humidifier Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 556doc 40557 | Fan 1 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 557doc 40558 | Fan 2 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 558doc 40559 | Fan 3 Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 559doc 40560 | Air Filter Run Hours Violation | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 560doc 40561 | Condensate Pump Runtime Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 561doc 40562 | Group Communication Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 562doc 40563 | Compressor Drive Communication Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 563doc 40564 | Supply Air High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 564doc 40565 | Return Air High Temperature Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 565doc 40566 | Filter Differential Pressure Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 567doc 40568 | Suction Pressure Sensor Failure | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 568doc 40569 | Discharge Pressure Sensor Failure | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 570doc 40571 | Standby Due to Input Contact | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 571doc 40572 | Supply Humidity Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 572doc 40573 | Return Humidity Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 573doc 40574 | Heater 1 Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 574doc 40575 | Heater 2 Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 575doc 40576 | Heater 3 Error | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 576doc 40577 | Compressor High Head Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 579doc 40580 | Lower Supply Air Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 581doc 40582 | Excessive Compressor Cycling Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 582doc 40583 | Persistent Compressor High Head Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 583doc 40584 | Chilled Water Flow Meter Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 584doc 40585 | Idle Due To Leak Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 585doc 40586 | Fluid Calibration Active | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 586doc 40587 | No Backup Units Available | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 587doc 40588 | EcoAisle Door Open | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 588doc 40589 | Unexpected Number of Active Flow Controllers | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 589doc 40590 | Insufficient Airflow Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 590doc 40591 | Active Flow Controller Sensor Error Detected | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 591doc 40592 | Condensate Pan Full | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 592doc 40593 | Compressor Drive Locked | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 593doc 40594 | VFD Inverter Over Heated Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 594doc 40595 | Persistent Low Suction Pressure Condition | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 595doc 40596 | Unit Capability Not Configured | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 596doc 40597 | Compressor Suction Sensor Fault | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 597doc 40598 | Low Superheat Warning | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 598doc 40599 | Low superheat Critical | INT16 | Read | 0 = Clear; 1 = Alarm | ||||
| HR | 1000doc 41001 | Group: Overall Status | INT16 | Read | 0 = OK State; 1 = Info State; 2 = Warning State; 3 = Critical State | ||||
| HR | 1001doc 41002 | Group Cool Output | UINT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 1003doc 41004 | Group Cool Demand | UINT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 1005doc 41006 | Group Humidify Output | UINT32 | ABCD | % | Read | |||
| HR | 1007doc 41008 | Group Humidify Demand | UINT32 | ABCD | % | Read | |||
| HR | 1009doc 41010 | Group Dehumidify Output | UINT32 | ABCD | % | Read | |||
| HR | 1011doc 41012 | Group Dehumidify Demand | UINT32 | ABCD | % | Read | |||
| HR | 1013doc 41014 | Group Reheat Output | UINT32 | ABCD | % | Read | |||
| HR | 1015doc 41016 | Group Reheat Demand | UINT32 | ABCD | % | Read | |||
| HR | 1017doc 41018 | Group Airflow | UINT32 | ABCD | × 0.1 | L/s | Read | ||
| HR | 1019doc 41020 | Group Maximum Rack Inlet Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1021doc 41022 | Group Minimum Rack Inlet Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1023doc 41024 | Group: Cool Setpoint | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1025doc 41026 | Group: Humidify Setpoint | UINT32 | ABCD | × 0.1 | %RH | Read/write | ||
| HR | 1027doc 41028 | Group: Dehumidify Setpoint | UINT32 | ABCD | × 0.1 | %RH | Read/write | ||
| HR | 1029doc 41030 | Group: Dehumidify Deadband | UINT32 | ABCD | %RH | Read/write | |||
| HR | 1031doc 41032 | Group: Reheat Setpoint | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1033doc 41034 | Group: Supply Air Setpoint | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1035doc 41036 | Group: Number of Units in Group | UINT32 | ABCD | Read/write | ||||
| HR | 1037doc 41038 | Group: Configuration Type | INT16 | Read | 0 = RACS; 1 = HACS; 2 = In-Row; 3 = CACS | ||||
| HR | 1038doc 41039 | Group: Percent Glycol | UINT32 | ABCD | % | Read | |||
| HR | 1040doc 41041 | Group: Cool Gain 'P' | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1042doc 41043 | Group: Cool Reset Rate 'I' | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1044doc 41045 | Group: Cool Derivative 'D' | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1046doc 41047 | Group: Humidify Sensitivity Band | UINT32 | ABCD | %RH | Read/write | |||
| HR | 1048doc 41049 | Group: Reheat Gain (P) | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1050doc 41051 | Group: Reheat Integral (I) | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1052doc 41053 | Group: Reheat Derivative (D) | UINT32 | ABCD | × 0.01 | Read | |||
| HR | 1054doc 41055 | Group: Fan Speed Preference | INT16 | Read/write | 0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High | ||||
| HR | 1055doc 41056 | Group: Air Flow Control | INT16 | Read/write | 0 = Automatic; 1 = Manual | ||||
| HR | 1056doc 41057 | Group: Number of Backup Units | UINT32 | ABCD | Read/write | ||||
| HR | 1058doc 41059 | Group: Number of Precision Units | UINT32 | ABCD | Read/write | ||||
| HR | 1060doc 41061 | Group: Load Assist Enable | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 1061doc 41062 | Group: Run-Time Balancing Enable | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 1062doc 41063 | Group: Maximum Fan Speed | UINT32 | ABCD | % | Read/write | |||
| HR | 1064doc 41065 | Group: Altitude | UINT32 | ABCD | m | Read/write | |||
| HR | 1066doc 41067 | Group: Number of Active Flow Controllers | UINT32 | ABCD | Read/write | ||||
| HR | 1068doc 41069 | Group: Active Flow Control Bias | INT16 | Read | 0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative | ||||
| HR | 1069doc 41070 | Group: Active Flow Control Status | INT16 | Read | 0 = Under; 1 = Okay; 2 = Over; 3 = NA | ||||
| HR | 1070doc 41071 | Group: Active Flow Control Lamp Test | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1071doc 41072 | Group: Dew Point Temperature | INT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1128doc 41129 | Unit Name | STRING[42] | Read/write | |||||
| HR | 1149doc 41150 | Location | STRING[42] | Read/write | |||||
| HR | 1170doc 41171 | Unit ID | UINT32 | ABCD | Read | ||||
| HR | 1172doc 41173 | Model Number | STRING[20] | Read | |||||
| HR | 1182doc 41183 | Serial Number | STRING[20] | Read | |||||
| HR | 1192doc 41193 | Firmware Revision | STRING[8] | Read | |||||
| HR | 1196doc 41197 | Hardware Revision | STRING[8] | Read | |||||
| HR | 1200doc 41201 | Manufacturing Date | STRING[12] | Read | |||||
| HR | 1206doc 41207 | Operating Mode | INT16 | Read | 0 = Standby; 1 = On; 2 = Idle; 3 = Prestart; 4 = Backup; 5 = Load Assist | ||||
| HR | 1207doc 41208 | Cool Output | UINT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 1209doc 41210 | Cool Demand | UINT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 1211doc 41212 | Humidify Output | UINT32 | ABCD | % | Read | |||
| HR | 1213doc 41214 | Humidify Demand | UINT32 | ABCD | % | Read | |||
| HR | 1215doc 41216 | Dehumidify Output | UINT32 | ABCD | % | Read | |||
| HR | 1217doc 41218 | Dehumidify Demand | UINT32 | ABCD | % | Read | |||
| HR | 1219doc 41220 | Reheat Output | UINT32 | ABCD | % | Read | |||
| HR | 1221doc 41222 | Reheat Demand | UINT32 | ABCD | % | Read | |||
| HR | 1223doc 41224 | Unit Maximum Rack Inlet Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1225doc 41226 | Supply Air Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1227doc 41228 | Return Air Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1229doc 41230 | Supply Humidity | UINT32 | ABCD | × 0.1 | %RH | Read | ||
| HR | 1231doc 41232 | Return Humidity | UINT32 | ABCD | × 0.1 | %RH | Read | ||
| HR | 1233doc 41234 | Airflow | UINT32 | ABCD | × 0.1 | L/s | Read | ||
| HR | 1235doc 41236 | Fan Speed | UINT32 | ABCD | × 0.1 | % | Read | ||
| HR | 1237doc 41238 | Active Power Source | INT16 | Read | 0 = Primary; 1 = Secondary | ||||
| HR | 1238doc 41239 | Rack Inlet Temperature 1 | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1240doc 41241 | Rack Inlet Temperature 2 | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1242doc 41243 | Rack Inlet Temperature 3 | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1244doc 41245 | Filter Differential Pressure | UINT32 | ABCD | × 0.1 | Pa | Read | ||
| HR | 1248doc 41249 | Humidifier Current | UINT32 | ABCD | × 0.1 | A | Read | ||
| HR | 1250doc 41251 | Humidifier Water Conductivity | UINT32 | ABCD | uS/cm | Read | |||
| HR | 1252doc 41253 | CW Valve Position | UINT32 | ABCD | % | Read | |||
| HR | 1254doc 41255 | CW Fluid Flow | UINT32 | ABCD | × 0.1 | L/s | Read | ||
| HR | 1256doc 41257 | Entering Fluid Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1258doc 41259 | Leaving Fluid Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1260doc 41261 | Suction Pressure | UINT32 | ABCD | × 0.1 | kPa | Read | ||
| HR | 1262doc 41263 | Discharge Pressure | UINT32 | ABCD | × 0.1 | kPa | Read | ||
| HR | 1264doc 41265 | VFD Speed | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| HR | 1266doc 41267 | VFD Power | UINT32 | ABCD | × 0.01 | kW | Read | ||
| HR | 1268doc 41269 | VFD Motor Voltage | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 1270doc 41271 | VFD Motor Current | UINT32 | ABCD | × 0.01 | A | Read | ||
| HR | 1272doc 41273 | VFD DC Link Voltage | UINT32 | ABCD | V | Read | |||
| HR | 1274doc 41275 | VFD Heat Sink Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1276doc 41277 | VFD Control Card Temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| HR | 1282doc 41283 | Air Filter Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1284doc 41285 | Fan 1 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1286doc 41287 | Fan 2 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1288doc 41289 | Fan 3 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1290doc 41291 | Compressor Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1292doc 41293 | Humidifier Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1294doc 41295 | Heater 1 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1296doc 41297 | Heater 2 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1298doc 41299 | Heater 3 Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1300doc 41301 | Condensate Pump Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1302doc 41303 | Air Filter Service Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1304doc 41305 | Air Filter Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1305doc 41306 | Humidifier Service Alarm Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1307doc 41308 | Humidifier Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1308doc 41309 | Heater Service Alarm Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1310doc 41311 | Heater Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1311doc 41312 | Compressor Service Alarm Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1313doc 41314 | Compressor Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1314doc 41315 | Fans Service Alarm Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1316doc 41317 | Fans Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1317doc 41318 | Condensate Pump Service Alarm Interval | UINT32 | ABCD | weeks | Read/write | |||
| HR | 1319doc 41320 | Condensate Pump Service Alarm Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1320doc 41321 | Rack Inlet Temperature High Threshold | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1322doc 41323 | Supply Air Temperature High Threshold | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1324doc 41325 | Return Air Temperature High Threshold | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1326doc 41327 | CW Entering Temp High Threshold | UINT32 | ABCD | × 0.1 | °C | Read/write | ||
| HR | 1328doc 41329 | Return Humidity High Threshold | UINT32 | ABCD | × 0.1 | %RH | Read/write | ||
| HR | 1330doc 41331 | Return Humidity Low Threshold | UINT32 | ABCD | × 0.1 | %RH | Read/write | ||
| HR | 1332doc 41333 | Startup Delay | UINT32 | ABCD | sec | Read/write | |||
| HR | 1334doc 41335 | Cool Capacity | INT16 | Read/write | 0 = Automatic; 1 = Maximum | ||||
| HR | 1335doc 41336 | Idle on Leak Detect | INT16 | Read/write | 0 = Yes; 1 = No | ||||
| HR | 1336doc 41337 | Standby Input Normal State | INT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 1337doc 41338 | Standby Input State | INT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 1338doc 41339 | Output Normal State | INT16 | Read/write | 0 = Open; 1 = Closed | ||||
| HR | 1339doc 41340 | Output State | INT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 1340doc 41341 | Output Source | INT16 | Read | 0 = Any Alarm; 1 = Only Critical Alarms | ||||
| HR | 1341doc 41342 | Humidify Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1342doc 41343 | Humidifier Control | INT16 | Read/write | 1 = Auto; 2 = Drain | ||||
| HR | 1343doc 41344 | Dehumidify Enable | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 1344doc 41345 | Reheat Enable | INT16 | Read/write | 0 = Enable; 1 = Disable | ||||
| HR | 1345doc 41346 | Heat Assist Enable | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 1346doc 41347 | Power Source | INT16 | Read/write | 0 = Single; 1 = Dual | ||||
| HR | 1347doc 41348 | Unit Role Override | INT16 | Read/write | 0 = Automatic; 1 = Forced On | ||||
| HR | 1348doc 41349 | System Run Hours | UINT32 | ABCD | hr | Read | |||
| HR | 1350doc 41351 | Secondary Power Feed Capability | INT16 | Read/write | 0 = FullPower; 1 = ReducedPower | ||||
| HR | 1351doc 41352 | Bypass Valve Position | INT16 | Read/write | 0 = Closed; 1 = Open | ||||
| HR | 1352doc 41353 | Air Filter Type | INT16 | Read/write | 0 = Standard; 1 = High Efficiency | ||||
| HR | 65518doc 465519 | Modbus RX CRC Errors | UINT32 | ABCD | Read | ||||
| HR | 65520doc 465521 | Modbus RX Count | UINT32 | ABCD | Read | ||||
| HR | 65522doc 465523 | Modbus TX Count | UINT32 | ABCD | Read |
Notes on this map
- The map gives every block twice: a US-units copy (deg F, CFM, ft; Group Data at 0-72, Unit Data at 128-352) and a metric copy 1000 registers higher (deg C, L/s, m). Only the metric copy, the alarm block (512-598) and the Modbus counters are listed here; for US units subtract 1000 from the address.
- Per the map: 32-bit values (UINT32, INT32) are big-endian, most-significant word first; signed values and ENUMs are two's complement 16-bit; strings carry two characters per register, high byte first.
- '(Tenths)' values are scaled 0.1 and '(Hundredths)' values 0.01.
- Reads use function code 3 or 4; writes use function code 16, or 6 for single-register points.
- Reading a single reserved/undefined register returns an exception; a block read that starts on a valid register returns zeros for undefined ones. Reserved rows and the raw VFD alarm/warning status streams (1278, 1280) are left out.
- The map prints no date; 2017-03 is the PDF's own creation date (2017-03-08).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
What Modbus registers does the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) have?
This map lists 216 registers: 216 holding registers. 53 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints three columns: the Modicon number (40001 style), the absolute register in hex and the absolute register in decimal. The notes state that absolute register 0 is Modicon 40001 and is address zero on the wire, so the decimal column is the wire address (e.g. 41226 = wire 1225).
What byte order does the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)?
Start with HR 1206 Operating Mode (Operating mode); HR 1225 Supply Air Temperature (Supply air temperature); HR 1227 Return Air Temperature (Return air temperature); HR 1238 Rack Inlet Temperature 1 (Rack inlet temperature 1); HR 1235 Fan Speed (Fan speed); HR 1023 Group: Cool Setpoint (Group cool setpoint); HR 1000 Group: Overall Status (Overall status); HR 512 Internal Communication Error (First alarm flag (alarm block starts here)).
How do I enable Modbus control of the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)?
Not described in the register map.
Where is the official APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus documentation?
The source is Modbus Register Map: InRow ACRD60x / ACRC60x (990-5786A), revision 2017-03, published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_SJAN-A9L2ZC_EN.
More APC (Schneider Electric) Modbus register maps
- UPS
APC (Schneider Electric) Galaxy VL 200-500 kW three-phase UPS
Schneider Electric Galaxy VL 200-500 kW UPS with firmware 7.23 or later, per register map 990-6447.
Also known as: Galaxy VL, GVL, Galaxy VL 200 kW, Galaxy VL 500 kW - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - UPS
APC Smart-UPS / Smart-UPS VT / MGE Galaxy 3500 (NMC Modbus map 990-5702)
APC Smart-UPS (excluding SMT, SMX, SURTD and SRT prefixes), Smart-UPS VT and MGE Galaxy 3500 through Network Management Card AP9630/AP9631/AP9635 (TCP) or AP9635 (RTU), part number 990-5702.
Also known as: 990-5702, AP9630, AP9631, AP9635, Smart-UPS VT, MGE Galaxy 3500, Schneider Electric APC Smart-UPS - UPS
APC Symmetra PX 250/500 kW
APC Symmetra PX 250/500 kW three-phase UPS via Network Management Card AP9635, register map 990-3936D (firmware sypx510 to sypx516 changes listed in the source).
Also known as: 990-3936D, Symmetra PX 250 kW, Symmetra PX 500 kW, SYPX
Other hvac equipment register maps
- Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master - Rooftop unit / packaged wall-mount air conditioner
Eubank EAH / EGH wall-mount air conditioner control board (Modbus RTU)
Eubank EAH1020A-1060A, EGH1072A, EAH2024A-2060A and EGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: EAH1020A, EAH1024A, EAH1030A, EAH1036A, EAH1042A, EAH1048A, EAH1060A, EGH1072A, EAH2024A, EAH2030A, EAH2036A, EAH2042A, EAH2048A, EAH2060A, EGH2072A, Eubank EAH, Eubank EGH - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Air handler (enclosure air conditioner)
Seifert Systems Enclosure air conditioners (standard Modbus table)
Seifert Systems enclosure cooling units with Carel, Variable Speed or Seifert Standard controllers, per technical guide RDTG2001 rev 0.2 (09.02.2021).
Also known as: RDTG2001, Seifert enclosure cooling unit Modbus
All hvac equipment Modbus register maps →
Source: Modbus Register Map: InRow ACRD60x / ACRC60x · 990-5786A · rev. 2017-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.