Air handler (in-row data-centre cooling unit) · Modbus register map

APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus register map

Updated 19 November 2026

Short answer

The InRow ACRD60x and ACRC60x are in-row cooling units for data-centre rows and contained aisles. Their controller answers Modbus RTU and Modbus TCP with everything in holding registers. This map covers the cooling-group values (output, demand, setpoints, airflow), the unit's operating mode, supply/return/rack-inlet temperatures, humidity, fan speed, chilled-water and refrigerant readings, compressor VFD data, run hours, service settings, thresholds and 80-plus alarm flags.

This page lists 216 Modbus registers for the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) — 53 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from APC (Schneider Electric)’s own free documentation (linked below) and checked against it.

Manufacturer
APC (Schneider Electric)
Model
InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
Equipment type
Air handler (in-row data-centre cooling unit)
Registers
216 (53 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786
Source document
Modbus Register Map: InRow ACRD60x / ACRC60x · 990-5786A · rev. 2017-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)

Integration in brief

Read the unit operating mode (1206, ENUM) and the supply/return air temperatures (1225, 1227), rack inlet temperatures (1238-1243) and fan speed (1235), which are UINT32 values in tenths, high word first. Write the group cool setpoint at 1023 (tenths of deg C, two registers with function 16).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1206Operating ModeINT16Operating modeRead
HR 1225Supply Air TemperatureUINT32 ABCDSupply air temperatureRead
HR 1227Return Air TemperatureUINT32 ABCDReturn air temperatureRead
HR 1238Rack Inlet Temperature 1UINT32 ABCDRack inlet temperature 1Read
HR 1235Fan SpeedUINT32 ABCDFan speedRead
HR 1023Group: Cool SetpointUINT32 ABCDGroup cool setpointRead/write
HR 1000Group: Overall StatusINT16Overall statusRead
HR 512Internal Communication ErrorINT16First alarm flag (alarm block starts here)Read

Enable Modbus control & writes

Not described in the register map.

Byte order & addressing

Network setup

Watch out for

APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

216 of 216 shown
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR512doc 40513Internal Communication ErrorINT16Read0 = Clear; 1 = Alarm
HR513doc 40514A-link isolation relay fault existsINT16Read0 = Clear; 1 = Alarm
HR514doc 40515External communication faultINT16Read0 = Clear; 1 = Alarm
HR515doc 40516Cool Function UnavailableINT16Read0 = Clear; 1 = Alarm
HR516doc 40517Rack Inlet 1 High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR517doc 40518Rack Inlet 2 High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR518doc 40519Rack Inlet 3 High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR519doc 40520High Return Humidity ConditionINT16Read0 = Clear; 1 = Alarm
HR520doc 40521Low Return Humidity ConditionINT16Read0 = Clear; 1 = Alarm
HR521doc 40522Air Filter CloggedINT16Read0 = Clear; 1 = Alarm
HR522doc 40523Return Air Temperature Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR523doc 40524Upper Supply Air Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR524doc 40525Rack Temperature Sensor 1 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR525doc 40526Rack Temperature Sensor 2 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR526doc 40527Rack Temperature Sensor 3 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR527doc 40528Chilled Water Valve Actuator Error DetectedINT16Read0 = Clear; 1 = Alarm
HR528doc 40529High Discharge Pressure ConditionINT16Read0 = Clear; 1 = Alarm
HR529doc 40530Low Suction Pressure ConditionINT16Read0 = Clear; 1 = Alarm
HR530doc 40531High Suction Pressure ConditionINT16Read0 = Clear; 1 = Alarm
HR531doc 40532Humidifier Error Tolerance Exceed ConditionINT16Read0 = Clear; 1 = Alarm
HR532doc 40533Fan 1 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR533doc 40534Fan 2 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR534doc 40535Fan 3 Error DetectedINT16Read0 = Clear; 1 = Alarm
HR535doc 40536Water Detected ErrorINT16Read0 = Clear; 1 = Alarm
HR536doc 40537Check Condensate Management SystemINT16Read0 = Clear; 1 = Alarm
HR538doc 40539Humidifier High Water ConductivityINT16Read0 = Clear; 1 = Alarm
HR539doc 40540Humidifier Low Water ConditionINT16Read0 = Clear; 1 = Alarm
HR540doc 40541Humidifier Excessive Output Reduction ConditionINT16Read0 = Clear; 1 = Alarm
HR541doc 40542Humidifier Drain ErrorINT16Read0 = Clear; 1 = Alarm
HR542doc 40543Humidifier Cylinder Full Unit Off ConditionINT16Read0 = Clear; 1 = Alarm
HR543doc 40544Humidifier Replace Cylinder ConditionINT16Read0 = Clear; 1 = Alarm
HR544doc 40545Compressor Drive FailureINT16Read0 = Clear; 1 = Alarm
HR545doc 40546Compressor Drive WarningINT16Read0 = Clear; 1 = Alarm
HR546doc 40547Entering Chilled Water High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR547doc 40548Entering Chilled Water Temperature Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR548doc 40549Leaving Chilled Water Temperature Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR549doc 40550Primary Power Source UnavailableINT16Read0 = Clear; 1 = Alarm
HR550doc 40551Humidifier Communication ErrorINT16Read0 = Clear; 1 = Alarm
HR551doc 40552Compressor Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR552doc 40553Heater 1 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR553doc 40554Heater 2 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR554doc 40555Heater 3 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR555doc 40556Humidifier Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR556doc 40557Fan 1 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR557doc 40558Fan 2 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR558doc 40559Fan 3 Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR559doc 40560Air Filter Run Hours ViolationINT16Read0 = Clear; 1 = Alarm
HR560doc 40561Condensate Pump Runtime ConditionINT16Read0 = Clear; 1 = Alarm
HR561doc 40562Group Communication ErrorINT16Read0 = Clear; 1 = Alarm
HR562doc 40563Compressor Drive Communication ErrorINT16Read0 = Clear; 1 = Alarm
HR563doc 40564Supply Air High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR564doc 40565Return Air High Temperature ConditionINT16Read0 = Clear; 1 = Alarm
HR565doc 40566Filter Differential Pressure Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR567doc 40568Suction Pressure Sensor FailureINT16Read0 = Clear; 1 = Alarm
HR568doc 40569Discharge Pressure Sensor FailureINT16Read0 = Clear; 1 = Alarm
HR570doc 40571Standby Due to Input ContactINT16Read0 = Clear; 1 = Alarm
HR571doc 40572Supply Humidity Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR572doc 40573Return Humidity Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR573doc 40574Heater 1 ErrorINT16Read0 = Clear; 1 = Alarm
HR574doc 40575Heater 2 ErrorINT16Read0 = Clear; 1 = Alarm
HR575doc 40576Heater 3 ErrorINT16Read0 = Clear; 1 = Alarm
HR576doc 40577Compressor High Head ConditionINT16Read0 = Clear; 1 = Alarm
HR579doc 40580Lower Supply Air Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR581doc 40582Excessive Compressor Cycling ConditionINT16Read0 = Clear; 1 = Alarm
HR582doc 40583Persistent Compressor High Head ConditionINT16Read0 = Clear; 1 = Alarm
HR583doc 40584Chilled Water Flow Meter Error DetectedINT16Read0 = Clear; 1 = Alarm
HR584doc 40585Idle Due To Leak DetectedINT16Read0 = Clear; 1 = Alarm
HR585doc 40586Fluid Calibration ActiveINT16Read0 = Clear; 1 = Alarm
HR586doc 40587No Backup Units AvailableINT16Read0 = Clear; 1 = Alarm
HR587doc 40588EcoAisle Door OpenINT16Read0 = Clear; 1 = Alarm
HR588doc 40589Unexpected Number of Active Flow ControllersINT16Read0 = Clear; 1 = Alarm
HR589doc 40590Insufficient Airflow DetectedINT16Read0 = Clear; 1 = Alarm
HR590doc 40591Active Flow Controller Sensor Error DetectedINT16Read0 = Clear; 1 = Alarm
HR591doc 40592Condensate Pan FullINT16Read0 = Clear; 1 = Alarm
HR592doc 40593Compressor Drive LockedINT16Read0 = Clear; 1 = Alarm
HR593doc 40594VFD Inverter Over Heated ConditionINT16Read0 = Clear; 1 = Alarm
HR594doc 40595Persistent Low Suction Pressure ConditionINT16Read0 = Clear; 1 = Alarm
HR595doc 40596Unit Capability Not ConfiguredINT16Read0 = Clear; 1 = Alarm
HR596doc 40597Compressor Suction Sensor FaultINT16Read0 = Clear; 1 = Alarm
HR597doc 40598Low Superheat WarningINT16Read0 = Clear; 1 = Alarm
HR598doc 40599Low superheat CriticalINT16Read0 = Clear; 1 = Alarm
HR1000doc 41001Group: Overall StatusINT16Read0 = OK State; 1 = Info State; 2 = Warning State; 3 = Critical State
HR1001doc 41002Group Cool OutputUINT32ABCD× 0.1kWRead
HR1003doc 41004Group Cool DemandUINT32ABCD× 0.1kWRead
HR1005doc 41006Group Humidify OutputUINT32ABCD%Read
HR1007doc 41008Group Humidify DemandUINT32ABCD%Read
HR1009doc 41010Group Dehumidify OutputUINT32ABCD%Read
HR1011doc 41012Group Dehumidify DemandUINT32ABCD%Read
HR1013doc 41014Group Reheat OutputUINT32ABCD%Read
HR1015doc 41016Group Reheat DemandUINT32ABCD%Read
HR1017doc 41018Group AirflowUINT32ABCD× 0.1L/sRead
HR1019doc 41020Group Maximum Rack Inlet TemperatureUINT32ABCD× 0.1°CRead
HR1021doc 41022Group Minimum Rack Inlet TemperatureUINT32ABCD× 0.1°CRead
HR1023doc 41024Group: Cool SetpointUINT32ABCD× 0.1°CRead/write
HR1025doc 41026Group: Humidify SetpointUINT32ABCD× 0.1%RHRead/write
HR1027doc 41028Group: Dehumidify SetpointUINT32ABCD× 0.1%RHRead/write
HR1029doc 41030Group: Dehumidify DeadbandUINT32ABCD%RHRead/write
HR1031doc 41032Group: Reheat SetpointUINT32ABCD× 0.1°CRead/write
HR1033doc 41034Group: Supply Air SetpointUINT32ABCD× 0.1°CRead/write
HR1035doc 41036Group: Number of Units in GroupUINT32ABCDRead/write
HR1037doc 41038Group: Configuration TypeINT16Read0 = RACS; 1 = HACS; 2 = In-Row; 3 = CACS
HR1038doc 41039Group: Percent GlycolUINT32ABCD%Read
HR1040doc 41041Group: Cool Gain 'P'UINT32ABCD× 0.01Read
HR1042doc 41043Group: Cool Reset Rate 'I'UINT32ABCD× 0.01Read
HR1044doc 41045Group: Cool Derivative 'D'UINT32ABCD× 0.01Read
HR1046doc 41047Group: Humidify Sensitivity BandUINT32ABCD%RHRead/write
HR1048doc 41049Group: Reheat Gain (P)UINT32ABCD× 0.01Read
HR1050doc 41051Group: Reheat Integral (I)UINT32ABCD× 0.01Read
HR1052doc 41053Group: Reheat Derivative (D)UINT32ABCD× 0.01Read
HR1054doc 41055Group: Fan Speed PreferenceINT16Read/write0 = Low; 1 = Med-Low; 2 = Med; 3 = Med-High; 4 = High
HR1055doc 41056Group: Air Flow ControlINT16Read/write0 = Automatic; 1 = Manual
HR1056doc 41057Group: Number of Backup UnitsUINT32ABCDRead/write
HR1058doc 41059Group: Number of Precision UnitsUINT32ABCDRead/write
HR1060doc 41061Group: Load Assist EnableINT16Read/write0 = Disable; 1 = Enable
HR1061doc 41062Group: Run-Time Balancing EnableINT16Read/write0 = Disable; 1 = Enable
HR1062doc 41063Group: Maximum Fan SpeedUINT32ABCD%Read/write
HR1064doc 41065Group: AltitudeUINT32ABCDmRead/write
HR1066doc 41067Group: Number of Active Flow ControllersUINT32ABCDRead/write
HR1068doc 41069Group: Active Flow Control BiasINT16Read0 = Positive; 1 = Slightly Positive; 2 = Zero; 3 = Slightly Negative; 4 = Negative
HR1069doc 41070Group: Active Flow Control StatusINT16Read0 = Under; 1 = Okay; 2 = Over; 3 = NA
HR1070doc 41071Group: Active Flow Control Lamp TestINT16Read/write0 = Off; 1 = On
HR1071doc 41072Group: Dew Point TemperatureINT32ABCD× 0.1°CRead
HR1128doc 41129Unit NameSTRING[42]Read/write
HR1149doc 41150LocationSTRING[42]Read/write
HR1170doc 41171Unit IDUINT32ABCDRead
HR1172doc 41173Model NumberSTRING[20]Read
HR1182doc 41183Serial NumberSTRING[20]Read
HR1192doc 41193Firmware RevisionSTRING[8]Read
HR1196doc 41197Hardware RevisionSTRING[8]Read
HR1200doc 41201Manufacturing DateSTRING[12]Read
HR1206doc 41207Operating ModeINT16Read0 = Standby; 1 = On; 2 = Idle; 3 = Prestart; 4 = Backup; 5 = Load Assist
HR1207doc 41208Cool OutputUINT32ABCD× 0.1kWRead
HR1209doc 41210Cool DemandUINT32ABCD× 0.1kWRead
HR1211doc 41212Humidify OutputUINT32ABCD%Read
HR1213doc 41214Humidify DemandUINT32ABCD%Read
HR1215doc 41216Dehumidify OutputUINT32ABCD%Read
HR1217doc 41218Dehumidify DemandUINT32ABCD%Read
HR1219doc 41220Reheat OutputUINT32ABCD%Read
HR1221doc 41222Reheat DemandUINT32ABCD%Read
HR1223doc 41224Unit Maximum Rack Inlet TemperatureUINT32ABCD× 0.1°CRead
HR1225doc 41226Supply Air TemperatureUINT32ABCD× 0.1°CRead
HR1227doc 41228Return Air TemperatureUINT32ABCD× 0.1°CRead
HR1229doc 41230Supply HumidityUINT32ABCD× 0.1%RHRead
HR1231doc 41232Return HumidityUINT32ABCD× 0.1%RHRead
HR1233doc 41234AirflowUINT32ABCD× 0.1L/sRead
HR1235doc 41236Fan SpeedUINT32ABCD× 0.1%Read
HR1237doc 41238Active Power SourceINT16Read0 = Primary; 1 = Secondary
HR1238doc 41239Rack Inlet Temperature 1UINT32ABCD× 0.1°CRead
HR1240doc 41241Rack Inlet Temperature 2UINT32ABCD× 0.1°CRead
HR1242doc 41243Rack Inlet Temperature 3UINT32ABCD× 0.1°CRead
HR1244doc 41245Filter Differential PressureUINT32ABCD× 0.1PaRead
HR1248doc 41249Humidifier CurrentUINT32ABCD× 0.1ARead
HR1250doc 41251Humidifier Water ConductivityUINT32ABCDuS/cmRead
HR1252doc 41253CW Valve PositionUINT32ABCD%Read
HR1254doc 41255CW Fluid FlowUINT32ABCD× 0.1L/sRead
HR1256doc 41257Entering Fluid TemperatureUINT32ABCD× 0.1°CRead
HR1258doc 41259Leaving Fluid TemperatureUINT32ABCD× 0.1°CRead
HR1260doc 41261Suction PressureUINT32ABCD× 0.1kPaRead
HR1262doc 41263Discharge PressureUINT32ABCD× 0.1kPaRead
HR1264doc 41265VFD SpeedUINT32ABCD× 0.1HzRead
HR1266doc 41267VFD PowerUINT32ABCD× 0.01kWRead
HR1268doc 41269VFD Motor VoltageUINT32ABCD× 0.1VRead
HR1270doc 41271VFD Motor CurrentUINT32ABCD× 0.01ARead
HR1272doc 41273VFD DC Link VoltageUINT32ABCDVRead
HR1274doc 41275VFD Heat Sink TemperatureUINT32ABCD× 0.1°CRead
HR1276doc 41277VFD Control Card TemperatureUINT32ABCD× 0.1°CRead
HR1282doc 41283Air Filter Run HoursUINT32ABCDhrRead
HR1284doc 41285Fan 1 Run HoursUINT32ABCDhrRead
HR1286doc 41287Fan 2 Run HoursUINT32ABCDhrRead
HR1288doc 41289Fan 3 Run HoursUINT32ABCDhrRead
HR1290doc 41291Compressor Run HoursUINT32ABCDhrRead
HR1292doc 41293Humidifier Run HoursUINT32ABCDhrRead
HR1294doc 41295Heater 1 Run HoursUINT32ABCDhrRead
HR1296doc 41297Heater 2 Run HoursUINT32ABCDhrRead
HR1298doc 41299Heater 3 Run HoursUINT32ABCDhrRead
HR1300doc 41301Condensate Pump Run HoursUINT32ABCDhrRead
HR1302doc 41303Air Filter Service IntervalUINT32ABCDweeksRead/write
HR1304doc 41305Air Filter Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1305doc 41306Humidifier Service Alarm IntervalUINT32ABCDweeksRead/write
HR1307doc 41308Humidifier Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1308doc 41309Heater Service Alarm IntervalUINT32ABCDweeksRead/write
HR1310doc 41311Heater Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1311doc 41312Compressor Service Alarm IntervalUINT32ABCDweeksRead/write
HR1313doc 41314Compressor Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1314doc 41315Fans Service Alarm IntervalUINT32ABCDweeksRead/write
HR1316doc 41317Fans Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1317doc 41318Condensate Pump Service Alarm IntervalUINT32ABCDweeksRead/write
HR1319doc 41320Condensate Pump Service Alarm EnableINT16Read/write0 = Enable; 1 = Disable
HR1320doc 41321Rack Inlet Temperature High ThresholdUINT32ABCD× 0.1°CRead/write
HR1322doc 41323Supply Air Temperature High ThresholdUINT32ABCD× 0.1°CRead/write
HR1324doc 41325Return Air Temperature High ThresholdUINT32ABCD× 0.1°CRead/write
HR1326doc 41327CW Entering Temp High ThresholdUINT32ABCD× 0.1°CRead/write
HR1328doc 41329Return Humidity High ThresholdUINT32ABCD× 0.1%RHRead/write
HR1330doc 41331Return Humidity Low ThresholdUINT32ABCD× 0.1%RHRead/write
HR1332doc 41333Startup DelayUINT32ABCDsecRead/write
HR1334doc 41335Cool CapacityINT16Read/write0 = Automatic; 1 = Maximum
HR1335doc 41336Idle on Leak DetectINT16Read/write0 = Yes; 1 = No
HR1336doc 41337Standby Input Normal StateINT16Read/write0 = Open; 1 = Closed
HR1337doc 41338Standby Input StateINT16Read0 = Open; 1 = Closed
HR1338doc 41339Output Normal StateINT16Read/write0 = Open; 1 = Closed
HR1339doc 41340Output StateINT16Read0 = Open; 1 = Closed
HR1340doc 41341Output SourceINT16Read0 = Any Alarm; 1 = Only Critical Alarms
HR1341doc 41342Humidify EnableINT16Read/write0 = Enable; 1 = Disable
HR1342doc 41343Humidifier ControlINT16Read/write1 = Auto; 2 = Drain
HR1343doc 41344Dehumidify EnableINT16Read/write0 = Disable; 1 = Enable
HR1344doc 41345Reheat EnableINT16Read/write0 = Enable; 1 = Disable
HR1345doc 41346Heat Assist EnableINT16Read/write0 = Disable; 1 = Enable
HR1346doc 41347Power SourceINT16Read/write0 = Single; 1 = Dual
HR1347doc 41348Unit Role OverrideINT16Read/write0 = Automatic; 1 = Forced On
HR1348doc 41349System Run HoursUINT32ABCDhrRead
HR1350doc 41351Secondary Power Feed CapabilityINT16Read/write0 = FullPower; 1 = ReducedPower
HR1351doc 41352Bypass Valve PositionINT16Read/write0 = Closed; 1 = Open
HR1352doc 41353Air Filter TypeINT16Read/write0 = Standard; 1 = High Efficiency
HR65518doc 465519Modbus RX CRC ErrorsUINT32ABCDRead
HR65520doc 465521Modbus RX CountUINT32ABCDRead
HR65522doc 465523Modbus TX CountUINT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)

What Modbus registers does the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) have?

This map lists 216 registers: 216 holding registers. 53 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints three columns: the Modicon number (40001 style), the absolute register in hex and the absolute register in decimal. The notes state that absolute register 0 is Modicon 40001 and is address zero on the wire, so the decimal column is the wire address (e.g. 41226 = wire 1225).

What byte order does the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)?

Start with HR 1206 Operating Mode (Operating mode); HR 1225 Supply Air Temperature (Supply air temperature); HR 1227 Return Air Temperature (Return air temperature); HR 1238 Rack Inlet Temperature 1 (Rack inlet temperature 1); HR 1235 Fan Speed (Fan speed); HR 1023 Group: Cool Setpoint (Group cool setpoint); HR 1000 Group: Overall Status (Overall status); HR 512 Internal Communication Error (First alarm flag (alarm block starts here)).

How do I enable Modbus control of the APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)?

Not described in the register map.

Where is the official APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786) Modbus documentation?

The source is Modbus Register Map: InRow ACRD60x / ACRC60x (990-5786A), revision 2017-03, published free by APC (Schneider Electric) at https://download.se.com/files?p_Doc_Ref=SPD_SJAN-A9L2ZC_EN.