- Enclosure air conditioners (standard Modbus table)
Air handler (enclosure air conditioner) · Modbus register map
Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus register map
Updated 17 November 2026
Seifert enclosure air conditioners share one Modbus RTU holding-register table across their controller families. Setpoints and temperatures are signed 16-bit values in tenths of a degree, speeds are plain integers, and state, alarm, output and door-contact information are bit fields. Writing the enable-flags register switches the unit from its potentiometer setpoints to network setpoints.
This page lists 29 Modbus registers for the Seifert Systems Enclosure air conditioners (standard Modbus table) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seifert Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seifert Systems
- Model
- Enclosure air conditioners (standard Modbus table)
- Equipment type
- Air handler (enclosure air conditioner)
- Registers
- 29 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- RDTG2001, Seifert enclosure cooling unit Modbus
Integration notes: Seifert Systems Enclosure air conditioners (standard Modbus table)
Poll holding registers 0-27 with function 03. Set bit 0 of register 4 to use network setpoints, then write the setpoints (tenths of a degree) to registers 0-3.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 12 | READ_CONTROL_SENSOR | INT16 | Internal (control) temperature | Read |
| HR 13 | READ_STATE | UINT16 | Operating state | Read |
| HR 14 | READ_ALARM_STATUS | BITMAP16 | Alarm bits | Read |
| HR 15 | READ_OUTPUT_STATUS | BITMAP16 | Output status | Read |
| HR 16 | READ_CONTACT_STATUS | BITMAP16 | Door contacts | Read |
| HR 0 | SET_NETWORK_COOLING_SETPOINT | INT16 | Network cooling setpoint | Read/write |
| HR 4 | SET_ENABLE_FLAGS | BITMAP16 | Enable flags (network setpoints) | Read/write |
Enable Modbus control & writes
Write register 4 (SET_ENABLE_FLAGS) with bit 0 set using function 06 so the controller uses Modbus setpoints instead of its potentiometers (not available on Carel-controller units).
Byte order & addressing
- Register 4 cannot be written with function 16 (write multiple); use function 06.
- Setting any undocumented bit in register 4 returns exception 03.
Network setup
- Defaults: unit address 1, 19200 baud, 8 data bits, even parity, 1 stop bit.
- To change the address write 0x0ADD to register 40, then the new address within 10 seconds.
Watch out for
- Switching the temperature unit changes every temperature register; set it before writing setpoints.
Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | SET_NETWORK_COOLING_SETPOINT | Cooling setpoint written by the network. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1 | SET_NETWORK_HIGH_TEMP_ALARM_SETPOINT | High-temperature alarm setpoint from the network. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2 | SET_NETWORK_LOW_TEMP_ALARM_SETPOINT | Low-temperature alarm setpoint from the network. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3 | SET_NETWORK_HEATER_SETPOINT | Heater setpoint from the network. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4 | SET_ENABLE_FLAGS | Write with function 06 only; undefined bits return exception 03. | BITMAP16 | Read/write | bit 0 = EN_NETWORK_SETPOINTS: 1 = use Modbus setpoints, 0 = onboard potentiometers (not on Carel units); bit 8 = EN_INPUT1_INVERT: 1 = unit off when door contact closed, 0 = off when open; bit 10 = EN_LOCK_KEYPAD: 1 = keypad disabled (units with display); bit 11 = EN_TEMP_UNIT: 1 = Fahrenheit, 0 = Celsius | |||
| HR | 5 | READ_CONTROL_SETPOINT | Control setpoint in use (network or onboard potentiometer). | INT16 | × 0.1 | °C | Read | ||
| HR | 6 | READ_HIGH_TEMP_SETPOINT | High alarm setpoint in use. | INT16 | × 0.1 | °C | Read | ||
| HR | 7 | READ_LOW_TEMP_SETPOINT | Low alarm setpoint in use (network only). | INT16 | × 0.1 | °C | Read | ||
| HR | 8 | READ_HEATER_SETPOINT | Heater setpoint in use. | INT16 | × 0.1 | °C | Read | ||
| HR | 9 | READ_TEMP_POT | Control setpoint potentiometer reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 10 | READ_ALARM_POT | High alarm setpoint potentiometer reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 11 | READ_HEATER_POT | Heater setpoint potentiometer reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 12 | READ_CONTROL_SENSOR | Sensor value used as the internal temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 13 | READ_STATE | Unit operating mode. | UINT16 | Read | 0 = Off (all outputs off); 1 = Idle (internal blower on); 2 = Cooling (blowers and compressor on); 3 = Heating (internal blower and heater on); 4 = Testing | |||
| HR | 14 | READ_ALARM_STATUS | 1 = alarm active. Some bits apply only to certain controller types. | BITMAP16 | Read | bit 0 = High internal temperature; bit 1 = Low internal temperature; bit 2 = Compressor failure (pressure pipe algorithm); bit 3 = Faulty ambient sensor; bit 4 = Faulty auxiliary sensor; bit 5 = Faulty icing sensor (S1); bit 6 = Faulty internal temperature sensor; bit 7 = Carel/inverter communication failure; bit 8 = Phase failure (3-phase units); bit 9 = Alarm compressor; bit 10 = Alarm ambient blower; bit 11 = Alarm internal blower; bit 12 = Warning compressor; bit 13 = Warning ambient blower; bit 14 = Warning internal blower; bit 15 = Alarm delta outlet-inlet temperature | |||
| HR | 15 | READ_OUTPUT_STATUS | 1 = output on. | BITMAP16 | Read | bit 0 = Heater; bit 1 = Internal blower; bit 2 = Ambient blower; bit 3 = Compressor | |||
| HR | 16 | READ_CONTACT_STATUS | 1 = door contact open, 0 = closed. | BITMAP16 | Read | bit 0 = Door contact 1; bit 1 = Door contact 2; bit 2 = Door contact 3 | |||
| HR | 17 | READ_INTERNAL_AIR_OUTLET_TEMP | Internal outlet sensor reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 18 | READ_AMBIENT_TEMP | Ambient sensor reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 19 | READ_ACTUAL_SPEED_INT_BLOWER | Actual internal blower speed. | UINT16 | rpm | Read | |||
| HR | 20 | READ_ACTUAL_SPEED_AMB_BLOWER | Actual ambient blower speed. | UINT16 | rpm | Read | |||
| HR | 21 | READ_ACTUAL_SPEED_COMPRESSOR | Actual compressor speed (revolutions per second). | UINT16 | rps | Read | |||
| HR | 22 | READ_SET_SPEED_INT_BLOWER | Commanded internal blower speed. | UINT16 | rpm | Read | |||
| HR | 23 | READ_SET_SPEED_AMB_BLOWER | Commanded ambient blower speed. | UINT16 | rpm | Read | |||
| HR | 24 | READ_SET_SPEED_COMPRESSOR | Commanded compressor speed, percent of maximum. | UINT16 | % | Read | |||
| HR | 25 | READ_ALARM_INT_BLOWER | Inverter alarm code, internal blower. | UINT16 | Read | ||||
| HR | 26 | READ_ALARM_AMB_BLOWER | Inverter alarm code, ambient blower. | UINT16 | Read | ||||
| HR | 27 | READ_ALARM_COMPRESSOR | Inverter alarm code, compressor. | UINT16 | Read | ||||
| HR | 40 | SET_UNIT_ADDRESS | Write 0x0ADD, then the new address within 10 s. | UINT16 | Read/write |
Notes on this map
- Source host: Seifert does not publish this table on its own site; the copy used is the Seifert document hosted by distributor AutomationDirect.
- Every register is 16-bit. S = signed, U = unsigned; a factor of 10 means the raw value is tenths (send 315 for 31.5).
- Temperatures are in Celsius unless EN_TEMP_UNIT (bit 11 of register 4) selects Fahrenheit, which changes both the Modbus values and the display.
- The document has a per-register availability chart for Unit A (Carel controller), Unit B (Variable Speed controller) and Unit C (Seifert Standard controller); check it, as not every register exists on every unit.
- Address 0xFF is a broadcast address the unit always answers; 0x00 and 0xFF cannot be set as the unit address.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seifert Systems Enclosure air conditioners (standard Modbus table)
What Modbus registers does the Seifert Systems Enclosure air conditioners (standard Modbus table) have?
This map lists 29 registers: 29 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table numbers registers from 0 (cooling setpoint) to 27, plus 40 for the address register. A register numbered 0 can only be a protocol address, so the printed numbers are used as wire addresses.
What are the minimum Modbus registers to integrate the Seifert Systems Enclosure air conditioners (standard Modbus table)?
Start with HR 12 READ_CONTROL_SENSOR (Internal (control) temperature); HR 13 READ_STATE (Operating state); HR 14 READ_ALARM_STATUS (Alarm bits); HR 15 READ_OUTPUT_STATUS (Output status); HR 16 READ_CONTACT_STATUS (Door contacts); HR 0 SET_NETWORK_COOLING_SETPOINT (Network cooling setpoint); HR 4 SET_ENABLE_FLAGS (Enable flags (network setpoints)).
How do I enable Modbus control of the Seifert Systems Enclosure air conditioners (standard Modbus table)?
Write register 4 (SET_ENABLE_FLAGS) with bit 0 set using function 06 so the controller uses Modbus setpoints instead of its potentiometers (not available on Carel-controller units).
Where is the official Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus documentation?
The source is R&D Technical Guide: Standard Modbus Table (RDTG2001 Rev 0.2), revision 2021-02-09. Seifert Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/seifertac/modbustable.pdf. It may be an older revision, so check it against the live unit.
Other hvac equipment register maps
- Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6) - Air handler (heat recovery ventilation unit)
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Airflow Entro-V MVHR units with the Entro-V control board (Basic controller 90001308 / Digital controller 90001299), per controls manual 80001022 Issue 1 (08/20).
Also known as: Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical
All hvac equipment Modbus register maps →
Source: R&D Technical Guide: Standard Modbus Table · RDTG2001 Rev 0.2 · rev. 2021-02-09 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.