Air handler (enclosure air conditioner) · Modbus register map

Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus register map

Updated 17 November 2026

Short answer

Seifert enclosure air conditioners share one Modbus RTU holding-register table across their controller families. Setpoints and temperatures are signed 16-bit values in tenths of a degree, speeds are plain integers, and state, alarm, output and door-contact information are bit fields. Writing the enable-flags register switches the unit from its potentiometer setpoints to network setpoints.

This page lists 29 Modbus registers for the Seifert Systems Enclosure air conditioners (standard Modbus table) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seifert Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Seifert Systems
Model
Enclosure air conditioners (standard Modbus table)
Equipment type
Air handler (enclosure air conditioner)
Registers
29 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
RDTG2001, Seifert enclosure cooling unit Modbus
Source document
R&D Technical Guide: Standard Modbus Table · RDTG2001 Rev 0.2 · rev. 2021-02-09 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seifert Systems Enclosure air conditioners (standard Modbus table)

Integration in brief

Poll holding registers 0-27 with function 03. Set bit 0 of register 4 to use network setpoints, then write the setpoints (tenths of a degree) to registers 0-3.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 12READ_CONTROL_SENSORINT16Internal (control) temperatureRead
HR 13READ_STATEUINT16Operating stateRead
HR 14READ_ALARM_STATUSBITMAP16Alarm bitsRead
HR 15READ_OUTPUT_STATUSBITMAP16Output statusRead
HR 16READ_CONTACT_STATUSBITMAP16Door contactsRead
HR 0SET_NETWORK_COOLING_SETPOINTINT16Network cooling setpointRead/write
HR 4SET_ENABLE_FLAGSBITMAP16Enable flags (network setpoints)Read/write

Enable Modbus control & writes

Write register 4 (SET_ENABLE_FLAGS) with bit 0 set using function 06 so the controller uses Modbus setpoints instead of its potentiometers (not available on Carel-controller units).

Byte order & addressing

Network setup

Watch out for

Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0SET_NETWORK_COOLING_SETPOINTCooling setpoint written by the network.INT16× 0.1°CRead/write
HR1SET_NETWORK_HIGH_TEMP_ALARM_SETPOINTHigh-temperature alarm setpoint from the network.INT16× 0.1°CRead/write
HR2SET_NETWORK_LOW_TEMP_ALARM_SETPOINTLow-temperature alarm setpoint from the network.INT16× 0.1°CRead/write
HR3SET_NETWORK_HEATER_SETPOINTHeater setpoint from the network.INT16× 0.1°CRead/write
HR4SET_ENABLE_FLAGSWrite with function 06 only; undefined bits return exception 03.BITMAP16Read/writebit 0 = EN_NETWORK_SETPOINTS: 1 = use Modbus setpoints, 0 = onboard potentiometers (not on Carel units); bit 8 = EN_INPUT1_INVERT: 1 = unit off when door contact closed, 0 = off when open; bit 10 = EN_LOCK_KEYPAD: 1 = keypad disabled (units with display); bit 11 = EN_TEMP_UNIT: 1 = Fahrenheit, 0 = Celsius
HR5READ_CONTROL_SETPOINTControl setpoint in use (network or onboard potentiometer).INT16× 0.1°CRead
HR6READ_HIGH_TEMP_SETPOINTHigh alarm setpoint in use.INT16× 0.1°CRead
HR7READ_LOW_TEMP_SETPOINTLow alarm setpoint in use (network only).INT16× 0.1°CRead
HR8READ_HEATER_SETPOINTHeater setpoint in use.INT16× 0.1°CRead
HR9READ_TEMP_POTControl setpoint potentiometer reading.INT16× 0.1°CRead
HR10READ_ALARM_POTHigh alarm setpoint potentiometer reading.INT16× 0.1°CRead
HR11READ_HEATER_POTHeater setpoint potentiometer reading.INT16× 0.1°CRead
HR12READ_CONTROL_SENSORSensor value used as the internal temperature.INT16× 0.1°CRead
HR13READ_STATEUnit operating mode.UINT16Read0 = Off (all outputs off); 1 = Idle (internal blower on); 2 = Cooling (blowers and compressor on); 3 = Heating (internal blower and heater on); 4 = Testing
HR14READ_ALARM_STATUS1 = alarm active. Some bits apply only to certain controller types.BITMAP16Readbit 0 = High internal temperature; bit 1 = Low internal temperature; bit 2 = Compressor failure (pressure pipe algorithm); bit 3 = Faulty ambient sensor; bit 4 = Faulty auxiliary sensor; bit 5 = Faulty icing sensor (S1); bit 6 = Faulty internal temperature sensor; bit 7 = Carel/inverter communication failure; bit 8 = Phase failure (3-phase units); bit 9 = Alarm compressor; bit 10 = Alarm ambient blower; bit 11 = Alarm internal blower; bit 12 = Warning compressor; bit 13 = Warning ambient blower; bit 14 = Warning internal blower; bit 15 = Alarm delta outlet-inlet temperature
HR15READ_OUTPUT_STATUS1 = output on.BITMAP16Readbit 0 = Heater; bit 1 = Internal blower; bit 2 = Ambient blower; bit 3 = Compressor
HR16READ_CONTACT_STATUS1 = door contact open, 0 = closed.BITMAP16Readbit 0 = Door contact 1; bit 1 = Door contact 2; bit 2 = Door contact 3
HR17READ_INTERNAL_AIR_OUTLET_TEMPInternal outlet sensor reading.INT16× 0.1°CRead
HR18READ_AMBIENT_TEMPAmbient sensor reading.INT16× 0.1°CRead
HR19READ_ACTUAL_SPEED_INT_BLOWERActual internal blower speed.UINT16rpmRead
HR20READ_ACTUAL_SPEED_AMB_BLOWERActual ambient blower speed.UINT16rpmRead
HR21READ_ACTUAL_SPEED_COMPRESSORActual compressor speed (revolutions per second).UINT16rpsRead
HR22READ_SET_SPEED_INT_BLOWERCommanded internal blower speed.UINT16rpmRead
HR23READ_SET_SPEED_AMB_BLOWERCommanded ambient blower speed.UINT16rpmRead
HR24READ_SET_SPEED_COMPRESSORCommanded compressor speed, percent of maximum.UINT16%Read
HR25READ_ALARM_INT_BLOWERInverter alarm code, internal blower.UINT16Read
HR26READ_ALARM_AMB_BLOWERInverter alarm code, ambient blower.UINT16Read
HR27READ_ALARM_COMPRESSORInverter alarm code, compressor.UINT16Read
HR40SET_UNIT_ADDRESSWrite 0x0ADD, then the new address within 10 s.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seifert Systems Enclosure air conditioners (standard Modbus table)

What Modbus registers does the Seifert Systems Enclosure air conditioners (standard Modbus table) have?

This map lists 29 registers: 29 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table numbers registers from 0 (cooling setpoint) to 27, plus 40 for the address register. A register numbered 0 can only be a protocol address, so the printed numbers are used as wire addresses.

What are the minimum Modbus registers to integrate the Seifert Systems Enclosure air conditioners (standard Modbus table)?

Start with HR 12 READ_CONTROL_SENSOR (Internal (control) temperature); HR 13 READ_STATE (Operating state); HR 14 READ_ALARM_STATUS (Alarm bits); HR 15 READ_OUTPUT_STATUS (Output status); HR 16 READ_CONTACT_STATUS (Door contacts); HR 0 SET_NETWORK_COOLING_SETPOINT (Network cooling setpoint); HR 4 SET_ENABLE_FLAGS (Enable flags (network setpoints)).

How do I enable Modbus control of the Seifert Systems Enclosure air conditioners (standard Modbus table)?

Write register 4 (SET_ENABLE_FLAGS) with bit 0 set using function 06 so the controller uses Modbus setpoints instead of its potentiometers (not available on Carel-controller units).

Where is the official Seifert Systems Enclosure air conditioners (standard Modbus table) Modbus documentation?

The source is R&D Technical Guide: Standard Modbus Table (RDTG2001 Rev 0.2), revision 2021-02-09. Seifert Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/seifertac/modbustable.pdf. It may be an older revision, so check it against the live unit.