- DucoBox ventilation units / IQ unit (Modbus RTU, master node)
Air handler (demand-controlled ventilation unit) · Modbus register map
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus register map
Updated 19 November 2026
Duco residential and light-commercial ventilation systems expose each network component (the DucoBox itself, control valves, sensors, user controls, window ventilators) as a Modbus 'node'. Registers are numbered node x 10 + parameter, with up to ten 16-bit input (read) and ten holding (write) parameters per node. This map lists the DucoBox master node (node 1, registers 10-19): system status, ventilation level and power, plus the system override, auto min/max and action registers.
This page lists 11 Modbus registers for the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Duco’s own free documentation (linked below) and checked against it.
- Manufacturer
- Duco
- Model
- DucoBox ventilation units / IQ unit (Modbus RTU, master node)
- Equipment type
- Air handler (demand-controlled ventilation unit)
- Registers
- 11 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009
- Source document
- Information sheet ModBus RTU · L8000009-B · rev. 2023-02-23
Integration notes: Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
Read input 11-12 for the system status and ventilation level. Control either with holding 10 (target %, -1 to release) or holding 19 (Action, simulates a button press so user controls stay in step).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 11 | Status | UINT16 | System status | Read |
| IR 12 | Ventilation position | UINT16 | Ventilation level % | Read |
| IR 13 | Current power | UINT16 | Current power | Read |
| HR 10 | Target value | INT16 | Target value override | Read/write |
| HR 19 | Action | UINT16 | Action (manual/auto) | Read/write |
| HR 15 | Auto min. | UINT16 | Auto minimum | Read/write |
Enable Modbus control & writes
Fit the Communication Print option (DucoBox) or use the IQ unit's built-in port; set the Modbus address in the display menu or Duco Network Tool.
Byte order & addressing
- Addresses are node x 10 + parameter; read node numbers from the Duco Network Tool.
- If the master reads values shifted by one register, set RegOffs = 1 in the Duco display menu.
Network setup
- Default serial settings 9600 baud, 8 data bits, no parity, 1 stop bit; change in the display menu.
Watch out for
- A target value left set overrides the zone and user controls no longer show the true setting; write -1 to release it.
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10 | Type of Module | 10 = DucoBox (master unit). | UINT16 | Read | 10 = DucoBox / master unit | |||
| IR | 11 | Status | Active ventilation setting of the whole system. | UINT16 | Read | 0 = Auto; 1 = 10 minutes in high setting; 2 = 20 minutes in high setting; 3 = 30 minutes in high setting; 4 = Manual low setting; 5 = Manual medium setting; 6 = Manual high setting; 7 = Nobody home / unoccupied; 8 = Permanent low position; 9 = Permanent middle position; 10 = Permanent high position; 99 = Error | |||
| IR | 12 | Ventilation position | Actual ventilation level of the whole system. | UINT16 | % | Read | |||
| IR | 13 | Current power | UINT16 | W | Read | ||||
| IR | 14 | Average power | UINT16 | W | Read | ||||
| IR | 15 | Maximum power | UINT16 | W | Read | ||||
| IR | 19 | Localisation number | Group number of components that belong together. | UINT16 | Read | ||||
| HR | 10 | Target value | Overrides the system ventilation level, 0-100 % in steps of 5; -1 = override off (default). | INT16 | % | Read/write | |||
| HR | 15 | Auto min. | Minimum level in automatic mode, 0-100 % in steps of 5 (default 10 %). | UINT16 | % | Read/write | |||
| HR | 16 | Auto max. | Maximum level in automatic mode, 0-100 % in steps of 5 (default 100 %). | UINT16 | % | Read/write | |||
| HR | 19 | Action | Simulates a user-control press for the zone. | UINT16 | Read/write | 0 = Node display off; 1 = Node display on; 2 = Zone to temporary manual setting 1; 3 = Zone to temporary manual setting 2; 4 = Zone to temporary manual setting 3; 5 = Zone to automatic setting; 6 = Nobody home / unoccupied setting |
Notes on this map
- Only the DucoBox master node (node 1) is listed because every other component's registers depend on the node number the installer's network assigns. For any component, input and holding register = node x 10 + parameter (parameter 0-9).
- Common per-component parameters (from the sheet): input 0 type of module, 1 status, 2 ventilation position %, 9 localisation number; holding 0 target value % (-1 = off), 9 action. Sensor nodes add indoor temperature (°C x 10), CO2 (ppm) or RH (% x 100) in the input block.
- Input register Status values differ from the Action values (manual low is 4 in Status but 2 in Action).
- Target value (holding 10) is typed INT16 because -1 turns the override off.
- All registers are 16-bit. Supported functions: 03, 04, 06, 16.
- The Modbus slave address is set in the display menu or the Duco Network Tool; its default is not stated in this sheet.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
What Modbus registers does the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) have?
This map lists 11 registers: 7 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Duco numbers registers as node number followed by parameter number (node 1 parameter 0 = 10, node 7 parameter 2 = 72). The sheet says its implementation follows the official Modbus specification, so the printed number is the address sent on the wire; masters that subtract one (reading 19 for 20) can be compensated with the RegOffs parameter set to 1.
What are the minimum Modbus registers to integrate the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)?
Start with IR 11 Status (System status); IR 12 Ventilation position (Ventilation level %); IR 13 Current power (Current power); HR 10 Target value (Target value override); HR 19 Action (Action (manual/auto)); HR 15 Auto min. (Auto minimum).
How do I enable Modbus control of the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)?
Fit the Communication Print option (DucoBox) or use the IQ unit's built-in port; set the Modbus address in the display menu or Duco Network Tool.
Where is the official Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus documentation?
The source is Information sheet ModBus RTU (L8000009-B), revision 2023-02-23, published free by Duco at https://www.duco.eu/Wes/CDN/1/Attachments/information-sheet-ModBus-RTU-(en)_638328128583726330.pdf.
Other hvac equipment register maps
- Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1 - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller
All hvac equipment Modbus register maps →
Source: Information sheet ModBus RTU · L8000009-B · rev. 2023-02-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.