Easy Modbus
  1. Home
  2. Modbus register maps
  3. Duco
  4. DucoBox ventilation units / IQ unit (Modbus RTU, master node)

Air handler (demand-controlled ventilation unit) · Modbus register map

Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus register map

Updated 19 November 2026

Short answer

Duco residential and light-commercial ventilation systems expose each network component (the DucoBox itself, control valves, sensors, user controls, window ventilators) as a Modbus 'node'. Registers are numbered node x 10 + parameter, with up to ten 16-bit input (read) and ten holding (write) parameters per node. This map lists the DucoBox master node (node 1, registers 10-19): system status, ventilation level and power, plus the system override, auto min/max and action registers.

This page lists 11 Modbus registers for the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Duco’s own free documentation (linked below) and checked against it.

Manufacturer
Duco
Model
DucoBox ventilation units / IQ unit (Modbus RTU, master node)
Equipment type
Air handler (demand-controlled ventilation unit)
Registers
11 (4 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009
Source document
Information sheet ModBus RTU · L8000009-B · rev. 2023-02-23
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)

Integration in brief

Read input 11-12 for the system status and ventilation level. Control either with holding 10 (target %, -1 to release) or holding 19 (Action, simulates a button press so user controls stay in step).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 11StatusUINT16System statusRead
IR 12Ventilation positionUINT16Ventilation level %Read
IR 13Current powerUINT16Current powerRead
HR 10Target valueINT16Target value overrideRead/write
HR 19ActionUINT16Action (manual/auto)Read/write
HR 15Auto min.UINT16Auto minimumRead/write

Enable Modbus control & writes

Fit the Communication Print option (DucoBox) or use the IQ unit's built-in port; set the Modbus address in the display menu or Duco Network Tool.

Byte order & addressing

Network setup

Watch out for

Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

11 of 11 shown
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10Type of Module10 = DucoBox (master unit).UINT16Read10 = DucoBox / master unit
IR11StatusActive ventilation setting of the whole system.UINT16Read0 = Auto; 1 = 10 minutes in high setting; 2 = 20 minutes in high setting; 3 = 30 minutes in high setting; 4 = Manual low setting; 5 = Manual medium setting; 6 = Manual high setting; 7 = Nobody home / unoccupied; 8 = Permanent low position; 9 = Permanent middle position; 10 = Permanent high position; 99 = Error
IR12Ventilation positionActual ventilation level of the whole system.UINT16%Read
IR13Current powerUINT16WRead
IR14Average powerUINT16WRead
IR15Maximum powerUINT16WRead
IR19Localisation numberGroup number of components that belong together.UINT16Read
HR10Target valueOverrides the system ventilation level, 0-100 % in steps of 5; -1 = override off (default).INT16%Read/write
HR15Auto min.Minimum level in automatic mode, 0-100 % in steps of 5 (default 10 %).UINT16%Read/write
HR16Auto max.Maximum level in automatic mode, 0-100 % in steps of 5 (default 100 %).UINT16%Read/write
HR19ActionSimulates a user-control press for the zone.UINT16Read/write0 = Node display off; 1 = Node display on; 2 = Zone to temporary manual setting 1; 3 = Zone to temporary manual setting 2; 4 = Zone to temporary manual setting 3; 5 = Zone to automatic setting; 6 = Nobody home / unoccupied setting

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)

What Modbus registers does the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) have?

This map lists 11 registers: 7 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Duco numbers registers as node number followed by parameter number (node 1 parameter 0 = 10, node 7 parameter 2 = 72). The sheet says its implementation follows the official Modbus specification, so the printed number is the address sent on the wire; masters that subtract one (reading 19 for 20) can be compensated with the RegOffs parameter set to 1.

What are the minimum Modbus registers to integrate the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)?

Start with IR 11 Status (System status); IR 12 Ventilation position (Ventilation level %); IR 13 Current power (Current power); HR 10 Target value (Target value override); HR 19 Action (Action (manual/auto)); HR 15 Auto min. (Auto minimum).

How do I enable Modbus control of the Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)?

Fit the Communication Print option (DucoBox) or use the IQ unit's built-in port; set the Modbus address in the display menu or Duco Network Tool.

Where is the official Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node) Modbus documentation?

The source is Information sheet ModBus RTU (L8000009-B), revision 2023-02-23, published free by Duco at https://www.duco.eu/Wes/CDN/1/Attachments/information-sheet-ModBus-RTU-(en)_638328128583726330.pdf.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Information sheet ModBus RTU · L8000009-B · rev. 2023-02-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.