Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The PAX2C is Red Lion's PID temperature and process controller. Its Modbus table starts with a block of frequently used registers (process value, setpoints, output power, tuning, alarms and status) followed by full configuration. This map covers that frequently used block, profile status and the serial settings.
This page lists 64 Modbus registers for the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) — 51 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Red Lion’s own free documentation (linked below) and checked against it.
- Manufacturer
- Red Lion
- Model
- PAX2C temperature/process PID controller (Modbus RTU/ASCII)
- Equipment type
- Thermostat / temperature and process PID controller
- Registers
- 64 (51 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 247
- Default serial
- 38400 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- PAX2C Ver 2.0
- Also known as
- PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1
Integration notes: Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
Read registers 1-8 in one request (wire 0-7) for process value, min/max, setpoints, deviation and output power. Write setpoint 1 at wire 4 and switch auto/manual at wire 17.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Input process value | INT16 | Process value | Read |
| HR 3 | Active setpoint value | INT16 | Active setpoint | Read/write |
| HR 4 | Setpoint 1 value | INT16 | Setpoint 1 (write) | Read/write |
| HR 7 | Output power | INT16 | Output power | Read/write |
| HR 17 | Control mode | UINT16 | Auto/manual control mode | Read/write |
| HR 25 | Alarm (1-16) status register | BITMAP16 | Alarm status bits | Read |
Enable Modbus control & writes
Set the comms type register (1702) to Modbus RTU or ASCII, set baud, data bits, parity and address in 1703-1706, then write 1 to 1710 to load the new settings.
Byte order & addressing
- Factory comms type is Modbus ASCII, not RTU.
- Display-unit values carry no decimal point.
Network setup
- Default address 247, 38400 baud, 8 data bits, no parity.
- Write 1 to register 1710 after changing serial registers.
Watch out for
- Output power can only be written in manual mode.
- Digital outputs can only be forced through register 29 when their MMR bit (register 30) is set.
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 01 | Input process value | Display units, decimal point not sent. | INT16 | Read | ||||
| HR | 1doc 02 | Maximum value | Highest reading captured. Display units, decimal point not sent. | INT16 | Read | ||||
| HR | 2doc 03 | Minimum value | Lowest reading captured. Display units, decimal point not sent. | INT16 | Read | ||||
| HR | 3doc 04 | Active setpoint value | Limited by setpoint low/high limits. | INT16 | Read/write | ||||
| HR | 4doc 05 | Setpoint 1 value | Limited by setpoint low/high limits. | INT16 | Read/write | ||||
| HR | 5doc 06 | Setpoint 2 value | Limited by setpoint low/high limits. | INT16 | Read/write | ||||
| HR | 6doc 07 | Setpoint deviation | Deviation from the active setpoint, display units. | INT16 | Read | ||||
| HR | 7doc 08 | Output power | Heat/cool output, -100.0 to 100.0 %; writable only in manual mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8doc 09 | Active proportional band | Display units, decimal point not sent. | UINT16 | Read/write | ||||
| HR | 9doc 10 | Active integral time | 0-6500.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 10doc 11 | Active derivative time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 11doc 12 | Active power filter | UINT16 | × 0.1 | s | Read/write | |||
| HR | 12doc 13 | Auto-tune code | Tuning aggressiveness. | UINT16 | Read/write | 0 = Very aggressive; 1 = Aggressive; 2 = Default; 3 = Conservative; 4 = Very conservative | |||
| HR | 13doc 14 | Auto-tune request | Write to start an auto-tune. | UINT16 | Read/write | 0 = Off; 1 = Invoke auto-tune; 2 = Auto-tune CS1; 3 = Auto-tune CS2; 4 = Auto-tune CS3; 5 = Auto-tune CS4; 6 = Auto-tune CS5; 7 = Auto-tune CS6 | |||
| HR | 14doc 15 | Auto-tune phase | UINT16 | Read | 0 = Off; 4 = Last phase of auto-tune | ||||
| HR | 15doc 16 | Auto-tune done | 1 after a successful auto-tune since power-up. | UINT16 | Read | ||||
| HR | 16doc 17 | Auto-tune fail | UINT16 | Read | 0 = Off; 1 = Auto-tune failed | ||||
| HR | 17doc 18 | Control mode | UINT16 | Read/write | 0 = Automatic; 1 = Manual | ||||
| HR | 18doc 19 | Setpoint selection | UINT16 | Read/write | 0 = Setpoint 1; 1 = Setpoint 2; 2 = Setpoint 3; 3 = Setpoint 4; 4 = Setpoint 5; 5 = Setpoint 6 | ||||
| HR | 19doc 20 | Remote/local setpoint selection | UINT16 | Read/write | 0 = Local; 1 = Remote | ||||
| HR | 20doc 21 | PID set selection | UINT16 | Read/write | 0 = PID set 1 (primary); 1 = PID set 2 (alternate); 2 = PID set 3; 3 = PID set 4; 4 = PID set 5; 5 = PID set 6; 6 = SPSL; 7 = Auto | ||||
| HR | 21doc 22 | Disable integral action | UINT16 | Read/write | 0 = Enabled; 1 = Disabled | ||||
| HR | 22doc 23 | Disable setpoint ramping | UINT16 | Read/write | 0 = Enabled; 1 = Disabled | ||||
| HR | 23doc 24 | Setpoint ramping in process | UINT16 | Read/write | 0 = Off; 1 = In process | ||||
| HR | 24doc 25 | Setpoint ramp rate value | Ramp rate per the configured timebase. | INT16 | × 0.1 | Read/write | |||
| HR | 25doc 26 | Alarm (1-16) status register | Bit 0 = alarm 1 ... bit 15 = alarm 16. | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Alarm 4; bit 4 = Alarm 5; bit 5 = Alarm 6; bit 6 = Alarm 7; bit 7 = Alarm 8; bit 8 = Alarm 9; bit 9 = Alarm 10; bit 10 = Alarm 11; bit 11 = Alarm 12; bit 12 = Alarm 13; bit 13 = Alarm 14; bit 14 = Alarm 15; bit 15 = Alarm 16 | |||
| HR | 26doc 27 | PID stop/run | Stop forces output power to 0 %. | UINT16 | Read/write | 0 = Run PID; 1 = Stop PID | |||
| HR | 27doc 28 | User input status | BITMAP16 | Read | bit 0 = User input 1; bit 1 = User input 2 | ||||
| HR | 28doc 29 | Digital output status | Writable only for outputs set to manual in register 30. | BITMAP16 | Read/write | bit 0 = Out4; bit 1 = Out3; bit 2 = Out2; bit 3 = Out1 | |||
| HR | 29doc 30 | Output manual mode register (MMR) | Bit set = output in manual mode. | BITMAP16 | Read/write | bit 0 = Linear output; bit 1 = DO4; bit 2 = DO3; bit 3 = DO2; bit 4 = DO1 | |||
| HR | 30doc 31 | Alarm reset register | Write 1 to a bit to reset that alarm. | BITMAP16 | Read/write | bit 0 = Reset alarm 1; bit 1 = Reset alarm 2; bit 2 = Reset alarm 3; bit 3 = Reset alarm 4; bit 4 = Reset alarm 5; bit 5 = Reset alarm 6; bit 6 = Reset alarm 7; bit 7 = Reset alarm 8; bit 8 = Reset alarm 9; bit 9 = Reset alarm 10; bit 10 = Reset alarm 11; bit 11 = Reset alarm 12; bit 12 = Reset alarm 13; bit 13 = Reset alarm 14; bit 14 = Reset alarm 15; bit 15 = Reset alarm 16 | |||
| HR | 31doc 32 | Analog output register (AOR) | 0-4095; used only when linear output is in manual (MMR bit 0). | UINT16 | Read/write | ||||
| HR | 32doc 33 | Active alarm 1 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 33doc 34 | Active alarm 2 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 34doc 35 | Active alarm 3 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 35doc 36 | Active alarm 4 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 36doc 37 | Active alarm 5 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 37doc 38 | Active alarm 6 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 38doc 39 | Active alarm 7 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 39doc 40 | Active alarm 8 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 40doc 41 | Active alarm 9 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 41doc 42 | Active alarm 10 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 42doc 43 | Active alarm 11 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 43doc 44 | Active alarm 12 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 44doc 45 | Active alarm 13 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 45doc 46 | Active alarm 14 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 46doc 47 | Active alarm 15 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 47doc 48 | Active alarm 16 value | Active list (A or B). Display units, decimal point not sent. | INT16 | Read/write | ||||
| HR | 64doc 65 | Remote SP value | Display units, decimal point not sent. | INT16 | Read | ||||
| HR | 65doc 66 | Profile operating status | UINT16 | Read/write | 0 = Profile control off; 1 = End profile; 2 = Pause; 3 = Error delay (status only); 4 = Run/resume/start; 5 = Advance profile segment | ||||
| HR | 66doc 67 | Active profile | 0 = stop, 1-16 = profile. | UINT16 | Read | ||||
| HR | 67doc 68 | Active segment | 0 = stop, 1-20 = segment. | UINT16 | Read | ||||
| HR | 68doc 69 | Profile segment type | UINT16 | Read | 0 = Ramp; 1 = Hold | ||||
| HR | 69doc 70 | Active profile cycle count remaining | 0 = continuous cycling. | UINT16 | Read/write | ||||
| HR | 70doc 71-72 | Active profile segment time remaining | Hi word at 71, Lo word at 72. | UINT32 | ABCD | × 0.1 | min | Read/write | |
| HR | 72doc 73 | Profile event status | BITMAP16 | Read/write | bit 0 = Event 1; bit 1 = Event 2; bit 2 = Event 3; bit 3 = Event 4 | ||||
| HR | 1700doc 1701 | USB mode | UINT16 | Read/write | 0 = Configuration; 1 = Serial | ||||
| HR | 1701doc 1702 | Comms type | UINT16 | Read/write | 0 = RLC protocol (ASCII); 1 = Modbus RTU; 2 = Modbus ASCII | ||||
| HR | 1702doc 1703 | Baud rate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400 | ||||
| HR | 1703doc 1704 | Data bits | UINT16 | Read/write | 0 = 7 bits; 1 = 8 bits | ||||
| HR | 1704doc 1705 | Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 1705doc 1706 | Modbus unit address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 1706doc 1707 | Transmit delay | UINT16 | × 0.001 | s | Read/write | |||
| HR | 1709doc 1710 | Load serial settings | Write 1 to apply changes made in 1701-1709. | UINT16 | Read/write |
Notes on this map
- Red Lion's site hosts only the older Ver 1.5 table (PAX2C8H8V, marked reference only); this file uses the unaltered Ver 2.0 table (LP0905F) from a distributor's file host.
- Registers can be read as holding (4x) or input (3x) registers; they are listed as holding registers.
- Values marked 1 = 1 display unit are the displayed digits without the decimal point; apply the controller's decimal point setting yourself.
- The only 32-bit value listed (segment time remaining) is printed as a Hi word register followed by a Lo word register, so it is ABCD.
- Factory serial settings: Modbus ASCII (type 2), 38400 baud, 8 data bits, no parity, address 247. Stop bits are not given in the table.
- Serial setting changes (1701-1709) take effect only after writing 1 to register 1710, and the master must then switch to the new settings.
- Do not power the unit down while parameters are being written; the table warns this can corrupt non-volatile memory.
- Profile definitions (5001 and up), the A/B parameter lists, input/output configuration and FlexCard registers are documented in the table but left out.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
What Modbus registers does the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) have?
This map lists 64 registers: 64 holding registers. 51 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are numbered from 1; the table's own example reads register 2 with start address 00 01, and its notes refer to 41701-41710 for registers 1701-1710. Request register N at wire address N-1.
What byte order does the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)?
Start with HR 0 Input process value (Process value); HR 3 Active setpoint value (Active setpoint); HR 4 Setpoint 1 value (Setpoint 1 (write)); HR 7 Output power (Output power); HR 17 Control mode (Auto/manual control mode); HR 25 Alarm (1-16) status register (Alarm status bits).
How do I enable Modbus control of the Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)?
Set the comms type register (1702) to Modbus RTU or ASCII, set baud, data bits, parity and address in 1703-1706, then write 1 to 1710 to load the new settings.
Where is the official Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII) Modbus documentation?
The source is PAX2C, PX2FCA0, and PX2FCA1 Modbus Register Tables (LP0905F), revision 2017-02-27. Red Lion doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.logic-control.com/docs/red-lion/Datasheets/PAX2CHZVR%20Modbus%20Register%20Table.pdf. It may be an older revision, so check it against the live unit.
More Red Lion Modbus register maps
- Sensor (counter / rate panel meter)
Red Lion PAX2D counter / rate panel meter (Modbus)
PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).
Also known as: PAX2D, PAX2 D, Red Lion PAX2D counter - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter
Other hvac equipment register maps
- Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller - Air curtain controller (Air handler / door heater)
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).
Also known as: IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272
All hvac equipment Modbus register maps →
Source: PAX2C, PX2FCA0, and PX2FCA1 Modbus Register Tables · LP0905F · rev. 2017-02-27 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.