Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus register map
Updated 19 November 2026
The Neptronic SKE4 is an electric steam humidifier with SSR-driven heater stages. Its Modbus RTU module exposes everything as holding registers: raw signal voltages, scaled readings (room and supply RH, water temperature, currents, demand and output), set points and PID terms, binary inputs and relay states as 0/1 registers, and enumerated control, source and alarm states.
This page lists 151 Modbus registers for the Neptronic SKE4 electric steam humidifier (Modbus communication module) — 69 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKE4 electric steam humidifier (Modbus communication module)
- Equipment type
- Air handler humidifier (electric steam)
- Registers
- 151 (69 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus
Integration notes: Neptronic SKE4 electric steam humidifier (Modbus communication module)
Read Room RH (6004), Humidity Demand (6044), System Power Output (6046), Boiler State (15018) and Boiler Alarm (15020). To drive the unit from the BAS set Control Profile (15005) and the demand source (15012) to Network, then write Humidity Control Network Demand (6042) or Room RH Network Reading (6028) within the Network Timeout.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6004 | Room RH | UINT16 | Room RH | Read |
| HR 6029 | Room RH Setpoint | UINT16 | Room RH set point | Read/write |
| HR 6044 | Humidity Demand | UINT16 | Humidity demand | Read |
| HR 6046 | System Power Output | UINT16 | System power output | Read |
| HR 15018 | Boiler State | UINT16 | Boiler state | Read |
| HR 15020 | Boiler Alarm | UINT16 | Boiler alarm | Read |
| HR 15024 | System Power State | UINT16 | System on/off | Read/write |
| HR 6042 | Humidity Control Network Demand | UINT16 | Network demand | Read/write |
Enable Modbus control & writes
Install the Modbus communication module, set the address in the device menu (or register 0), and choose a network control profile (15005) and sources (15008-15014) when the BAS should supply readings or demand.
Communication loss & watchdog
Network Timeout (6081, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12009) shows a fault.
Byte order & addressing
- All points, including binary ones, are holding registers (FC03/06/16 only).
- Default framing is no parity with 2 stop bits; the text calls auto baud the default while register 1 lists 19200 as its default, so check the menu.
Network setup
- RS-485 two-wire, RTU mode; 9600-57600 baud, or auto baud detection.
- Set parity/stop bits via register 2 or the Modbus Comport Config menu item.
Watch out for
- Some network-source registers only take effect when the matching source register is set to Network.
Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud rate / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Control Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2001doc 2001 / 402002 | Room RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Supply RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2003doc 2003 / 402004 | Water Level Signal | UINT16 | Hz | Read | ||||
| HR | 2004doc 2004 / 402005 | Water Level Low Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2005doc 2005 / 402006 | Water Level High Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2006doc 2006 / 402007 | Water Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2007doc 2007 / 402008 | Foam Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2008doc 2008 / 402009 | SSR Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2009doc 2009 / 402010 | Cabinet Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2010doc 2010 / 402011 | Current Sensor 1 Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2011doc 2011 / 402012 | Current Sensor 2 Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2013doc 2013 / 402014 | Main Power Supply | UINT16 | × 0.1 | V | Read | |||
| HR | 4000doc 4000 / 404001 | Power Output Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 4001doc 4001 / 404002 | Heater SSR Stage | UINT16 | × 0.01 | % | Read | |||
| HR | 6000doc 6000 / 406001 | Control Input | UINT16 | × 0.01 | % | Read | |||
| HR | 6001doc 6001 / 406002 | Control Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6002doc 6002 / 406003 | Control Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6003doc 6003 / 406004 | Control Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6004doc 6004 / 406005 | Room RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6005doc 6005 / 406006 | Room RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6006doc 6006 / 406007 | Room RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6008doc 6008 / 406009 | Supply High Limit RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6009doc 6009 / 406010 | Supply High Limit RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6010doc 6010 / 406011 | Supply High Limit RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6011doc 6011 / 406012 | Supply High Limit RH Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6012doc 6012 / 406013 | Water Temperature | Unit follows Modbus Server Units (415002). | UINT16 | × 0.01 | °C / °F | Read | ||
| HR | 6013doc 6013 / 406014 | Water Temperature Bias | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6014doc 6014 / 406015 | SSR Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6015doc 6015 / 406016 | Cabinet Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6016doc 6016 / 406017 | Current Sensor 1 | UINT16 | × 0.01 | A | Read | |||
| HR | 6017doc 6017 / 406018 | Current Sensor 2 | UINT16 | × 0.01 | A | Read | |||
| HR | 6022doc 6022 / 406023 | Power Output Feedback | UINT16 | × 0.01 | % | Read | |||
| HR | 6023doc 6023 / 406024 | Water Level | UINT16 | × 0.1 | % | Read | |||
| HR | 6024doc 6024 / 406025 | Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6025doc 6025 / 406026 | Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6026doc 6026 / 406027 | Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6027doc 6027 / 406028 | Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6028doc 6028 / 406029 | Room RH Network Reading | Room RH written by the BAS when Room RH Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6029doc 6029 / 406030 | Room RH Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6030doc 6030 / 406031 | Room RH Unoccupied Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6031doc 6031 / 406032 | Room RH Vacant Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6032doc 6032 / 406033 | Room Demand Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6033doc 6033 / 406034 | Room Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6034doc 6034 / 406035 | Room Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6035doc 6035 / 406036 | Room Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6036doc 6036 / 406037 | Supply High Limit Network Reading | Supply high-limit RH written by the BAS when its source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6037doc 6037 / 406038 | Supply High Limit Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6038doc 6038 / 406039 | Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6039doc 6039 / 406040 | Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6040doc 6040 / 406041 | Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6041doc 6041 / 406042 | Supply High Limit Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6042doc 6042 / 406043 | Humidity Control Network Demand | Demand written by the BAS when Demand Source = Network. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 6043doc 6043 / 406044 | Humidity Control Network High Limit | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6044doc 6044 / 406045 | Humidity Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6045doc 6045 / 406046 | SDU Fan Off Delay | UINT16 | min | Read/write | ||||
| HR | 6046doc 6046 / 406047 | System Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6048doc 6048 / 406049 | Boiler Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6049doc 6049 / 406050 | Boiler Capacity | UINT16 | × 0.1 | kg/h / lb/h | Read | |||
| HR | 6050doc 6050 / 406051 | Boiler Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6067doc 6067 / 406068 | Boiler Minimum Steam Output | UINT16 | % | Read/write | ||||
| HR | 6068doc 6068 / 406069 | Boiler Drain Interval | UINT16 | h | Read/write | ||||
| HR | 6069doc 6069 / 406070 | Boiler Drain Volume | UINT16 | % | Read/write | ||||
| HR | 6070doc 6070 / 406071 | Boiler Max Steam Output | UINT16 | % | Read/write | ||||
| HR | 6071doc 6071 / 40672 | Boiler Idle Time Drain | UINT16 | h | Read/write | ||||
| HR | 6073doc 6073 / 406074 | Boiler Blowdown Rate | UINT16 | % | Read/write | ||||
| HR | 6074doc 6074 / 406075 | Boiler Service Interval | UINT16 | h | Read/write | ||||
| HR | 6076doc 6076 / 406077 | HRL Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6078doc 6078 / 406079 | HRL Humidity | UINT16 | × 0.01 | % | Read | |||
| HR | 6079doc 6079 / 406080 | Modbus TCP IP Keep Alive Time Out | UINT16 | min | Read/write | ||||
| HR | 6080doc 6080 / 406081 | Humidity Demand Low Dead Band | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6081doc 6081 / 406082 | Network Timeout | Time allowed between network writes before a network fault. | UINT16 | s | Read/write | |||
| HR | 6082doc 6082 / 406083 | Water Level Replace Interval | UINT16 | days | Read/write | ||||
| HR | 6087doc 6087 / 406088 | HRL Temperature Bas | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6088doc 6088 / 406089 | HRL Humidity Bias | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 6090doc 6090 / 406091 | Clean Valve Delay | UINT16 | % | Read/write | ||||
| HR | 10000doc 10000 / 410001 | Air Flow | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10001doc 10001 / 410002 | Supply High Limit | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10002doc 10002 / 410003 | Interlock | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10003doc 10003 / 410004 | Binary External Demand | UINT16 | Read | 0 = 0%; 1 = 100% | ||||
| HR | 10004doc 10004 / 410005 | Water Leak Detection | UINT16 | Read | 0 = Ok; 1 = Leak | ||||
| HR | 10005doc 10005 / 410006 | Thermal Cutout | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10006doc 10006 / 410007 | RS485 Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10007doc 10007 / 410008 | Ethernet Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10008doc 10008 / 410009 | Contactors PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Blown Fuse | ||||
| HR | 10009doc 10009 / 410010 | Control PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Open Fuse | ||||
| HR | 11000doc 11000 / 411001 | Alarm Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Service Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11002doc 11002 / 411003 | Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11003doc 11003 / 411004 | Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11005doc 11005 / 411006 | Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11006doc 11006 / 411007 | Drain Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11007doc 11007 / 411008 | Main Contactor | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11008doc 11008 / 411009 | Heater Stage 1 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11009doc 11009 / 411010 | Heater Stage2 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11010doc 11010 / 411011 | Heater Stage 3 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11011doc 11011 / 411012 | SDU Fan | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11012doc 11012 / 411013 | Alarm LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11013doc 11013 / 411014 | Power LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11014doc 11014 / 411015 | Buzzer | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12000doc 12000 / 412001 | Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12001doc 12001 / 412002 | Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12002doc 12002 / 412003 | Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12003doc 12003 / 412004 | Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12004doc 12004 / 412005 | SDU Fan Fault | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12005doc 12005 / 412006 | Boiler Service Operation | UINT16 | Read/write | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 12006doc 12006 / 412007 | Boiler Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12007doc 12007 / 412008 | Foam | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12008doc 12008 / 412009 | HRL Lock Setpoint | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 12009doc 12009 / 412010 | Network Control State | Network control fault flag (0 normal, 1 fault). | UINT16 | Read/write | 0 = Normal; 1 = Fault | |||
| HR | 12011doc 12011 / 412012 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12012doc 12012 / 412013 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12013doc 12013 / 412014 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12014doc 12014 / 412015 | Boiler Line Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12015doc 12015 / 412016 | AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 12016doc 12016 / 412017 | Memory Status | UINT16 | Read | 0 = Ok; 1 = Fail | ||||
| HR | 15001doc 15001 / 415002 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15002doc 15002 / 415003 | Control Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15003doc 15003 / 415004 | Room RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15004doc 15004 / 415005 | Supply RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15005doc 15005 / 415006 | Control Profile | UINT16 | Read/write | 0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom | ||||
| HR | 15006doc 15006 / 415007 | Modulating High Limit Profile | UINT16 | Read/write | 0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom | ||||
| HR | 15007doc 15007 / 415008 | Occupancy State | UINT16 | Read | 0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off | ||||
| HR | 15008doc 15008 / 415009 | Room RH Source | UINT16 | Read/write | 0 = None; 1 = RoomRH; 2 = Network; 3 = HRL | ||||
| HR | 15009doc 15009 / 415010 | Room RH Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15010doc 15010 / 415011 | Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SuppyHLRH; 2 = Network | ||||
| HR | 15011doc 15011 / 415012 | Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15012doc 15012 / 415013 | Humidity Control Demand Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network | ||||
| HR | 15013doc 15013 / 415014 | Humidity Control High Limit Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network | ||||
| HR | 15014doc 15014 / 415015 | Humidity Control Binary Demand Source | UINT16 | Read/write | 0 = None; 1 = BinaryExtDemand | ||||
| HR | 15015doc 15015 / 415016 | Humidity Control Cutout State | UINT16 | Read | 0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock | ||||
| HR | 15016doc 15016 / 415017 | SDU Fan Target | UINT16 | Read/write | 0 = None; 1 = SDUFan | ||||
| HR | 15017doc 15017 / 415018 | Boiler Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib | ||||
| HR | 15018doc 15018 / 415019 | Boiler State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm | ||||
| HR | 15019doc 15019 / 415020 | Boiler Fill Mode | UINT16 | Read/write | 0 = OneShot; 1 = Pulsed | ||||
| HR | 15020doc 15020 / 415021 | Boiler Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = Overheat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = TankBlocked; 10 = RefillDelay | ||||
| HR | 15021doc 15021 / 415022 | Boiler Idle Tank Rinse On | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15022doc 15022 / 415023 | Boiler Idle Tank Rinse Off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15023doc 15023 / 415024 | Water Probe Auto Calib | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15024doc 15024 / 415025 | System Power State | Humidifier on/off. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 15025doc 15025 / 415026 | Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15026doc 15026 / 415027 | Water Level Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15027doc 15027 / 415028 | Water Level Probe Alarm | UINT16 | Read | 0 = Ok; 1 = Defect; 2 = NoCalib | ||||
| HR | 15028doc 15028 / 415029 | Boiler Startup Tank Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15029doc 15029 / 415030 | Update Process Status | UINT16 | Read | 0 = Ok; 1 = CRC; 2 = Device; 3 = Failed |
Notes on this map
- Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.
- Scale column 'Scale N' with 'Value x N' means the raw value is the engineering value times N; this map stores the multiplier 1/N.
- Temperature and capacity units follow Modbus Server Units (415002): 0 metric, 1 imperial.
- Left out: product name ASCII registers 3-6 (character order unclear); Room RH Bias 6007 (typed unsigned with a negative range); Power Output Feedback Bias/Min/Max 6019-6021, Room Demand and Supply High Limit Proportional Band 6075/6077 and Boiler Idle Temperature Setpoint 6072 (scale column and example disagree); the run-time / on-time / service-time / manual calibration counters 6051-6066 and 6083-6086, which span four registers each with no stated word order.
- The guide prints holding register 40672 for protocol address 6071; this is a typo for 406072 (the protocol-base column is used).
- Water Temperature Bias (6013) is marked read-only in the guide even though it is a bias setting.
- Default unit address is not stated; it is set from the device menu or register 0.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKE4 electric steam humidifier (Modbus communication module)
What Modbus registers does the Neptronic SKE4 electric steam humidifier (Modbus communication module) have?
This map lists 151 registers: 151 holding registers. 69 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6004 / 406005. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKE4 electric steam humidifier (Modbus communication module)?
Start with HR 6004 Room RH (Room RH); HR 6029 Room RH Setpoint (Room RH set point); HR 6044 Humidity Demand (Humidity demand); HR 6046 System Power Output (System power output); HR 15018 Boiler State (Boiler state); HR 15020 Boiler Alarm (Boiler alarm); HR 15024 System Power State (System on/off); HR 6042 Humidity Control Network Demand (Network demand).
How do I enable Modbus control of the Neptronic SKE4 electric steam humidifier (Modbus communication module)?
Install the Modbus communication module, set the address in the device menu (or register 0), and choose a network control profile (15005) and sources (15008-15014) when the BAS should supply readings or demand.
What happens when the Neptronic SKE4 electric steam humidifier (Modbus communication module) loses Modbus communication?
Network Timeout (6081, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12009) shows a fault.
Where is the official Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus documentation?
The source is SKE4 Steam Humidifier - Modbus Communication Module User Guide (SKE4-Modbus Guide-240531 (V2.07)), revision 2024-05-31, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKE4/Manuals/2024/SKE4-Modbus%20Guide-240531%20(V2.07).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1 - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller - Air curtain controller (Air handler / door heater)
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).
Also known as: IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826
All hvac equipment Modbus register maps →
Source: SKE4 Steam Humidifier - Modbus Communication Module User Guide · SKE4-Modbus Guide-240531 (V2.07) · rev. 2024-05-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.