Air handler humidifier (electric steam) · Modbus register map

Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The Neptronic SKE4 is an electric steam humidifier with SSR-driven heater stages. Its Modbus RTU module exposes everything as holding registers: raw signal voltages, scaled readings (room and supply RH, water temperature, currents, demand and output), set points and PID terms, binary inputs and relay states as 0/1 registers, and enumerated control, source and alarm states.

This page lists 151 Modbus registers for the Neptronic SKE4 electric steam humidifier (Modbus communication module) — 69 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKE4 electric steam humidifier (Modbus communication module)
Equipment type
Air handler humidifier (electric steam)
Registers
151 (69 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus
Source document
SKE4 Steam Humidifier - Modbus Communication Module User Guide · SKE4-Modbus Guide-240531 (V2.07) · rev. 2024-05-31
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKE4 electric steam humidifier (Modbus communication module)

Integration in brief

Read Room RH (6004), Humidity Demand (6044), System Power Output (6046), Boiler State (15018) and Boiler Alarm (15020). To drive the unit from the BAS set Control Profile (15005) and the demand source (15012) to Network, then write Humidity Control Network Demand (6042) or Room RH Network Reading (6028) within the Network Timeout.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6004Room RHUINT16Room RHRead
HR 6029Room RH SetpointUINT16Room RH set pointRead/write
HR 6044Humidity DemandUINT16Humidity demandRead
HR 6046System Power OutputUINT16System power outputRead
HR 15018Boiler StateUINT16Boiler stateRead
HR 15020Boiler AlarmUINT16Boiler alarmRead
HR 15024System Power StateUINT16System on/offRead/write
HR 6042Humidity Control Network DemandUINT16Network demandRead/write

Enable Modbus control & writes

Install the Modbus communication module, set the address in the device menu (or register 0), and choose a network control profile (15005) and sources (15008-15014) when the BAS should supply readings or demand.

Communication loss & watchdog

Network Timeout (6081, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12009) shows a fault.

Byte order & addressing

Network setup

Watch out for

Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

151 of 151 shown
Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud rate / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Control SignalUINT16× 0.001VRead
HR2001doc 2001 / 402002Room RH SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Supply RH SignalUINT16× 0.001VRead
HR2003doc 2003 / 402004Water Level SignalUINT16HzRead
HR2004doc 2004 / 402005Water Level Low SignalUINT16× 0.001VRead
HR2005doc 2005 / 402006Water Level High SignalUINT16× 0.001VRead
HR2006doc 2006 / 402007Water Temperature SignalUINT16× 0.001VRead
HR2007doc 2007 / 402008Foam SignalUINT16× 0.001VRead
HR2008doc 2008 / 402009SSR Temperature SignalUINT16× 0.001VRead
HR2009doc 2009 / 402010Cabinet Temperature SignalUINT16× 0.001VRead
HR2010doc 2010 / 402011Current Sensor 1 SignalUINT16× 0.001VRead
HR2011doc 2011 / 402012Current Sensor 2 SignalUINT16× 0.001VRead
HR2013doc 2013 / 402014Main Power SupplyUINT16× 0.1VRead
HR4000doc 4000 / 404001Power Output Feedback SignalUINT16× 0.001VRead
HR4001doc 4001 / 404002Heater SSR StageUINT16× 0.01%Read
HR6000doc 6000 / 406001Control InputUINT16× 0.01%Read
HR6001doc 6001 / 406002Control MinUINT16× 0.01%Read/write
HR6002doc 6002 / 406003Control MaxUINT16× 0.01%Read/write
HR6003doc 6003 / 406004Control BiasINT16× 0.01%Read/write
HR6004doc 6004 / 406005Room RHUINT16× 0.01%RHRead
HR6005doc 6005 / 406006Room RH MinUINT16× 0.01%RHRead/write
HR6006doc 6006 / 406007Room RH MaxUINT16× 0.01%RHRead/write
HR6008doc 6008 / 406009Supply High Limit RHUINT16× 0.01%RHRead
HR6009doc 6009 / 406010Supply High Limit RH MinUINT16× 0.01%RHRead/write
HR6010doc 6010 / 406011Supply High Limit RH MaxUINT16× 0.01%RHRead/write
HR6011doc 6011 / 406012Supply High Limit RH BiasINT16× 0.01%Read/write
HR6012doc 6012 / 406013Water TemperatureUnit follows Modbus Server Units (415002).UINT16× 0.01°C / °FRead
HR6013doc 6013 / 406014Water Temperature BiasINT16× 0.01°C / °FRead
HR6014doc 6014 / 406015SSR TemperatureINT16× 0.01°C / °FRead
HR6015doc 6015 / 406016Cabinet TemperatureINT16× 0.01°C / °FRead
HR6016doc 6016 / 406017Current Sensor 1UINT16× 0.01ARead
HR6017doc 6017 / 406018Current Sensor 2UINT16× 0.01ARead
HR6022doc 6022 / 406023Power Output FeedbackUINT16× 0.01%Read
HR6023doc 6023 / 406024Water LevelUINT16× 0.1%Read
HR6024doc 6024 / 406025Water Probe Low Pos ReadingUINT16HzRead
HR6025doc 6025 / 406026Water Probe High Pos ReadingUINT16HzRead
HR6026doc 6026 / 406027Water Probe Abs Low Pos ReadingUINT16HzRead
HR6027doc 6027 / 406028Water Probe Abs High Pos ReadingUINT16HzRead
HR6028doc 6028 / 406029Room RH Network ReadingRoom RH written by the BAS when Room RH Source = Network.UINT16× 0.01%RHRead/write
HR6029doc 6029 / 406030Room RH SetpointUINT16× 0.01%RHRead/write
HR6030doc 6030 / 406031Room RH Unoccupied SetpointUINT16× 0.01%RHRead/write
HR6031doc 6031 / 406032Room RH Vacant SetpointUINT16× 0.01%RHRead/write
HR6032doc 6032 / 406033Room Demand Proportional GainUINT16× 0.1Read/write
HR6033doc 6033 / 406034Room Demand Integral TimeUINT16× 0.1sRead/write
HR6034doc 6034 / 406035Room Demand Derivative TimeUINT16× 0.1sRead/write
HR6035doc 6035 / 406036Room DemandUINT16× 0.01%RHRead
HR6036doc 6036 / 406037Supply High Limit Network ReadingSupply high-limit RH written by the BAS when its source = Network.UINT16× 0.01%RHRead/write
HR6037doc 6037 / 406038Supply High Limit SetpointUINT16× 0.01%RHRead/write
HR6038doc 6038 / 406039Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6039doc 6039 / 406040Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6040doc 6040 / 406041Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6041doc 6041 / 406042Supply High Limit DemandUINT16× 0.01%RHRead
HR6042doc 6042 / 406043Humidity Control Network DemandDemand written by the BAS when Demand Source = Network.UINT16× 0.01%Read/write
HR6043doc 6043 / 406044Humidity Control Network High LimitUINT16× 0.01%Read/write
HR6044doc 6044 / 406045Humidity DemandUINT16× 0.01%Read
HR6045doc 6045 / 406046SDU Fan Off DelayUINT16minRead/write
HR6046doc 6046 / 406047System Power OutputUINT16× 0.01%Read
HR6048doc 6048 / 406049Boiler DemandUINT16× 0.01%Read/write
HR6049doc 6049 / 406050Boiler CapacityUINT16× 0.1kg/h / lb/hRead
HR6050doc 6050 / 406051Boiler Power OutputUINT16× 0.01%Read
HR6067doc 6067 / 406068Boiler Minimum Steam OutputUINT16%Read/write
HR6068doc 6068 / 406069Boiler Drain IntervalUINT16hRead/write
HR6069doc 6069 / 406070Boiler Drain VolumeUINT16%Read/write
HR6070doc 6070 / 406071Boiler Max Steam OutputUINT16%Read/write
HR6071doc 6071 / 40672Boiler Idle Time DrainUINT16hRead/write
HR6073doc 6073 / 406074Boiler Blowdown RateUINT16%Read/write
HR6074doc 6074 / 406075Boiler Service IntervalUINT16hRead/write
HR6076doc 6076 / 406077HRL TemperatureINT16× 0.01°C / °FRead
HR6078doc 6078 / 406079HRL HumidityUINT16× 0.01%Read
HR6079doc 6079 / 406080Modbus TCP IP Keep Alive Time OutUINT16minRead/write
HR6080doc 6080 / 406081Humidity Demand Low Dead BandUINT16× 0.01%Read/write
HR6081doc 6081 / 406082Network TimeoutTime allowed between network writes before a network fault.UINT16sRead/write
HR6082doc 6082 / 406083Water Level Replace IntervalUINT16daysRead/write
HR6087doc 6087 / 406088HRL Temperature BasINT16× 0.1°C / °FRead/write
HR6088doc 6088 / 406089HRL Humidity BiasINT16× 0.1%RHRead/write
HR6090doc 6090 / 406091Clean Valve DelayUINT16%Read/write
HR10000doc 10000 / 410001Air FlowUINT16Read0 = Closed; 1 = Open
HR10001doc 10001 / 410002Supply High LimitUINT16Read0 = Closed; 1 = Open
HR10002doc 10002 / 410003InterlockUINT16Read0 = Closed; 1 = Open
HR10003doc 10003 / 410004Binary External DemandUINT16Read0 = 0%; 1 = 100%
HR10004doc 10004 / 410005Water Leak DetectionUINT16Read0 = Ok; 1 = Leak
HR10005doc 10005 / 410006Thermal CutoutUINT16Read0 = Closed; 1 = Open
HR10006doc 10006 / 410007RS485 InterfaceUINT16Read0 = No; 1 = Yes
HR10007doc 10007 / 410008Ethernet InterfaceUINT16Read0 = No; 1 = Yes
HR10008doc 10008 / 410009Contactors PCB FuseUINT16Read0 = Normal; 1 = Blown Fuse
HR10009doc 10009 / 410010Control PCB FuseUINT16Read0 = Normal; 1 = Open Fuse
HR11000doc 11000 / 411001Alarm Warning RelayUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Service Warning RelayUINT16Read0 = Off; 1 = On
HR11002doc 11002 / 411003Water Level ValveUINT16Read0 = Off; 1 = On
HR11003doc 11003 / 411004Tank Water ValveUINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR11005doc 11005 / 411006Drain PumpUINT16Read0 = Off; 1 = On
HR11006doc 11006 / 411007Drain ValveUINT16Read0 = Off; 1 = On
HR11007doc 11007 / 411008Main ContactorUINT16Read0 = Off; 1 = On
HR11008doc 11008 / 411009Heater Stage 1UINT16Read0 = Off; 1 = On
HR11009doc 11009 / 411010Heater Stage2UINT16Read0 = Off; 1 = On
HR11010doc 11010 / 411011Heater Stage 3UINT16Read0 = Off; 1 = On
HR11011doc 11011 / 411012SDU FanUINT16Read0 = Off; 1 = On
HR11012doc 11012 / 411013Alarm LEDUINT16Read0 = Off; 1 = On
HR11013doc 11013 / 411014Power LEDUINT16Read0 = Off; 1 = On
HR11014doc 11014 / 411015BuzzerUINT16Read0 = Off; 1 = On
HR12000doc 12000 / 412001Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12001doc 12001 / 412002Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12002doc 12002 / 412003Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12003doc 12003 / 412004Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12004doc 12004 / 412005SDU Fan FaultUINT16Read0 = Off; 1 = On
HR12005doc 12005 / 412006Boiler Service OperationUINT16Read/write0 = Not Allowed; 1 = Allowed
HR12006doc 12006 / 412007Boiler Service DueUINT16Read0 = No; 1 = Yes
HR12007doc 12007 / 412008FoamUINT16Read0 = Ok; 1 = Detected
HR12008doc 12008 / 412009HRL Lock SetpointUINT16Read/write0 = Unlock; 1 = Lock
HR12009doc 12009 / 412010Network Control StateNetwork control fault flag (0 normal, 1 fault).UINT16Read/write0 = Normal; 1 = Fault
HR12011doc 12011 / 412012Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12012doc 12012 / 412013Notify WarningUINT16Read/write0 = Off; 1 = On
HR12013doc 12013 / 412014Notify App MsgUINT16Read/write0 = Off; 1 = On
HR12014doc 12014 / 412015Boiler Line RinseUINT16Read/write0 = Off; 1 = On
HR12015doc 12015 / 412016AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR12016doc 12016 / 412017Memory StatusUINT16Read0 = Ok; 1 = Fail
HR15001doc 15001 / 415002Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15002doc 15002 / 415003Control Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15003doc 15003 / 415004Room RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15004doc 15004 / 415005Supply RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15005doc 15005 / 415006Control ProfileUINT16Read/write0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom
HR15006doc 15006 / 415007Modulating High Limit ProfileUINT16Read/write0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom
HR15007doc 15007 / 415008Occupancy StateUINT16Read0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off
HR15008doc 15008 / 415009Room RH SourceUINT16Read/write0 = None; 1 = RoomRH; 2 = Network; 3 = HRL
HR15009doc 15009 / 415010Room RH Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15010doc 15010 / 415011Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SuppyHLRH; 2 = Network
HR15011doc 15011 / 415012Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15012doc 15012 / 415013Humidity Control Demand SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network
HR15013doc 15013 / 415014Humidity Control High Limit SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network
HR15014doc 15014 / 415015Humidity Control Binary Demand SourceUINT16Read/write0 = None; 1 = BinaryExtDemand
HR15015doc 15015 / 415016Humidity Control Cutout StateUINT16Read0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock
HR15016doc 15016 / 415017SDU Fan TargetUINT16Read/write0 = None; 1 = SDUFan
HR15017doc 15017 / 415018Boiler RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib
HR15018doc 15018 / 415019Boiler StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm
HR15019doc 15019 / 415020Boiler Fill ModeUINT16Read/write0 = OneShot; 1 = Pulsed
HR15020doc 15020 / 415021Boiler AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = Overheat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = TankBlocked; 10 = RefillDelay
HR15021doc 15021 / 415022Boiler Idle Tank Rinse OnUINT16Read/write0 = Off; 1 = On
HR15022doc 15022 / 415023Boiler Idle Tank Rinse OffUINT16Read/write0 = Off; 1 = On
HR15023doc 15023 / 415024Water Probe Auto CalibUINT16Read/write0 = Off; 1 = On
HR15024doc 15024 / 415025System Power StateHumidifier on/off.UINT16Read/write0 = Off; 1 = On
HR15025doc 15025 / 415026Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15026doc 15026 / 415027Water Level Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15027doc 15027 / 415028Water Level Probe AlarmUINT16Read0 = Ok; 1 = Defect; 2 = NoCalib
HR15028doc 15028 / 415029Boiler Startup Tank RinseUINT16Read/write0 = Off; 1 = On
HR15029doc 15029 / 415030Update Process StatusUINT16Read0 = Ok; 1 = CRC; 2 = Device; 3 = Failed

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKE4 electric steam humidifier (Modbus communication module)

What Modbus registers does the Neptronic SKE4 electric steam humidifier (Modbus communication module) have?

This map lists 151 registers: 151 holding registers. 69 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6004 / 406005. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKE4 electric steam humidifier (Modbus communication module)?

Start with HR 6004 Room RH (Room RH); HR 6029 Room RH Setpoint (Room RH set point); HR 6044 Humidity Demand (Humidity demand); HR 6046 System Power Output (System power output); HR 15018 Boiler State (Boiler state); HR 15020 Boiler Alarm (Boiler alarm); HR 15024 System Power State (System on/off); HR 6042 Humidity Control Network Demand (Network demand).

How do I enable Modbus control of the Neptronic SKE4 electric steam humidifier (Modbus communication module)?

Install the Modbus communication module, set the address in the device menu (or register 0), and choose a network control profile (15005) and sources (15008-15014) when the BAS should supply readings or demand.

What happens when the Neptronic SKE4 electric steam humidifier (Modbus communication module) loses Modbus communication?

Network Timeout (6081, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12009) shows a fault.

Where is the official Neptronic SKE4 electric steam humidifier (Modbus communication module) Modbus documentation?

The source is SKE4 Steam Humidifier - Modbus Communication Module User Guide (SKE4-Modbus Guide-240531 (V2.07)), revision 2024-05-31, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKE4/Manuals/2024/SKE4-Modbus%20Guide-240531%20(V2.07).pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps