Air handler humidifier (steam-to-steam) · Modbus register map

Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The Neptronic SKS4 is a steam-to-steam humidifier with a modulating steam valve. Its Modbus RTU module exposes holding registers only: signal voltages, scaled room and supply RH, water and board temperatures, demand and steam-valve output, set points and PID terms, binary inputs and relays as 0/1 registers, and enumerated profile, source, boiler-state and alarm codes.

This page lists 147 Modbus registers for the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) — 69 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKS4 steam-to-steam humidifier (Modbus communication module)
Equipment type
Air handler humidifier (steam-to-steam)
Registers
147 (69 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus
Source document
SKS4 Steam to Steam Humidifier - Modbus Communication Module User Guide · SKS4-Modbus Guide-220509 (V2.03) · rev. 2022-05-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)

Integration in brief

Read Room RH (6005), Humidity Demand (6047), System Power Output (6048), Boiler State (15015) and Boiler Alarm (15017). For BAS control set Control Profile (15004) and Humidity Control Demand Source (15011) to the network options and write Humidity Control Network Demand (6045) within the Network Timeout.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6005Room RHUINT16Room RHRead
HR 6032Room RH SetpointUINT16Room RH set pointRead/write
HR 6047Humidity DemandUINT16Humidity demandRead
HR 6048System Power OutputUINT16System power outputRead
HR 15015Boiler StateUINT16Boiler stateRead
HR 15017Boiler AlarmUINT16Boiler alarmRead
HR 15021System Power StateUINT16System on/offRead/write
HR 6045Humidity Control Network DemandUINT16Network demandRead/write

Enable Modbus control & writes

Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.

Communication loss & watchdog

Network Timeout (6084, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12008) shows a fault.

Byte order & addressing

Network setup

Watch out for

Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

147 of 147 shown
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud rate / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Cabinet Temperature SignalUINT16× 0.001VRead
HR2001doc 2001 / 402002Control SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Room RH SignalUINT16× 0.001VRead
HR2003doc 2003 / 402004Supply RH SignalUINT16× 0.001VRead
HR2004doc 2004 / 402005Water Level SignalUINT16HzRead
HR2005doc 2005 / 402006Water Level Low SignalUINT16× 0.001VRead
HR2006doc 2006 / 402007Water Level High SignalUINT16× 0.001VRead
HR2007doc 2007 / 402008Water Temperature SignalUINT16× 0.001VRead
HR2008doc 2008 / 402009Foam SignalUINT16× 0.001VRead
HR2009doc 2009 / 402010Board Temperature SignalUINT16× 0.001VRead
HR2010doc 2010 / 402011Main Power SupplyUINT16× 0.1VRead
HR2011doc 2011 / 402012Steam Valve Feedback SignalUINT16× 0.001VRead
HR4000doc 4000 / 404001Steam Output Feedback SignalUINT16× 0.001VRead
HR4001doc 4001 / 404002Steam Valve SignalUINT16× 0.001VRead
HR6000doc 6000 / 406001Water Level Replace IntervalUINT16daysRead/write
HR6001doc 6001 / 406002Control InputUINT16× 0.01%Read/write
HR6002doc 6002 / 406003Control MinUINT16× 0.01%Read/write
HR6003doc 6003 / 406004Control MaxUINT16× 0.01%Read/write
HR6004doc 6004 / 406005Control BiasINT16× 0.01%Read/write
HR6005doc 6005 / 406006Room RHUINT16× 0.01%RHRead
HR6006doc 6006 / 406007Room RH MinUINT16× 0.01%RHRead
HR6007doc 6007 / 406008Room RH MaxUINT16× 0.01%RHRead
HR6010doc 6010 / 406011Supply High Limit RH MinUINT16× 0.01%Read/write
HR6011doc 6011 / 406012Supply High Limit RH MaxUINT16× 0.01%Read/write
HR6012doc 6012 / 406013Supply High Limit RH BiasINT16× 0.01%Read/write
HR6013doc 6013 / 406014Water Temperature Signal MinUINT16× 0.001VRead
HR6014doc 6014 / 406015Water Temperature Signal MaxUINT16× 0.001VRead
HR6015doc 6015 / 406016Water TemperatureUINT16× 0.01°C / °FRead
HR6016doc 6016 / 406017Water Temperature MinUINT16× 0.01°C / °FRead
HR6017doc 6017 / 406018Water Temperature MaxUINT16× 0.01°C / °FRead
HR6020doc 6020 / 406021Board TemperatureUINT16× 0.01°C / °FRead
HR6021doc 6021 / 406022Power Output Feedback BiasUINT16× 0.001VRead/write
HR6022doc 6022 / 406023Power Output Feedback MinUINT16× 0.001VRead/write
HR6023doc 6023 / 406024Power Output Feedback MaxUINT16× 0.001VRead/write
HR6024doc 6024 / 406025Power Output FeedbackUINT16× 0.01%Read
HR6025doc 6025 / 406026Steam Valve ControlUINT16× 0.01%Read
HR6026doc 6026 / 406027Water LevelUINT16× 0.1%Read
HR6027doc 6027 / 406028Water Probe Low Pos ReadingUINT16HzRead
HR6028doc 6028 / 406029Water Probe High Pos ReadingUINT16HzRead
HR6029doc 6029 / 406030Water Probe Abs Low Pos ReadingUINT16HzRead
HR6030doc 6030 / 406031Water Probe Abs High Pos ReadingUINT16HzRead
HR6031doc 6031 / 406032Room RH Network ReadingRoom RH written by the BAS when Room RH Source = Network.UINT16× 0.01%RHRead/write
HR6032doc 6032 / 406033Room RH SetpointUINT16× 0.01%RHRead/write
HR6033doc 6033 / 406034Room RH Unoccupied SetpointUINT16× 0.01%RHRead/write
HR6034doc 6034 / 406035Room RH Vacant SetpointUINT16× 0.01%RHRead/write
HR6037doc 6037 / 406038Room Demand Derivative TimeUINT16× 0.1sRead/write
HR6038doc 6038 / 406039Room DemandUINT16× 0.01%RHRead
HR6039doc 6039 / 406040Supply High Limit Network ReadingUINT16× 0.01%RHRead/write
HR6040doc 6040 / 406041Supply High Limit SetpointUINT16× 0.01%RHRead/write
HR6041doc 6041 / 406042Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6042doc 6042 / 406043Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6043doc 6043 / 406044Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6044doc 6044 / 406045Supply High Limit DemandUINT16× 0.01%RHRead
HR6045doc 6045 / 406046Humidity Control Network DemandDemand written by the BAS when Demand Source = Network.UINT16× 0.01%RHRead/write
HR6046doc 6046 / 406047Humidity Control Network High LimitUINT16× 0.01%RHRead/write
HR6047doc 6047 / 406048Humidity DemandUINT16× 0.01%RHRead
HR6048doc 6048 / 406049System Power OutputUINT16× 0.01%Read
HR6049doc 6049 / 406050System Steam CapacityUINT16× 0.1kg/h / lb/hRead
HR6050doc 6050 / 406051Boiler DemandUINT16× 0.01%Read/write
HR6051doc 6051 / 406052Boiler CapacityUINT16× 0.1kg/h / lb/hRead
HR6052doc 6052 / 406053Boiler Power OutputUINT16× 0.01%Read
HR6069doc 6069 / 406070Boiler Minimum Steam OutputUINT16%Read/write
HR6070doc 6070 / 406071Boiler Drain IntervalUINT16hRead/write
HR6073doc 6073 / 406074Boiler Idle Time DrainUINT16hRead/write
HR6075doc 6075 / 406076HRL TemperatureINT16× 0.01°C / °FRead
HR6076doc 6076 / 406077HRL HumidityUINT16× 0.01%RHRead
HR6077doc 6077 / 406078Boiler Blowdown RateUINT16%Read/write
HR6078doc 6078 / 406079Boiler Service IntervalUINT16hRead/write
HR6079doc 6079 / 406080Modbus TCP IP Keep Alive Time OutUINT16minRead/write
HR6080doc 6080 / 406081Boiler Idle Tank Rinse IntervalUINT16daysRead/write
HR6081doc 6081 / 406082Steam Valve FeedbackUINT16× 0.01%Read
HR6082doc 6082 / 406083Actuator DeadbandUINT16%Read/write
HR6083doc 6083 / 406084Humidity Demand Low Dead BandUINT16× 0.01%Read/write
HR6084doc 6084 / 406085Network TimeoutTime allowed between network writes before a network fault.UINT16sRead/write
HR6085doc 6085 / 406086Room Demand Proportional BandUINT16× 0.1%Read/write
HR6086doc 6086 / 406087Supply High Limit Proportional BandUINT16× 0.1%Read/write
HR6091doc 6091 / 406092HRL Temperature BasINT16× 0.1°C / °FRead/write
HR6092doc 6092 / 406093HRL Humidity BiasINT16× 0.1%RHRead/write
HR10000doc 10000 / 410001Air FlowUINT16Read0 = Closed; 1 = Open
HR10001doc 10001 / 410002Supply High LimitUINT16Read0 = Closed; 1 = Open
HR10002doc 10002 / 410003InterlockUINT16Read0 = Closed; 1 = Open
HR10003doc 10003 / 410004Binary External DemandUINT16Read0 = 0%; 1 = 100%
HR10004doc 10004 / 410005Water Leak DetectionUINT16Read0 = Ok; 1 = Leak
HR10005doc 10005 / 410006Thermal CutoutUINT16Read0 = Closed; 1 = Open
HR10006doc 10006 / 410007RS485 InterfaceUINT16Read0 = No; 1 = Yes
HR10007doc 10007 / 410008Ethernet InterfaceUINT16Read0 = No; 1 = Yes
HR10008doc 10008 / 410009Contactors PCB FuseUINT16Read0 = Normal; 1 = Blown Fuse
HR10009doc 10009 / 410010Control PCB FuseUINT16Read0 = Normal; 1 = Open Fuse
HR11000doc 11000 / 411001Alarm Warning RelayUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Service Warning RelayUINT16Read0 = Off; 1 = On
HR11002doc 11002 / 411003Water Level ValveUINT16Read0 = Off; 1 = On
HR11003doc 11003 / 411004Tank Water ValveUINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005Drain Cooler ValveUINT16Read0 = Off; 1 = On
HR11005doc 11005 / 411006Drain PumpUINT16Read0 = Off; 1 = On
HR11006doc 11006 / 411007Drain ValveUINT16Read0 = Off; 1 = On
HR11007doc 11007 / 411008Drain Pump 2UINT16Read0 = Off; 1 = On
HR11008doc 11008 / 411009Drain Pump 3UINT16Read0 = Off; 1 = On
HR11009doc 11009 / 411010Alarm LEDUINT16Read0 = Off; 1 = On
HR11010doc 11010 / 411011Power LEDUINT16Read0 = Off; 1 = On
HR11011doc 11011 / 411012BuzzerUINT16Read0 = Off; 1 = On
HR12000doc 12000 / 412001Water Level LowUINT16Read0 = Inactive; 1 = Active
HR12001doc 12001 / 412002Water Level HighUINT16Read0 = Inactive; 1 = Active
HR12002doc 12002 / 412003Foam SensorUINT16Read0 = NoFoam; 1 = Foam
HR12003doc 12003 / 412004Boiler Service OperationUINT16Read/write0 = Not Allowed; 1 = Allowed
HR12004doc 12004 / 412005Boiler Service DueUINT16Read0 = Off; 1 = On
HR12005doc 12005 / 412006FoamUINT16Read0 = Ok; 1 = Detected
HR12006doc 12006 / 412007Boiler Line RinseUINT16Read/write0 = Off; 1 = On
HR12007doc 12007 / 412008HRL Lock SetpointUINT16Read/write0 = Unlock; 1 = Lock
HR12008doc 12008 / 412009Network Control StateUINT16Read/write0 = Normal; 1 = Fault
HR12009doc 12009 / 412010Inhibit Resistive ProbeUINT16Read/write0 = No; 1 = Yes
HR12010doc 12010 / 412011Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12011doc 12011 / 412012Notify WarningUINT16Read/write0 = Off; 1 = On
HR12012doc 12012 / 412013Notify App MsgUINT16Read/write0 = Off; 1 = On
HR12013doc 12013 / 412014Power Up DrainUINT16Read/write0 = Off; 1 = On
HR12014doc 12014 / 412015Manual Water Calibration StateUINT16Read0 = Ok; 1 = Required
HR12015doc 12015 / 412016AntiFreeze WarningUINT16Read0 = Inactive; 1 = Drain
HR15000doc 15000 / 415001Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15001doc 15001 / 415002Control Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15002doc 15002 / 415003Room RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15003doc 15003 / 415004Supply RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15004doc 15004 / 415005Control ProfileUINT16Read/write0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom
HR15005doc 15005 / 415006Modulating High Limit ProfileUINT16Read/write0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom
HR15006doc 15006 / 415007Occupancy StateUINT16Read0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off
HR15007doc 15007 / 415008Room RH SourceUINT16Read/write0 = None; 1 = RoomRH; 2 = Network
HR15008doc 15008 / 415009Room RH Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15009doc 15009 / 415010Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SuppyHLRH; 2 = Network
HR15010doc 15010 / 415011Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15011doc 15011 / 415012Humidity Control Demand SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network
HR15012doc 15012 / 415013Humidity Control High Limit SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network
HR15013doc 15013 / 415014Humidity Control Cutout StateUINT16Read0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock
HR15014doc 15014 / 415015Boiler RequestUINT16Read/write0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib
HR15015doc 15015 / 415016Boiler StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm
HR15016doc 15016 / 415017Boiler Fill ModeUINT16Read/write0 = OneShot; 1 = Pulsed
HR15017doc 15017 / 415018Boiler AlarmUINT16Read0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = Overheat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = TankBlocked; 10 = RefillDelay
HR15018doc 15018 / 415019Boiler Idle Tank Rinse OnUINT16Read/write0 = Off; 1 = On
HR15019doc 15019 / 415020Boiler Idle Tank Rinse OffUINT16Read/write0 = Off; 1 = On
HR15020doc 15020 / 415021Water Probe Auto CalibUINT16Read/write0 = None; 1 = Once; 2 = Always
HR15021doc 15021 / 415022System Power StateHumidifier on/off.UINT16Read/write0 = Off; 1 = On
HR15022doc 15022 / 415023Boiler Startup Tank RinseUINT16Read/write0 = Off; 1 = On
HR15023doc 15023 / 415024Water Level Probe WarningUINT16Read0 = Ok; 1 = Replace
HR15024doc 15024 / 415025Water Level Probe FailureUINT16Read0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both
HR15025doc 15025 / 415026Water Level Probe AlarmUINT16Read0 = OK; 1 = Defect; 2 = NoCalib

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)

What Modbus registers does the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) have?

This map lists 147 registers: 147 holding registers. 69 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)?

Start with HR 6005 Room RH (Room RH); HR 6032 Room RH Setpoint (Room RH set point); HR 6047 Humidity Demand (Humidity demand); HR 6048 System Power Output (System power output); HR 15015 Boiler State (Boiler state); HR 15017 Boiler Alarm (Boiler alarm); HR 15021 System Power State (System on/off); HR 6045 Humidity Control Network Demand (Network demand).

How do I enable Modbus control of the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)?

Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.

What happens when the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) loses Modbus communication?

Network Timeout (6084, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12008) shows a fault.

Where is the official Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus documentation?

The source is SKS4 Steam to Steam Humidifier - Modbus Communication Module User Guide (SKS4-Modbus Guide-220509 (V2.03)), revision 2022-05-09, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKS4/20230525/SKS4-Modbus%20Guide-220509%20(V2.03).pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SKS4 Steam to Steam Humidifier - Modbus Communication Module User Guide · SKS4-Modbus Guide-220509 (V2.03) · rev. 2022-05-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.