- SKS4 steam-to-steam humidifier (Modbus communication module)
Air handler humidifier (steam-to-steam) · Modbus register map
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus register map
Updated 19 November 2026
The Neptronic SKS4 is a steam-to-steam humidifier with a modulating steam valve. Its Modbus RTU module exposes holding registers only: signal voltages, scaled room and supply RH, water and board temperatures, demand and steam-valve output, set points and PID terms, binary inputs and relays as 0/1 registers, and enumerated profile, source, boiler-state and alarm codes.
This page lists 147 Modbus registers for the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) — 69 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKS4 steam-to-steam humidifier (Modbus communication module)
- Equipment type
- Air handler humidifier (steam-to-steam)
- Registers
- 147 (69 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus
Integration notes: Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Read Room RH (6005), Humidity Demand (6047), System Power Output (6048), Boiler State (15015) and Boiler Alarm (15017). For BAS control set Control Profile (15004) and Humidity Control Demand Source (15011) to the network options and write Humidity Control Network Demand (6045) within the Network Timeout.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6005 | Room RH | UINT16 | Room RH | Read |
| HR 6032 | Room RH Setpoint | UINT16 | Room RH set point | Read/write |
| HR 6047 | Humidity Demand | UINT16 | Humidity demand | Read |
| HR 6048 | System Power Output | UINT16 | System power output | Read |
| HR 15015 | Boiler State | UINT16 | Boiler state | Read |
| HR 15017 | Boiler Alarm | UINT16 | Boiler alarm | Read |
| HR 15021 | System Power State | UINT16 | System on/off | Read/write |
| HR 6045 | Humidity Control Network Demand | UINT16 | Network demand | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.
Communication loss & watchdog
Network Timeout (6084, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12008) shows a fault.
Byte order & addressing
- All points, binary ones included, are holding registers (FC03/06/16 only).
- Default framing is no parity with 2 stop bits.
Network setup
- RS-485 two-wire, RTU; 9600-57600 baud or auto baud detection.
- Parity/stop bits via register 2 or the Modbus Comport Config menu item.
Watch out for
- Several register numbers differ from the SKE4 guide even where names match; use the SKS4 list.
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud rate / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Cabinet Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2001doc 2001 / 402002 | Control Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Room RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2003doc 2003 / 402004 | Supply RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2004doc 2004 / 402005 | Water Level Signal | UINT16 | Hz | Read | ||||
| HR | 2005doc 2005 / 402006 | Water Level Low Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2006doc 2006 / 402007 | Water Level High Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2007doc 2007 / 402008 | Water Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2008doc 2008 / 402009 | Foam Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2009doc 2009 / 402010 | Board Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2010doc 2010 / 402011 | Main Power Supply | UINT16 | × 0.1 | V | Read | |||
| HR | 2011doc 2011 / 402012 | Steam Valve Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 4000doc 4000 / 404001 | Steam Output Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 4001doc 4001 / 404002 | Steam Valve Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 6000doc 6000 / 406001 | Water Level Replace Interval | UINT16 | days | Read/write | ||||
| HR | 6001doc 6001 / 406002 | Control Input | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6002doc 6002 / 406003 | Control Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6003doc 6003 / 406004 | Control Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6004doc 6004 / 406005 | Control Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6005doc 6005 / 406006 | Room RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6006doc 6006 / 406007 | Room RH Min | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6007doc 6007 / 406008 | Room RH Max | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6010doc 6010 / 406011 | Supply High Limit RH Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6011doc 6011 / 406012 | Supply High Limit RH Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6012doc 6012 / 406013 | Supply High Limit RH Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6013doc 6013 / 406014 | Water Temperature Signal Min | UINT16 | × 0.001 | V | Read | |||
| HR | 6014doc 6014 / 406015 | Water Temperature Signal Max | UINT16 | × 0.001 | V | Read | |||
| HR | 6015doc 6015 / 406016 | Water Temperature | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6016doc 6016 / 406017 | Water Temperature Min | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6017doc 6017 / 406018 | Water Temperature Max | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6020doc 6020 / 406021 | Board Temperature | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6021doc 6021 / 406022 | Power Output Feedback Bias | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6022doc 6022 / 406023 | Power Output Feedback Min | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6023doc 6023 / 406024 | Power Output Feedback Max | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6024doc 6024 / 406025 | Power Output Feedback | UINT16 | × 0.01 | % | Read | |||
| HR | 6025doc 6025 / 406026 | Steam Valve Control | UINT16 | × 0.01 | % | Read | |||
| HR | 6026doc 6026 / 406027 | Water Level | UINT16 | × 0.1 | % | Read | |||
| HR | 6027doc 6027 / 406028 | Water Probe Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6028doc 6028 / 406029 | Water Probe High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6029doc 6029 / 406030 | Water Probe Abs Low Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6030doc 6030 / 406031 | Water Probe Abs High Pos Reading | UINT16 | Hz | Read | ||||
| HR | 6031doc 6031 / 406032 | Room RH Network Reading | Room RH written by the BAS when Room RH Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6032doc 6032 / 406033 | Room RH Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6033doc 6033 / 406034 | Room RH Unoccupied Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6034doc 6034 / 406035 | Room RH Vacant Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6037doc 6037 / 406038 | Room Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6038doc 6038 / 406039 | Room Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6039doc 6039 / 406040 | Supply High Limit Network Reading | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6040doc 6040 / 406041 | Supply High Limit Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6041doc 6041 / 406042 | Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6042doc 6042 / 406043 | Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6043doc 6043 / 406044 | Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6044doc 6044 / 406045 | Supply High Limit Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6045doc 6045 / 406046 | Humidity Control Network Demand | Demand written by the BAS when Demand Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6046doc 6046 / 406047 | Humidity Control Network High Limit | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6047doc 6047 / 406048 | Humidity Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6048doc 6048 / 406049 | System Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6049doc 6049 / 406050 | System Steam Capacity | UINT16 | × 0.1 | kg/h / lb/h | Read | |||
| HR | 6050doc 6050 / 406051 | Boiler Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6051doc 6051 / 406052 | Boiler Capacity | UINT16 | × 0.1 | kg/h / lb/h | Read | |||
| HR | 6052doc 6052 / 406053 | Boiler Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6069doc 6069 / 406070 | Boiler Minimum Steam Output | UINT16 | % | Read/write | ||||
| HR | 6070doc 6070 / 406071 | Boiler Drain Interval | UINT16 | h | Read/write | ||||
| HR | 6073doc 6073 / 406074 | Boiler Idle Time Drain | UINT16 | h | Read/write | ||||
| HR | 6075doc 6075 / 406076 | HRL Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6076doc 6076 / 406077 | HRL Humidity | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6077doc 6077 / 406078 | Boiler Blowdown Rate | UINT16 | % | Read/write | ||||
| HR | 6078doc 6078 / 406079 | Boiler Service Interval | UINT16 | h | Read/write | ||||
| HR | 6079doc 6079 / 406080 | Modbus TCP IP Keep Alive Time Out | UINT16 | min | Read/write | ||||
| HR | 6080doc 6080 / 406081 | Boiler Idle Tank Rinse Interval | UINT16 | days | Read/write | ||||
| HR | 6081doc 6081 / 406082 | Steam Valve Feedback | UINT16 | × 0.01 | % | Read | |||
| HR | 6082doc 6082 / 406083 | Actuator Deadband | UINT16 | % | Read/write | ||||
| HR | 6083doc 6083 / 406084 | Humidity Demand Low Dead Band | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6084doc 6084 / 406085 | Network Timeout | Time allowed between network writes before a network fault. | UINT16 | s | Read/write | |||
| HR | 6085doc 6085 / 406086 | Room Demand Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6086doc 6086 / 406087 | Supply High Limit Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6091doc 6091 / 406092 | HRL Temperature Bas | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6092doc 6092 / 406093 | HRL Humidity Bias | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 10000doc 10000 / 410001 | Air Flow | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10001doc 10001 / 410002 | Supply High Limit | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10002doc 10002 / 410003 | Interlock | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10003doc 10003 / 410004 | Binary External Demand | UINT16 | Read | 0 = 0%; 1 = 100% | ||||
| HR | 10004doc 10004 / 410005 | Water Leak Detection | UINT16 | Read | 0 = Ok; 1 = Leak | ||||
| HR | 10005doc 10005 / 410006 | Thermal Cutout | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10006doc 10006 / 410007 | RS485 Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10007doc 10007 / 410008 | Ethernet Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10008doc 10008 / 410009 | Contactors PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Blown Fuse | ||||
| HR | 10009doc 10009 / 410010 | Control PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Open Fuse | ||||
| HR | 11000doc 11000 / 411001 | Alarm Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Service Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11002doc 11002 / 411003 | Water Level Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11003doc 11003 / 411004 | Tank Water Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Drain Cooler Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11005doc 11005 / 411006 | Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11006doc 11006 / 411007 | Drain Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11007doc 11007 / 411008 | Drain Pump 2 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11008doc 11008 / 411009 | Drain Pump 3 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11009doc 11009 / 411010 | Alarm LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11010doc 11010 / 411011 | Power LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11011doc 11011 / 411012 | Buzzer | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12000doc 12000 / 412001 | Water Level Low | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12001doc 12001 / 412002 | Water Level High | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12002doc 12002 / 412003 | Foam Sensor | UINT16 | Read | 0 = NoFoam; 1 = Foam | ||||
| HR | 12003doc 12003 / 412004 | Boiler Service Operation | UINT16 | Read/write | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 12004doc 12004 / 412005 | Boiler Service Due | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12005doc 12005 / 412006 | Foam | UINT16 | Read | 0 = Ok; 1 = Detected | ||||
| HR | 12006doc 12006 / 412007 | Boiler Line Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12007doc 12007 / 412008 | HRL Lock Setpoint | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 12008doc 12008 / 412009 | Network Control State | UINT16 | Read/write | 0 = Normal; 1 = Fault | ||||
| HR | 12009doc 12009 / 412010 | Inhibit Resistive Probe | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12010doc 12010 / 412011 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12011doc 12011 / 412012 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12012doc 12012 / 412013 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12013doc 12013 / 412014 | Power Up Drain | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12014doc 12014 / 412015 | Manual Water Calibration State | UINT16 | Read | 0 = Ok; 1 = Required | ||||
| HR | 12015doc 12015 / 412016 | AntiFreeze Warning | UINT16 | Read | 0 = Inactive; 1 = Drain | ||||
| HR | 15000doc 15000 / 415001 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15001doc 15001 / 415002 | Control Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15002doc 15002 / 415003 | Room RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15003doc 15003 / 415004 | Supply RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15004doc 15004 / 415005 | Control Profile | UINT16 | Read/write | 0 = ExternAnalog; 1 = ExternNetwork; 2 = InternAnalog; 3 = InternNetwork; 4 = HRL; 5 = Custom | ||||
| HR | 15005doc 15005 / 415006 | Modulating High Limit Profile | UINT16 | Read/write | 0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternAnalog; 4 = InternNetwork; 5 = Custom | ||||
| HR | 15006doc 15006 / 415007 | Occupancy State | UINT16 | Read | 0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off | ||||
| HR | 15007doc 15007 / 415008 | Room RH Source | UINT16 | Read/write | 0 = None; 1 = RoomRH; 2 = Network | ||||
| HR | 15008doc 15008 / 415009 | Room RH Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15009doc 15009 / 415010 | Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SuppyHLRH; 2 = Network | ||||
| HR | 15010doc 15010 / 415011 | Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15011doc 15011 / 415012 | Humidity Control Demand Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network | ||||
| HR | 15012doc 15012 / 415013 | Humidity Control High Limit Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = SupplyHLDemand; 3 = Network | ||||
| HR | 15013doc 15013 / 415014 | Humidity Control Cutout State | UINT16 | Read | 0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock | ||||
| HR | 15014doc 15014 / 415015 | Boiler Request | UINT16 | Read/write | 0 = None; 1 = Reset Alarms; 2 = Drain; 3 = Reset Counters; 4 = Filling; 5 = WaterCalib | ||||
| HR | 15015doc 15015 / 415016 | Boiler State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = TankRinse; 4 = Filling; 5 = Draining; 6 = Heating; 7 = Boiling; 8 = Alarm | ||||
| HR | 15016doc 15016 / 415017 | Boiler Fill Mode | UINT16 | Read/write | 0 = OneShot; 1 = Pulsed | ||||
| HR | 15017doc 15017 / 415018 | Boiler Alarm | UINT16 | Read | 0 = Normal; 1 = FailedPump; 2 = FillTimeout; 3 = BlockedPiping; 4 = HeatTimeout; 5 = Overheat; 6 = WaterLeak; 7 = Service; 8 = Reserved; 9 = TankBlocked; 10 = RefillDelay | ||||
| HR | 15018doc 15018 / 415019 | Boiler Idle Tank Rinse On | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15019doc 15019 / 415020 | Boiler Idle Tank Rinse Off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15020doc 15020 / 415021 | Water Probe Auto Calib | UINT16 | Read/write | 0 = None; 1 = Once; 2 = Always | ||||
| HR | 15021doc 15021 / 415022 | System Power State | Humidifier on/off. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 15022doc 15022 / 415023 | Boiler Startup Tank Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15023doc 15023 / 415024 | Water Level Probe Warning | UINT16 | Read | 0 = Ok; 1 = Replace | ||||
| HR | 15024doc 15024 / 415025 | Water Level Probe Failure | UINT16 | Read | 0 = None; 1 = Capacitive; 2 = Resistive; 3 = Both | ||||
| HR | 15025doc 15025 / 415026 | Water Level Probe Alarm | UINT16 | Read | 0 = OK; 1 = Defect; 2 = NoCalib |
Notes on this map
- Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.
- 'Scale N' with 'Value x N' means the raw value is the engineering value times N; this map stores the multiplier 1/N.
- Temperature and capacity units follow Modbus Server Units (415001): 0 metric, 1 imperial.
- The guide text calls automatic baud detection the default, while register 1 lists 19200 as its default value; the baud default is left blank here.
- Default unit address is not stated; it is set from the device menu or register 0.
- Left out: product name ASCII registers 3-6; protocol addresses 6008 and 6035, which each appear twice in the table with different holding numbers and names (Room RH Bias / Supply High Limit RH, Room Demand Proportional Gain / Integral Time); Water Temperature Bias 6018 and Cabinet Temperature 6019 (typed unsigned with negative ranges); Boiler Drain Volume 6071, Boiler Max Steam Output 6072 and Boiler Idle Temperature Setpoint 6074 (scale and example disagree); the run/on/service time and calibration counters (6053-6068, 6087-6090), which span four registers with no stated word order.
- System Power State (15021) has its writable flag printed inside the value column; it is listed as writable here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
What Modbus registers does the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) have?
This map lists 147 registers: 147 holding registers. 69 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)?
Start with HR 6005 Room RH (Room RH); HR 6032 Room RH Setpoint (Room RH set point); HR 6047 Humidity Demand (Humidity demand); HR 6048 System Power Output (System power output); HR 15015 Boiler State (Boiler state); HR 15017 Boiler Alarm (Boiler alarm); HR 15021 System Power State (System on/off); HR 6045 Humidity Control Network Demand (Network demand).
How do I enable Modbus control of the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)?
Fit the Modbus communication module, set the address in the device menu (or register 0) and pick network profile and sources (15004-15012) if the BAS supplies readings or demand.
What happens when the Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) loses Modbus communication?
Network Timeout (6084, 1-900 s, default 900 s): network-supplied values must be refreshed within this time; Network Control State (12008) shows a fault.
Where is the official Neptronic SKS4 steam-to-steam humidifier (Modbus communication module) Modbus documentation?
The source is SKS4 Steam to Steam Humidifier - Modbus Communication Module User Guide (SKS4-Modbus Guide-220509 (V2.03)), revision 2022-05-09, published free by Neptronic at http://www.neptronic.com/Humidifiers/PDF/SKS4/20230525/SKS4-Modbus%20Guide-220509%20(V2.03).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
SMT-770 thermostat (with or without a paired EC-02 module), communications addendum v4.6 for firmware 2.31.
Also known as: SMT-770 Chameleon, EC-02, SMT770 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523
All hvac equipment Modbus register maps →
Source: SKS4 Steam to Steam Humidifier - Modbus Communication Module User Guide · SKS4-Modbus Guide-220509 (V2.03) · rev. 2022-05-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.