Easy Modbus
  1. Home
  2. Modbus register maps
  3. Smart Temp
  4. SMT-770 thermostat with EC-02 module (Modbus RTU)

Thermostat · Modbus register map

Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Smart Temp SMT-770 is an Australian 24 V multifunction thermostat with an RS-485 Modbus RTU port; a paired EC-02 output module appears as the same device. This map covers relay coils, thermostat and fan modes, set temperatures, room temperature, network settings and the coil override.

This page lists 35 Modbus registers for the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Smart Temp’s own free documentation (linked below) and checked against it.

Manufacturer
Smart Temp
Model
SMT-770 thermostat with EC-02 module (Modbus RTU)
Equipment type
Thermostat
Registers
35 (25 writable)
Transport
Modbus RTU
Default unit ID
7
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
2.31 (addendum v4.6)
Also known as
SMT-770 Chameleon, EC-02, SMT770
Source document
SMT-770 / EC-02 Communications Addendum · Version 4.6 (firmware 2.31, 1/03/12) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)

Integration in brief

Read 40354 for the room temperature shown on the display and 40318 for the active setpoint; write mode (40002), fan (40003) and setpoints (40005/40006 or 40015 depending on DIP mode).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 353Displayed room temperatureUINT16Room temperature (0.1 °C)Read
HR 317Active set temperatureUINT16Active setpointRead
HR 1Thermostat modeUINT16Thermostat modeRead/write
HR 2Fan modeUINT16Fan modeRead/write
HR 14Single set point (manual mode)UINT16Single setpoint (manual mode)Read/write
CO 0G1 relayBITG1 fan relayRead/write

Enable Modbus control & writes

Set the thermostat address in the installer menu (item AD, default 7); 9600 8N1 by default. A paired EC-02 copies address and baud from the thermostat.

Communication loss & watchdog

Coil override (40062) falls back to thermostat control after about 5 minutes without Modbus or after a power loss; refresh it at least every 4 minutes.

Byte order & addressing

Network setup

Watch out for

Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

35 of 35 shown
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001G1 relayWritable from firmware 2.19; see coil override 40062.BITRead/write0 = Off; 1 = On
CO1doc 00002G2/Y2 relayWritable from firmware 2.19; see coil override 40062.BITRead/write0 = Off; 1 = On
CO2doc 00003G3/W2/OB relayWritable from firmware 2.19; see coil override 40062.BITRead/write0 = Off; 1 = On
CO3doc 00004Y1 relayWritable from firmware 2.19; see coil override 40062.BITRead/write0 = Off; 1 = On
CO4doc 00005W1 relayWritable from firmware 2.19; see coil override 40062.BITRead/write0 = Off; 1 = On
HR1doc 40002Thermostat modeUINT16Read/write0 = Off; 2 = Heat only; 3 = Cool only; 4 = Auto changeover; 5 = Emergency heat; 6 = Cool and dry (v2.3+); 7 = Auto and dry (v2.3+)
HR2doc 40003Fan modeUINT16Read/write0 = Auto (cycles with heat/cool); 1 = On
HR3doc 40004Program holdOnly in residential programmable mode (DIP 6 and 8 on).UINT16Read/write0 = Off; 1 = Temporary hold; 2 = Permanent hold
HR4doc 40005Heat set temperature (hold)Two-setpoint modes. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR5doc 40006Cool set temperature (hold)Two-setpoint modes. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR9doc 40010Fan speedNeeds 3-speed fan DIP setting.UINT16Read/write1 = Low; 2 = Medium; 3 = High; 4 = Auto
HR10doc 40011Day cool set temperature255 = off. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR11doc 40012Day heat set temperature0 = off. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR12doc 40013Night cool set temperature255 = off. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR13doc 40014Night heat set temperature0 = off. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR14doc 40015Single set point (manual mode)DIP 6 and 8 off. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead/write
HR18doc 40019Current running programUINT16Read0 = Manual mode; 1 = Program event 1; 2 = Program event 2; 3 = Program event 3; 4 = Program event 4; 5 = Start event; 6 = Stop event
HR19doc 40020Sentinel pointIdentifies an SMT-770: 77 before firmware 2.17, 78 from 2.17.UINT16Read
HR21doc 40022Modbus address1-32; the network must follow a change.UINT16Read/write
HR23doc 40024Temperature display modeUINT16Read/write0 = Room and set temperature; 1 = Set temperature only
HR28doc 40029Display unitsUINT16Read/write0 = °F; 1 = °C
HR40doc 40041Permitted modesUINT16Read/write0 = Auto (heat and cool); 1 = Cool only; 2 = Heat only; 3 = Manual heat/cool (v2.19+); 4 = Cool-dry / auto-dry (v2.3+); 5 = Cool and dry (v2.3+); 6 = Manual plus cool-dry (v2.3+)
HR53doc 40054Day/night modeTwo-setpoint manual mode only.UINT16Read/write0 = Night; 1 = Day
HR54doc 40055Firmware revisionUINT16Read
HR56doc 40057Remote off statusUINT16Read0 = Mode selected by user; 1 = Held off remotely
HR57doc 40058Start/stop mode overrideCommercial programmable mode only.UINT16Read/write0 = Normal schedule; 1 = Locked to start program; 2 = Locked to stop program
HR59doc 40060Baud rateChanging it disconnects the unit from the current network.UINT16Read/write1 = 4800; 2 = 9600; 3 = 19200
HR61doc 40062Coil override modeWrite 1 at least every 4 minutes to keep Modbus control of the relays (v2.2+).UINT16Read/write0 = Thermostat controls relays; 1 = Modbus controls relays
HR67doc 40068ParityFirmware 2.31+.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR69doc 40070TT input statusFirmware 2.2+.UINT16Read0 = Open; 1 = Shorted
HR317doc 40318Active set temperatureCurrent active setpoint. °C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead
HR318doc 40319Active cooling set temperature°C = (raw - 20) / 2.UINT16× 0.5 − 10°CRead
HR346doc 40347Room minus set temperature100 = equal; each count is 0.1 °C above (+) or below (-) the setpoint (v2.19+).UINT16Read
HR349doc 40350Raw room temperatureFast-updating sensor value, (raw - 400) / 10 (v2.17+).UINT16× 0.1 − 40°CRead
HR353doc 40354Displayed room temperatureValue shown on the LCD, (raw - 400) / 10 (v2.17+).UINT16× 0.1 − 40°CRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)

What Modbus registers does the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) have?

This map lists 35 registers: 5 coils, 30 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coils are printed 00001-00005 and holding registers 40002 upward (Modicon references); subtract 1 (coils) or 40001 (holding registers) for the wire address.

What are the minimum Modbus registers to integrate the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)?

Start with HR 353 Displayed room temperature (Room temperature (0.1 °C)); HR 317 Active set temperature (Active setpoint); HR 1 Thermostat mode (Thermostat mode); HR 2 Fan mode (Fan mode); HR 14 Single set point (manual mode) (Single setpoint (manual mode)); CO 0 G1 relay (G1 fan relay).

How do I enable Modbus control of the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)?

Set the thermostat address in the installer menu (item AD, default 7); 9600 8N1 by default. A paired EC-02 copies address and baud from the thermostat.

What happens when the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) loses Modbus communication?

Coil override (40062) falls back to thermostat control after about 5 minutes without Modbus or after a power loss; refresh it at least every 4 minutes.

Where is the official Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus documentation?

The source is SMT-770 / EC-02 Communications Addendum (Version 4.6 (firmware 2.31, 1/03/12)). Smart Temp doesn't publish it on its own website, so this map was re-typed from a free copy at https://digitalassets.reecegroup.com.au/m/b5ba7cc34ddc69cd/original/Modbus-Smart-Temp-SMT-770-Chameleon-Multifunction-Thermostat.pdf. It may be an older revision, so check it against the live unit.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SMT-770 / EC-02 Communications Addendum · Version 4.6 (firmware 2.31, 1/03/12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.