- SMT-770 thermostat with EC-02 module (Modbus RTU)
Thermostat · Modbus register map
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus register map
Updated 17 November 2026
The Smart Temp SMT-770 is an Australian 24 V multifunction thermostat with an RS-485 Modbus RTU port; a paired EC-02 output module appears as the same device. This map covers relay coils, thermostat and fan modes, set temperatures, room temperature, network settings and the coil override.
This page lists 35 Modbus registers for the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Smart Temp’s own free documentation (linked below) and checked against it.
- Manufacturer
- Smart Temp
- Model
- SMT-770 thermostat with EC-02 module (Modbus RTU)
- Equipment type
- Thermostat
- Registers
- 35 (25 writable)
- Transport
- Modbus RTU
- Default unit ID
- 7
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 2.31 (addendum v4.6)
- Also known as
- SMT-770 Chameleon, EC-02, SMT770
Integration notes: Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
Read 40354 for the room temperature shown on the display and 40318 for the active setpoint; write mode (40002), fan (40003) and setpoints (40005/40006 or 40015 depending on DIP mode).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 353 | Displayed room temperature | UINT16 | Room temperature (0.1 °C) | Read |
| HR 317 | Active set temperature | UINT16 | Active setpoint | Read |
| HR 1 | Thermostat mode | UINT16 | Thermostat mode | Read/write |
| HR 2 | Fan mode | UINT16 | Fan mode | Read/write |
| HR 14 | Single set point (manual mode) | UINT16 | Single setpoint (manual mode) | Read/write |
| CO 0 | G1 relay | BIT | G1 fan relay | Read/write |
Enable Modbus control & writes
Set the thermostat address in the installer menu (item AD, default 7); 9600 8N1 by default. A paired EC-02 copies address and baud from the thermostat.
Communication loss & watchdog
Coil override (40062) falls back to thermostat control after about 5 minutes without Modbus or after a power loss; refresh it at least every 4 minutes.
Byte order & addressing
- Celsius setpoints are (raw - 20) / 2.
- Registers 40350/40354 are (raw - 400) / 10.
Network setup
- Only the last device on the bus gets the EOL resistor; with a paired EC-02, terminate at the EC-02, not the thermostat.
- Up to 32 thermostats per segment.
Watch out for
- Writes that conflict with the DIP-switch mode are silently ignored.
- Changing baud (40060) or parity (40068) over Modbus drops the device off the current network.
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | G1 relay | Writable from firmware 2.19; see coil override 40062. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 1doc 00002 | G2/Y2 relay | Writable from firmware 2.19; see coil override 40062. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 2doc 00003 | G3/W2/OB relay | Writable from firmware 2.19; see coil override 40062. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 3doc 00004 | Y1 relay | Writable from firmware 2.19; see coil override 40062. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 4doc 00005 | W1 relay | Writable from firmware 2.19; see coil override 40062. | BIT | Read/write | 0 = Off; 1 = On | |||
| HR | 1doc 40002 | Thermostat mode | UINT16 | Read/write | 0 = Off; 2 = Heat only; 3 = Cool only; 4 = Auto changeover; 5 = Emergency heat; 6 = Cool and dry (v2.3+); 7 = Auto and dry (v2.3+) | ||||
| HR | 2doc 40003 | Fan mode | UINT16 | Read/write | 0 = Auto (cycles with heat/cool); 1 = On | ||||
| HR | 3doc 40004 | Program hold | Only in residential programmable mode (DIP 6 and 8 on). | UINT16 | Read/write | 0 = Off; 1 = Temporary hold; 2 = Permanent hold | |||
| HR | 4doc 40005 | Heat set temperature (hold) | Two-setpoint modes. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 5doc 40006 | Cool set temperature (hold) | Two-setpoint modes. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 9doc 40010 | Fan speed | Needs 3-speed fan DIP setting. | UINT16 | Read/write | 1 = Low; 2 = Medium; 3 = High; 4 = Auto | |||
| HR | 10doc 40011 | Day cool set temperature | 255 = off. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 11doc 40012 | Day heat set temperature | 0 = off. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 12doc 40013 | Night cool set temperature | 255 = off. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 13doc 40014 | Night heat set temperature | 0 = off. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 14doc 40015 | Single set point (manual mode) | DIP 6 and 8 off. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read/write | ||
| HR | 18doc 40019 | Current running program | UINT16 | Read | 0 = Manual mode; 1 = Program event 1; 2 = Program event 2; 3 = Program event 3; 4 = Program event 4; 5 = Start event; 6 = Stop event | ||||
| HR | 19doc 40020 | Sentinel point | Identifies an SMT-770: 77 before firmware 2.17, 78 from 2.17. | UINT16 | Read | ||||
| HR | 21doc 40022 | Modbus address | 1-32; the network must follow a change. | UINT16 | Read/write | ||||
| HR | 23doc 40024 | Temperature display mode | UINT16 | Read/write | 0 = Room and set temperature; 1 = Set temperature only | ||||
| HR | 28doc 40029 | Display units | UINT16 | Read/write | 0 = °F; 1 = °C | ||||
| HR | 40doc 40041 | Permitted modes | UINT16 | Read/write | 0 = Auto (heat and cool); 1 = Cool only; 2 = Heat only; 3 = Manual heat/cool (v2.19+); 4 = Cool-dry / auto-dry (v2.3+); 5 = Cool and dry (v2.3+); 6 = Manual plus cool-dry (v2.3+) | ||||
| HR | 53doc 40054 | Day/night mode | Two-setpoint manual mode only. | UINT16 | Read/write | 0 = Night; 1 = Day | |||
| HR | 54doc 40055 | Firmware revision | UINT16 | Read | |||||
| HR | 56doc 40057 | Remote off status | UINT16 | Read | 0 = Mode selected by user; 1 = Held off remotely | ||||
| HR | 57doc 40058 | Start/stop mode override | Commercial programmable mode only. | UINT16 | Read/write | 0 = Normal schedule; 1 = Locked to start program; 2 = Locked to stop program | |||
| HR | 59doc 40060 | Baud rate | Changing it disconnects the unit from the current network. | UINT16 | Read/write | 1 = 4800; 2 = 9600; 3 = 19200 | |||
| HR | 61doc 40062 | Coil override mode | Write 1 at least every 4 minutes to keep Modbus control of the relays (v2.2+). | UINT16 | Read/write | 0 = Thermostat controls relays; 1 = Modbus controls relays | |||
| HR | 67doc 40068 | Parity | Firmware 2.31+. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 69doc 40070 | TT input status | Firmware 2.2+. | UINT16 | Read | 0 = Open; 1 = Shorted | |||
| HR | 317doc 40318 | Active set temperature | Current active setpoint. °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read | ||
| HR | 318doc 40319 | Active cooling set temperature | °C = (raw - 20) / 2. | UINT16 | × 0.5 − 10 | °C | Read | ||
| HR | 346doc 40347 | Room minus set temperature | 100 = equal; each count is 0.1 °C above (+) or below (-) the setpoint (v2.19+). | UINT16 | Read | ||||
| HR | 349doc 40350 | Raw room temperature | Fast-updating sensor value, (raw - 400) / 10 (v2.17+). | UINT16 | × 0.1 − 40 | °C | Read | ||
| HR | 353doc 40354 | Displayed room temperature | Value shown on the LCD, (raw - 400) / 10 (v2.17+). | UINT16 | × 0.1 − 40 | °C | Read |
Notes on this map
- This copy is hosted by the distributor Reece; it is the Smart Temp SMT-770 / EC-02 Communications Addendum, version 4.6.
- Set temperatures in Celsius mode are stored as (°C x 2) + 20, so value = raw x 0.5 - 10; in Fahrenheit mode the raw value is °F directly. The map shows the Celsius scaling; check 40029.
- Left out: 40310/40313/40316 room and outside-air temperatures, whose Celsius formula is printed two ways (subtract 20 or subtract 80); register 4021 (security PIN, address misprinted); the second 40318 row (heating set temperature, duplicate address); the TT temperature 40356, whose label says °F while its range is in °C; schedule registers 40513 upward.
- Many registers only act in particular DIP-switch modes (DIP 6/8 select manual, two-setpoint, commercial or residential programmable). Writing values that conflict with the DIP settings is ignored.
- Factory Modbus address is 7. The addendum warns that writing unlisted registers can corrupt the thermostat setup.
- The addendum prints 40318 twice (active set temperature, then heating set temperature after 40319). This map keeps the first, in-sequence 40318 as the active setpoint; confirm on site.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
What Modbus registers does the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) have?
This map lists 35 registers: 5 coils, 30 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coils are printed 00001-00005 and holding registers 40002 upward (Modicon references); subtract 1 (coils) or 40001 (holding registers) for the wire address.
What are the minimum Modbus registers to integrate the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)?
Start with HR 353 Displayed room temperature (Room temperature (0.1 °C)); HR 317 Active set temperature (Active setpoint); HR 1 Thermostat mode (Thermostat mode); HR 2 Fan mode (Fan mode); HR 14 Single set point (manual mode) (Single setpoint (manual mode)); CO 0 G1 relay (G1 fan relay).
How do I enable Modbus control of the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)?
Set the thermostat address in the installer menu (item AD, default 7); 9600 8N1 by default. A paired EC-02 copies address and baud from the thermostat.
What happens when the Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) loses Modbus communication?
Coil override (40062) falls back to thermostat control after about 5 minutes without Modbus or after a power loss; refresh it at least every 4 minutes.
Where is the official Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU) Modbus documentation?
The source is SMT-770 / EC-02 Communications Addendum (Version 4.6 (firmware 2.31, 1/03/12)). Smart Temp doesn't publish it on its own website, so this map was re-typed from a free copy at https://digitalassets.reecegroup.com.au/m/b5ba7cc34ddc69cd/original/Modbus-Smart-Temp-SMT-770-Chameleon-Multifunction-Thermostat.pdf. It may be an older revision, so check it against the live unit.
Other hvac equipment register maps
- Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
All hvac equipment Modbus register maps →
Source: SMT-770 / EC-02 Communications Addendum · Version 4.6 (firmware 2.31, 1/03/12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.